Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST <br /> Test Method Developed by ❑ Manufacturer El Industry Standard ❑ Professional Engineer <br /> Test Type ❑ Pressure ❑ Vacuum El Hydrostatic <br /> Test Equipment Used:OEL8000111-CLD Proteus Series <br /> Sump/UDC ID 87 STP 91 STP Diesel STP <br /> Sump Manufacturer Xerxes Xerxes Xerxes <br /> Sump Depth (inches) 47 47 49 <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration 21 22 22 <br /> (inches) <br /> Test Start Time 10:20 10:20 10:20 <br /> Initial Reading 6.988 16.152 8.252 <br /> Test End Time 10:35 10:35 10:35 <br /> Final Reading 6.987 16.152 8.252 <br /> Change in Reading 0.001 0.000 0.000 <br /> Pass/Fail Criteria +i-0.002 +i-0.002 +i-0.002 <br /> Tightness Test Results p Pass ❑ Fail El Pass ❑ Fail 0 Pass ❑ Fail ❑ Pass ❑ Fail <br /> Sump/UDC ID UDC 1-2 UDC 3-4 UDC 5-6 <br /> Sump Manufacturer Bravo Bravo Bravo <br /> Sump Depth (inches) 9 9 9 <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration Bottom Bottom Bottom <br /> (inches) <br /> Test Start Time 11:58 11:58 11:58 <br /> Initial Reading 1.738 6.048 4.914 <br /> Test End Time 12:13 12:13 12:13 <br /> Final Reading 1.738 6.048 4.914 <br /> Change in Reading 0.000 0.000 0.000 <br /> Pass/Fail Criteria +i-0.002 +i-0.002 +i-0.002 <br /> Tightness Test Results El Pass ❑ Fail El Pass ❑ Fail El Pass ❑ Fail ❑ Pass ❑ Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail'and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 3 of 5 <br />