Laserfiche WebLink
_ LDT 5000 Field Test Apparatus Page 1 of 1 <br /> -ipTanknology Line Leak Detector Test <br /> Work Order: 2384340 Date: 6/11/2025 <br /> Site Name/ID. Chevron 212470/212470 <br /> Address: 3400 N MacArthur Drive <br /> City: Tracy State: CA Zip: 95376 <br /> Tank ID 91 87 dsl <br /> Product PREMIUM REG UNLEAD Diesel <br /> Product Line 1 1 1 <br /> Tested From 1 1 1 <br /> Existing/New Existing Existing Existing <br /> Mechanical/Electronic Electronic Electronic Electronic <br /> Manufacturer/Model Vaporless LD-2000 Vaporless LD-2000 Vaporless LD-2000 <br /> Serial No. UNK UNK UNK <br /> Pump Operating Pressure(psi) 40.00 40.00 42.00 <br /> Calibrated Leak(ml/min) 189.0 189.0 189.0 <br /> Calibrated Leak(gph) 3.00 3.00 3.00 <br /> Holding PSI <br /> NIA for Electronic Lo's <br /> Resiliency(ml) <br /> NIA for Electronic Lo's <br /> Metering PSI <br /> NIA for Electronic Lo's <br /> Opening Time(sec) <br /> NIA for Electronic Lo's <br /> Test Results Pass Pass Pass <br /> Technician Comments: <br /> Technician Name: Carlos Zaragoza Certification#: 209437 <br /> Technician Signature: Expire Date: 5/28/2027 <br /> Environmental Compliance for Petroleum Systems <br /> ©2025 Tanknology Inc.,Austin,TX. All rights reserved. tanknology.com <br />