Laserfiche WebLink
_LDT 5000 Field Test Apparatus <br />Tanknology Line Leak Detector Test <br />Work Order: <br />Site Name / ID. <br />Address: <br />City: <br />2384685 <br />CHEVRON 99280 / 385102 <br />1222 W Atherton <br />Manteca <br />Date: 8/18/2025 <br />State: CA <br />Page 1 of 1 <br />Zip: 95337 <br />Tank ID <br />REGULAR <br />PREMIUM <br />DIESEL <br />Product <br />REGULAR <br />PREMIUM <br />Biodiesel <br />Product Line <br />1 <br />1 <br />1 <br />Tested From <br />2 <br />2 <br />2 <br />Existing/New <br />Existing <br />Existing <br />Existing <br />Mechanical/Electronic <br />Electronic <br />Electronic <br />Electronic <br />Manufacturer/Model <br />Veeder Root PLLD <br />Veeder Root PLLD <br />Veeder Root PLLD <br />Serial No. <br />LINK <br />LINK <br />LINK <br />Pump Operating Pressure (psi) <br />40.00 <br />40.00 <br />40.00 <br />Calibrated Leak (ml/min) <br />189.0 <br />189.0 <br />189.0 <br />Calibrated Leak (gph) <br />3.00 <br />3.00 <br />3.00 <br />Holding PSI <br />NIA for Electronic Lo's <br />Resiliency (ml) <br />NIA for Electronic Lo's <br />Metering PSI <br />NIA for Electronic Lo's <br />Opening Time (sec) <br />NIA for Electronic Lo's <br />Test Results <br />Pass <br />Pass <br />Pass <br />Technician Comments: <br />Technician Name: <br />Technician Signature: <br />Carlos Zaragoza Certification #: 209437 <br />Environmental Compliance for Petroleum Systems <br />© 2025 Tanknology Inc., Austin, TX. All rights reserved. tanknology.com <br />Expire Date: 5/28/2027 <br />