Laserfiche WebLink
_ LDT 5000 Field Test Apparatus Page 1 of 1 <br /> Tanknology Line Leak Detector Test <br /> Work Order: 2384587 Date: 7/9/2025 <br /> Site Name/ID: 7-ELEVEN#17647, MKT 2368(N-744)/ 17647 <br /> Address: 1048 W.YOSEMITE AVE @ EL PORTEL <br /> City: MANTECA State: CA Zip: 95336 <br /> Tank ID Regular Premium <br /> Product RUL PUL <br /> Product Line 1 1 <br /> Tested From 4 4 <br /> Existing/New Existing Existing <br /> Mechanical/Electronic Mechanical Mechanical <br /> Manufacturer/Model Veeder Root FX1V Veeder Root FX1V <br /> Serial No. 11002 6195 116056 40710 4609 11605 <br /> Pump Operating Pressure(psi) 29.00 28.00 <br /> Calibrated Leak(ml/min) 189.0 189.0 <br /> Calibrated Leak(gph) 3.00 3.00 <br /> Holding PSI 21.00 20.00 <br /> N/A for Electronic LD's <br /> Resiliency(ml) 130.00 130.00 <br /> N/A for Electronic LD's <br /> Metering PSI 11 11 <br /> N/A for Electronic LD's <br /> Opening Time(sec) 2 2 <br /> N/A for Electronic LD's <br /> est Results Pass Pass <br /> Technician Comments: <br /> Technician Name: Carlos Zaragoza Certification#: 209437 <br /> Technician Signature: Expire Date: 5/28/2027 <br /> Environmental Compliance for Petroleum Systems <br /> ©2025 Tanknology Inc.,Austin,TX. All rights reserved. tanknology.com <br />