Laserfiche WebLink
JONES COVEY GROUP, INC, <br /> COMPLETE FUEL SYSTEM CONSTRUCTION Et MAINTENANCE SERVICES <br /> MECHANICAL j ELECTRONIC LEAK DETECTOR CERTIFICATION <br /> SITE: Pilot 1017 Lathrop DATE: 8/26/2025 <br /> State Facility# CONTACT: Manager <br /> 1017 PHONE: (865) 588-7488 <br /> JOB#: 2598439-1-1 <br /> Tank # T1 Unleaded T2 Premium <br /> Product Unleaded Premium <br /> LD Manufacturer VMI VMI <br /> LD Model 99 LD-2000 99 LD-2000 <br /> Sump Condition Good Good <br /> Operation Pressure 40 PSI 36 PSI <br /> PSI <br /> Opening Time(Sec) 6 Seconds 5Seconds <br /> Metering Pressure <br /> 20 PSI 18 PSI <br /> (PSI) <br /> Functional Element 31 PSI <br /> Holding Pressure 26 PSI <br /> Leak Rate LD Detected 3 GPH 3 GPH <br /> (GPH) <br /> Does LD Detect 3 GPH Yes Yes <br /> Leak Rate? <br /> LD Serial 21121517 18031473 <br /> Comments: <br /> Technician Keith Henderson License Number VMI -3248 <br /> Signature 'eA <br /> 9595 LUCAS RANCH ROAD, RANCHO CUCAMONGA, CA 91730- LICENSED IN 41 STATES <br /> California State License#804431 A, B, HAZ <br />