LDT 5000 Field Test Apparatus Page 1 of 1 <br /> ,,�PTanknoiogy Line Leak Detector Test <br /> Work Order: 2383364 Date: 8/4/2025 <br /> Site Name/ID: 7-ELEVEN 38616/38616 <br /> Address: 601 Carolyn Weston Blvd <br /> City: Stockton State: CA Zip: 95206 <br /> Tank ID Regular PREMIUM DSL <br /> Product REGULAR PREMIUM Diesel <br /> Product Line 1 1 1 <br /> Tested From 10 10 10 <br /> Existing/New Existing Existing Existing <br /> Mechanical/Electronic Mechanical Mechanical Mechanical <br /> Manufacturer/Model Vaporless LD-2000 Vaporless LD-2000 Vaporless LD-2000 <br /> Serial No. U.R. U.R. U.R. <br /> Pump Operating Pressure(psi) 32.00 40.00 40.00 <br /> Calibrated Leak(ml/min) 189.0 189.0 189.0 <br /> Calibrated Leak(gph) 3.00 3.00 3.00 <br /> Holding PSI 32.00 40.00 40.00 <br /> *N/A for Electronic LD's <br /> Resiliency(ml) 140.00 160.00 180.00 <br /> *N/A for Electronic LD's <br /> Metering PSI 16 18 18 <br /> *N/A for Electronic LD's <br /> Opening Time(sec) 9 10 9 <br /> *N/A for Electronic LD's <br /> Test Results Pass Pass Pass <br /> Technician Comments: <br /> Technician Name: Jesus Saldivar Certification#: 115237 <br /> Technician Signature: Expire Date: 10/22/2027 <br /> Environmental Compliance for Petroleum Systems <br /> ©2025 Tanknology Inc.,Austin,TX. All rights reserved. tanknology.com <br />