Laserfiche WebLink
Hazardous Waste Tank System Nov <br /> Written Assessment per CCR Title 22 <br /> Applied Aerospace Structures Inc.34375 South Airport Way,Stockton,CA 95205 2022 <br /> Tank Assessment Page Tank Name/marking: Polymer Mix Tank <br /> Tank age: new <br /> Remaining service life: 25 years, inspect in 5 <br /> years <br /> Tank Construction: <br /> Shape: Cylindrical, flat bottom, covered top <br /> Orientation: Vertical <br /> Location (above/below ground): Above ground <br /> Material of construction: linear polyethylene <br /> Thickness and method used to determine: 0.2" similarity <br /> Lining material &thickness (if applicable): N. A. <br /> Corrosion Protection equipment: Compatible <br /> Structural support: The tank rests on a coated concrete floor <br /> Other identifying features: Natural <br /> Piping and ancillary equipment (pumps): <br /> Piping Material of Construction: PVC pipe <br /> Piping Diameter: 1" <br /> Pump location(s): within 10 feet of tank, within secondary containment <br /> dike <br /> Pump type(s)/capacities: AODP, 5 gpm <br /> Overfill protection: Direct Operator Observation <br /> Material Storage: <br /> Material and characteristics: Water with 0.01 percent anion <br /> polyacrylamide, gras. <br /> Specific Gravity: 1 <br /> Tank Capacity: 44 gallons <br /> Strandberg Associates 1(866) 388-0404 john@strandberga <br />