SANsJOAQUIN Environmental Health Department <br /> COUNTY <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: TAuqust <br /> ate: <br /> Frontier California Inc.: Manteca CO 1430 W Center ST, Manteca 05, 2025 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I, CLASS II, or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 25 CA Code of Regulations 2631(g), 2632(c)(2) 2030016 -Annular space of USTs are continuously monitored with an <br /> audible and visual alarm system (TCR 9d) <br /> OBSERVATION: The diesel annular sensor failed to activate an audible and visual alarm when tested and, therefore, the <br /> tank is not monitored. <br /> REGULATION GUIDANCE: The interstitial space shall be monitored with a monitoring system connected to an audible <br /> and visual alarm system. <br /> CORRECTIVE ACTION: Corrected on-site. The sensor was replaced and retested during the inspection. <br /> This is a Repeat(Class 2)Violation. <br /> 53 CA Health and Safety Code 25292.2; CCR 2711(a)(11) 2010007 - Submitted/maintained current Cert of Financial <br /> Responsibility/mech of financial assurance (TCR 11) <br /> OBSERVATION: Current financial responsibility documents were not found on site. Financial responsibility documents <br /> observed on-site were dated 6/27/2024. <br /> REGULATION GUIDANCE: A copy of current financial responsibility documents are required to be maintained on site. <br /> CORRECTIVE ACTION: Corrected on-site. Current copy of financial responsibility documents were printed during <br /> inspection. <br /> This is a Repeat(Class 2)Violation. <br /> 59 CA Code of Regulations 2712(b)(1-2) 2030001 - Records of release detection monitoring and maintenance properly <br /> maintained (TCR 9d) <br /> OBSERVATION: Maintenance and monitoring records for the last three years were not found on site. The monitoring <br /> system certification and spill container test results were not observed for 2022. <br /> REGULATION GUIDANCE: These records shall be maintained on site for at least three years. Monitoring records <br /> include: (1)date and time of all monitoring or sampling; (2) monitoring equipment calibration and maintenance records; <br /> (3) results of any visual observations; (4) results of sample analysis performed a lab or in the field; (5) logs of all readings <br /> of gauges or other monitoring equipment, ground water elevations, or other test results; (6) results of inventory readings <br /> and reconciliations. <br /> CORRECTIVE ACTION: Corrected on-site. Missing monitoring system certification and spill container test results for <br /> 2022 were printed at the time of inspection. <br /> This is a Repeat(Class 2)Violation. <br /> 67 CA Code of Regulations 2712(i) 2030078 - Owner/Operator retained a paper or electronic copy of the permit to operate <br /> at the facility <br /> OBSERVATION: A current copy of the UST operating permit was not found on site. The most recent permit on site was <br /> dated 2023. <br /> REGULATION GUIDANCE: A copy of the UST operating permit and all attachments and conditions shall be retained at <br /> the facility. <br /> CORRECTIVE ACTION: Immediately obtain a copy of the 2025 permit and retain it on site. <br /> This is a Repeat(Class 2)Violation. <br /> EHD-CUPA Inspection Report IS02 Page 5 of 6 FA0003838 PR0231425 4533111 8/5/2025 <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />