Laserfiche WebLink
Mechanical Leak Detector Test Data Sheet <br /> Site Name CA Army National Guard Date 2025-07-29 <br /> Address 2000 Stimson Rd <br /> Stockton 95206 <br /> Test Information <br /> 1 2 3 4 5 <br /> Product Jet A <br /> Manufacturer VM1 <br /> Model 99LD-3000 <br /> Full Operating Pressure (PSI) 40 <br /> Line Bleed Back (mL) 1000 <br /> Trip Time (sec) <br /> Metering Pressure (PSI) 22 <br /> F/E Holding Pressure (PSI) 35 <br /> Test Leak Rate (ml/min)(gph) 189 <br /> PASS or FAIL Pass <br /> Comments <br /> This letter certifies that the annual leak detector tests were performed at the above referenced facility <br /> according to the equipment manufacturers procedures and limitations and the results as listed are to <br /> my knowledge true and correct. The mechanical leak detector test pass/fail <br /> is determined using a low flow threshold trip rate of 3 gph at 10 PSI. <br /> Inspected By: Contractor SunWest Engineering Constructors <br /> Technician Ruben Becerra Lic#5302139 <br /> Signature <br />