Laserfiche WebLink
A dOAQU1N Environmental Health Department <br /> COUNTY <br /> CP22 - UST FULL Inspection Report <br /> Facility Name: T�7749 <br /> ility Address: Date: <br /> SRH FOOD&GAS INC E DR MARTIN LUTHER KING JR BLVD May 06 2025 <br /> 87 CA Code of Regulations 2060021-Striker plate installed and positioned correctly. ❑OUT ❑R ❑COS <br /> 2631(c),2662(d) <br /> 88 CA Code of Regulations 2060007-Primary and secondary containment designed and constructed to an engineering ❑OUT ❑R ❑COS <br /> 2631(b&d),2666(b&e) specification. <br /> 89 CA Health and Safety 2060008-Enhanced leak detection testing performed before the tank is placed in use ❑OUT ❑R ❑COS <br /> Code 25290.10) <br /> 90 CA Code of Regulations 2060029-SW piping has been upgraded to continuously monitored DW piping when replacement ❑OUT ❑R ❑COS <br /> 2666(b)(2) or repair needed <br /> 91 CA Health and Safety 2010-Administration/Documentation-General ❑OUT ❑R ❑COS <br /> Code 25291(e) <br /> 92 2015-Administrative/Documentation-General Local Ordinance ❑OUT ❑R ❑COS <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 56 CA Code of Regulations 2716(a-e)2030013-DO inspections completed at least every 30 days and meet all <br /> requirements(TCR 12). <br /> OBSERVATION:The designated operator failed to check and note the correct test dates on the designated operator <br /> inspection reports. The correct dates for the Monitoring System Certification, Spill Container and Overfill Prevention <br /> Equipment is 5/28/24.The correct date for the Secondary Containment is 3/14/24. <br /> REGULATION GUIDANCE: During the inspection, the designated operator shall check that all required testing and <br /> maintenance for the UST system have been completed and document the dates they were done. <br /> CORRECTIVE ACTION: This was corrected on site. <br /> This is a repeat violation (Class 2) Violation. <br /> 59 CA Code of Regulations 2712(b)(1-2)2030001 - Records of release detection monitoring and maintenance properly <br /> maintained (TCR 9d). <br /> OBSERVATION: Maintenance and monitoring records for the last three years were not found on site: <br /> -5/23/23 Monitoring System Certification <br /> -5/23/23 Spill Container <br /> -3/14/24 Secondary Containment <br /> REGULATION GUIDANCE:These records shall be maintained on site for at least three years. Monitoring records <br /> include: (1)date and time of all monitoring or sampling; (2)monitoring equipment calibration and maintenance records; <br /> (3)results of any visual observations; (4)results of sample analysis performed a lab or in the field; (5)logs of all <br /> readings of gauges or other monitoring equipment, ground water elevations, or other test results; (6)results of <br /> inventory readings and reconciliations. <br /> CORRECTIVE ACTION: This was corrected on site. <br /> This is a repeat violation (Class 2) Violation. <br /> 77 CA Code of Regulations 2712(f)2030073- Facility has corrected cited violations within 30 days of receiving report. <br /> OBSERVATION:An inspection was last done on 5/28/24 and an inspection report was issued identifying information <br /> to be submitted to bring this site into compliance. This information was required to be submitted by 7/5/24.This <br /> information has not been fully received resulting in a non-compliant status for this facility. <br /> REGULATION GUIDANCE:An operator that receives an inspection report shall have 30 days to implement the <br /> FA0003870 PR0231060 SCO01 05/06/2025 <br /> EHD Rev.12/06/2021 Page 5 of 6 CP22-UST FULL OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />