Laserfiche WebLink
■_irTankn log y <br />Work Order: 2385980 <br />Site Name/ID: Fed Ex Ground / 953 <br />Product Line Tightness Test <br />Date: 9/26/2025 <br />Address: 5655 Hood Way <br />City: Tracy State: CA <br />Zip: 95377 <br />Page 1 of 1 <br />Tank Information <br />Tank # 1 <br />Line # 1 <br />Tank # 2 <br />Line # 1 <br />Tank # <br />Line # <br />Tank # <br />Line # <br />Tank # <br />Line # <br />Tank # <br />Line # <br />Test Method <br />TLD -1 <br />TLD -1 <br />Customer Tank ID <br />T-1 <br />T-2 <br />Product Name <br />Diesel <br />Diesel <br />Delivery Type <br />Pressure <br />Pressure <br />Test Pressure (psi) <br />60 <br />60 <br />Test Start Time <br />09:15 <br />09:15 <br />Test End Time <br />09:45 <br />09:45 <br />Final Leak Rate (gph) <br />0.00 <br />0.00 <br />Test Result(P/F/1) <br />Pass <br />Pass <br />Test was performed per <br />3rd party certifications as <br />specified in 40 CFR parts <br />280 and 281 <br />Yes <br />Yes <br />Technician Comments: <br />Technician Name: Brent Bowen <br />Technician Signature: <br />Certification #: 99942 exp:10/19/2028 <br />Environmental Compliance for Petroleum Systems <br />©2025 Tanknology Inc., Austin, TX. All rights reserved. tanknology.com <br />