Laserfiche WebLink
_ VEEDER-ROOT <br />Hour (LPH) and 0.2 GPH/0.76 LPH, and a pressure decay test to meet the U.S. Environmental <br />Protection Agency (EPA) EPA 3.0 GPH/11.4 LPH test requirements. DPLLD offers flexible testing <br />and digital reporting options, helping to detect catastrophic Maks. When paired with a TLS <br />450PLUS Automatic Tank Gauge (ATG), customers can monitor up to 1,178 gallons/4,459 liters <br />of fuel line volume. <br />System Features <br />Equipment Design <br />• Pressure sensor is installed easily without breaking piping or adding a new sump <br />• Stainless steel construction meets the challenges of a highly corrosive environment <br />• Test lines at full pressure for quick and accurate results, without restricting fuel flow rate <br />• Not impacted by thermal contraction of fuel in the line due to changes in temperature <br />System Functionality <br />• Monitors line pressure during dispensing activity to ensure a catastrophic leak is not <br />occurring during a dispense <br />• If a leak is detected at a pre-set pressure threshold, the system will shutoff power to the <br />Submersible Turbine Pump (STP) to minimize environmental damage and help prevent a <br />public safety issue <br />• Conducts test once all dispensing is completed to ensure the integrity of the line <br />