My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
COMPLIANCE INFO_2025
EnvironmentalHealth
>
EHD Program Facility Records by Street Name
>
F
>
FREMONT
>
2285
>
2300 - Underground Storage Tank Program
>
PR0231111
>
COMPLIANCE INFO_2025
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
2/1/2026 12:24:56 PM
Creation date
8/1/2025 4:48:19 PM
Metadata
Fields
Template:
EHD - Public
ProgramCode
2300 - Underground Storage Tank Program
File Section
COMPLIANCE INFO
FileName_PostFix
2025
RECORD_ID
PR0231111
PE
2361 - UST FACILITY
FACILITY_ID
FA0001659
FACILITY_NAME
QUIK STOP MARKET #039
STREET_NUMBER
2285
Direction
E
STREET_NAME
FREMONT
STREET_TYPE
ST
City
STOCKTON
Zip
95205
APN
14121403
CURRENT_STATUS
Active, billable
QC Status
Approved
Scanner
SJGOV\kblackwell
Supplemental fields
Site Address
2285 E FREMONT ST STOCKTON 95205
Tags
EHD - Public
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
32
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
A dOAQU1N Environmental Health Department <br /> COUNTY <br /> CP22 - UST FULL Inspection Report <br /> Facility Name: Facility Address: Date: <br /> QUIK STOP MARKET#039 2285 E FREMONT ST STOCKTON August 04 2025 <br /> 87 CA Code of Regulations 2060021-Striker plate installed and positioned correctly. ❑OUT ❑R ❑COS <br /> 2631(c),2662(d) <br /> 88 CA Code of Regulations 2060007-Primary and secondary containment designed and constructed to an engineering ❑OUT ❑R ❑COS <br /> 2631(b&d),2666(b&e) specification. <br /> 89 CA Health and Safety 2060008-Enhanced leak detection testing performed before the tank is placed in use ❑OUT ❑R ❑COS <br /> Code 25290.10) <br /> 90 CA Code of Regulations 2060029-SW piping has been upgraded to continuously monitored DW piping when replacement ❑OUT ❑R ❑COS <br /> 2666(b)(2) or repair needed <br /> 91 �CA Health and Safety 12010-Administration/Documentation-General ■OUT ■R ■COS <br /> Code 25291(e) <br /> 92 2015-Administrative/Documentation-General Local Ordinance ❑OUT ❑R ❑COS <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 21 CA Code of Regulations 2637, 2638(e), 2643(g)2030064- CUPA was notified within 48 hours prior to testing. <br /> OBSERVATION11 87 annular sensor repaired performed on 5/2/2025 without providing notification to the EHD at least <br /> 48 hours in advance. <br /> REGULATION GUIDANCE: Notification shall be provided to the CUPA at least 48 hours in advance of testing. <br /> CORRECTIVE ACTION: The EHD will not accept these results and testing must be rescheduled with a 48-hour <br /> notification. Immediately schedule these tests and provide 48 hours notification to the EHD. <br /> This is (Class 2)Violation. <br /> 45 CA Code of Regulations 2636(f)(2)2030025-LLD on DW press piping monitors hrly, detects a 3.0 gph leak, and <br /> restricts/shuts off flow(TCR 9d). <br /> OBSERVATION:The 91 VMI line leak detector failed to detect a leak when tested. <br /> REGULATION GUIDANCE:All line leak detectors shall be capable of detecting a 3-gallon per hour leak at 10 psi. <br /> CORRECTIVE ACTION: The service technician adjusted the leak detector, retested it, and it passed. <br /> This is a repeat violation (Class 2) Violation. <br /> 56 CA Code of Regulations 2716(a-e)2030013-DO inspections completed at least every 30 days and meet all <br /> requirements(TCR 12). <br /> OBSERVATION:The designated operator failed to document all the alarms from the attached alarm history on the <br /> August, June, and July designated operator inspection report and failed to check that they were responded to <br /> appropriately. The missing alarms include: Overfill alarms August 1st, 2025; July 1, 2025; June 28,2025 <br /> REGULATION GUIDANCE: During the inspection,the designated operator shall review the alarm history since the <br /> previous inspection, check that each alarm was documented and responded to appropriately, and attach a copy of the <br /> alarm history with documentation taken in response to any alarms to the inspection report. <br /> CORRECTIVE ACTION: Ensure that designated operators performing inspections at this facility are including all of the <br /> required information on the reports. <br /> This is a repeat violation (Class 2) Violation. <br /> FA0001659 PR0231111 SCO01 08/04/2025 <br /> EHD Rev.12/06/2021 Page 5 of 6 CP22-UST FULL OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />
The URL can be used to link to this page
Your browser does not support the video tag.