Laserfiche WebLink
SAN JOAQUIN Environmental Health Department <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name; Facility Phone: Data: <br /> PARKWOODS GAS & FOOD '�J'J 1 I May 30 2025 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> hem# Remarks <br /> CA Code of Regulations 2632(d)(1),2634(d)2010013-Facility has submitted a complete and accurate UST <br /> Monitoring Plan. <br /> OBSERVATION:The monitoring plan is not current and/or not approved by the EHD. <br /> -The monitoring plan states that the floats and chains were located in UDC's 5/6 and 7/8.The floats and chains were <br /> observed to be located in UDC's 112 and 3/4. <br /> -The monitoring plan states that the 208 sensors were located in UDC's 1/2 and 3/4.The 208 sensors were observed to <br /> be located in UDC's 5/6 and 7/8. <br /> REGULATION GUIDANCE:The monitoring plan must be uploaded to the California Environmental Reporting System <br /> (CERS). <br /> CORRECTIVE ACTION: Immediately log into CERS,make the necessary changes,and submit for review by the EHD. <br /> T�s is a Repeat(Class 2)Violation. <br /> CA Code of Regulations 2715(a)(1xB),2715(a)(3)2010003-Owner/Operator submitted DO form and/or informed the <br /> CUPA of any change(s)within 30 days(TCR 10) <br /> OBSERVATION:A new designated operator, David Winkler, began conducting inspections on 3/5/25 and notification <br /> Jwas not provided to the END within 30 days of the change. <br /> REGULATION GUIDANCE:The owner or operator shall submit a"Designated Underground Storage Tank Operator <br /> Identification Form"no later than 30 days after any change in the designated UST operator(s). <br /> CORRECTIVE ACTION: Immediately log into the California Environmental Reporting System (CERS)at <br /> httpJ/cers.calepa.ca.gov and upload the notification identifying all the designated operators for this facility. <br /> This is a Repeat(Class 2)Violation. <br /> 53 CA Health and Safety Code 25292.2;CCR 2711(a)(11)2010007-Submitted/maintained current Cert of Financial <br /> Responsibility/mech of financial assurance(TCR 11) <br /> OBSERVATION:Current financial responsibility documents(dated 50/25)were not found on site. <br /> JREGULATION GUIDANCE:A copy of current financial responsibility documents are required to be maintained on site. <br /> CORRECTIVE ACTION: Immediately obtain a copy of the facility's financial responsibility documents and maintain a <br /> copy on site. <br /> This is a Repeat(Class 2)Violation. <br /> 56 CA Code of Regulations 2716(a-e)2030013-DO inspections completed at least every 30 days and meet all <br /> requirements(TCR 12) <br /> OBSERVATION:Designated operator reports were not signed within the required time frame. <br /> i -The 7/9/24,8/1/24,and 8/28/24 designated operator reports were not signed by the owner/operator. <br /> REGULATORY GUIDANCE:Within 48 hours of the completion of the designated UST operator visual inspection,the <br /> designated operator shall sign and provide the owner or operator with a copy of the inspection report.Within 72 hours of <br /> being provided a signed copy of the report,the owner or operator shall provide a description of each corrective action <br /> taken or to be taken and shall sign and date the report,acknowledging the identified compliance issues. <br /> CORRECTIVE ACTION: Ensure all designated operator inspection reports are completed and signed within the required <br /> time frame in the future. <br /> This is a Repeat(Class 2) Violation. <br /> EHD-CUPA Inspection Report IS01 Page 5 of 6 FA0003611 PRO231127 4513852 5/30/2025 <br /> 1868 E. Hazelton Avenue I Stockton,California 95205 1 T 209 468-3420 1 F 209 464-01 38 1 www.sjgov.org/EHD <br />