Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST <br /> Test Method Developed by ❑ Manufacturer El Industry Standard ❑ Professional Engineer <br /> Test Type ❑ Pressure ❑ Vacuum El Hydrostatic <br /> Test Equipment Used:Incon TS-STS tester <br /> Sump/UDC ID 87 STP 91 STP UDC 1/2 UDC 3/4 <br /> Sump Manufacturer Fiberglass Fiberglass Bravo Bravo <br /> Sump Depth (inches) 712 72" 12" 12" <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration 202 21°° Bottom Bottom <br /> (inches) <br /> Test Start Time 12:42 pm 12:21 pm 11:46 pm 11:46 pm <br /> Initial Reading 3.9616 4.1650 2.2815 1.5740 <br /> Test End Time 12:57 pm 12:36 pm 12:01 pm 12:01 pm <br /> Final Reading 3.9617 4.1648 2.2813 1.5736 <br /> Change in Reading 0.0001 0.0002 0.0002 0.0004 <br /> Pass/Fail Criteria 0.0020 0.0020 0.0020 0.0020 <br /> Tightness Test Results 0 Pass ❑ Fail El Pass ❑ Fail 0 Pass ❑ Fail 0 Pass ❑ Fail <br /> Sump/UDC ID <br /> Sump Manufacturer <br /> Sump Depth (inches) <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time <br /> Initial Reading <br /> Test End Time <br /> Final Reading <br /> Change in Reading <br /> Pass/Fail Criteria <br /> Tightness Test Results ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail"and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 3 of 5 <br />