Laserfiche WebLink
Underground Storage Tank <br /> Monitoring System Certification Form <br /> 7. LINE LEAK DETECTOR TESTING <br /> El Check this box if line leak detectors ARE NOT installed. (Do not complete this section.) <br /> Simulated release rate verified: (Check all that apply.) Yes No NA <br /> 0 3 GPH 0 0.1 GPH rj 0.2 GPH I <br /> Has the testing apparatus been properly calibrated? <br /> For emergency generator tank systems, does the LLD create an audible and visual Fr 0 0 <br /> alarm when a leak is detected? <br /> For mechanical LLDs, does the LLD restrict the flow through the pipe when a <br /> release is detected? <br /> For electronic LLDs, does the turbine automatically shut off when a release is ri <br /> detected? <br /> For electronic LLDs, does the turbine automatically shut off if any portion of the <br /> monitoring system is disabled or disconnected? <br /> For electronic LLDs, does the turbine automatically shut off if any portion of the M FM FM <br /> monitoring system malfunctions or fails a tightness test? <br /> For electronic LLDs, have all accessible wiring connections been visually inspected M In ri <br /> for kinks and breaks? <br /> Were all items on the equipment manufacturer's maintenance checklist completed? M rl FM <br /> Were all LLDs confirmed operational within regulatory requirements? ri 10 1 <br /> LLD ID LLD Model Lines Monitored Pass Fail <br /> Q1 848480 87 <br /> Q2 848480 91 <br /> ri ri <br /> ri M <br /> ri M <br /> Fn M <br /> In <br /> rl In <br /> Describe all answers marked "No" or"Fail"and proposed remedy in Section 9. <br /> List all monitoring equipment either replaced or repaired in Section 9 <br /> Page 4 of 6 <br />