Laserfiche WebLink
NOR T H T R A C Y B O U L E V A R D <br />FUEL S Y S TEM � S I T E PLAN <br />MONITORING NOTES <br />A. THE UNDERGROUND STORAGE TANK lUSTs), TANK SUMPS, VENT TRANSITION /CONTAINMENT SUMP, AND <br />UNDER DISPENSER CONTAINMENT (UDC) SUMPS ARE ALL DOUBLE WALLED, WITH LIQUID FILLED INTERSTICE. <br />HYDROSTATICALLY MONITORED, ALL SUMPS ARE ALSO MONITORED BY A LIQUID SENSING PROBE LL/IN <br />EACH SUMP. <br />B. THE PIPING 15 ALL DOUBLE WALLED, WITH A VACUUM FILLED INTERSTICE, WHICH 15 MONITORED FOR THE <br />PRESENCE OF LIQUID AND CHANGES IN THE VACUUM PRESSURE, W/ SENSORS IN THE TURBINE SUMPS, THE <br />VENT PIPING INTERSTICE 15 MANIFOLDED IN THE VENT TRANSITION / CONTAINMENT SUMP AND MONITORED <br />WAIN THE 91 OCTANE GASOLINE SUMP. THE VAPOR RECOVERY PIPING INTERSTICE IS MANIFOLDED AND <br />MONITORED WAIN THE 81 OCTANE GASOLINE SUMP. EACH PRODUCT PIPE INTERSTICE IS MONITORED WAN <br />ITS TURBINE SUMP. <br />C. THE PRESSURIZED PRODUCT PIPING IS MONITORED BY AN ELECTRONIC LINE LEAK DETECTOR LOCATED <br />AT THE SUBMERSIBLE TURBINE RUMP (5TP) MANIFOLD ASSEMBLY, WHICH WILL AUTOMATICALLY SHUT DOWN <br />THE TURBINE IF AN ALARM OCCURS. <br />D. U5Ts ARE EQUIPPED W/ POSITIVE SHUT-OFF DEVICES ON THE FILL TUBES, SET FOR 95. OF TANK CAPACITY, <br />MAX. THE UST* ALSO HAVE AUTOMATIC TANK GAUGES (ATGO WHICH MONITOR CHANGES IN THE LEVEL OF <br />PRODUCT AND WATER IN THE TANKS. ATG* PROVIDE OVERFILL ALARM AND REPORT, ONLY, AT W% OF <br />TANK CAPACITY, W/O STP SHUTDOWN. <br />E. AUTO STP SHUTDOWN WILL OCCUR ON A LIQUID -SENSING PROBE ALARM THAT 15 WAN A SUMP THAT HAS <br />PRESSURIZED PRODUCT PIPING, IE, TURBINE SUMPS AND UDCs. LIQUID -SENSING PROBES WAIN SUMPS THAT <br />HAVE NO PRESSURIZED PRODUCT PIPING, IE. FILL SUMPS AND THE VENT TRANSITION / CONTAINMENT SUMP, <br />MAY ALARM, W/O 5TP SHUTDOWN. VACUUM SENSORS MAY WARN ONLY, W/O 51P SHUTDOLLN, IN THE ABSENCE <br />OF LIQUID DETECTION. LIQUID DETEC7ED'5Y THE VACUUM SENSING SYSTEM WILL ALARM AND SHUT DOWN <br />THE STP, THE HYDROSTATIC PROBE FOR THE UST INTERSTICE MAY ALARM, W/O 5TP SHUTDOWN, PER TL5 <br />SYSTEM PROGRAMMING, <br />F. IN -STATION DIAGNOSTICS (I5D) WILL ALARM AND SHUT DOWN TURBINE FOR CERTAIN DESIGNATED ALARMS, <br />G. AUTO STP SHUTDOWN WILL ALSO OCCUR IF ANY OF THE MONITORING SYSTEM FAILS OR IS DISCONNECTED. <br />FUEL SYSTEM KEYNOTES <br />I. NEW UNDERGROUND STORAGE TANKS (UST*). DOUBLE-WALL FIBERGLASS REINFORCED PLASTIC,(FRP,) TANKS W/ <br />LIQUID -FILLED ANNULAR/INTER5TICE, BY XERXES. ONE 30K TANK W/ ISK PREM. GASOLINE, 15K 820, ONE 30K <br />TANK W/ 24K REGULAR OCTANE UNLEADED GASOLINE AND 6K E85. 4 <br />2. NEW (N) TANK VENT RISERS ON (N) RI5ER RACK INSTALL LISTED FLEX CONNECTORS AT BASE AND CONNECT TO TANK <br />VENT PIPING, WITHIN (N) DOUBLE -WALLED, LIQUID -FILLED INTERSTICE, CONTAINMENT / TERMINATION SUMP. MANIFOLD <br />GASOLINE VENT RISERS. PROTECT W/ BOLLARDS, MIN. AS $HOUK <br />3. INSTALL NEW VEEDER-ROOT ENHANCED VAPOR RECOVERY (EYR) CARBON CANISTER VAPOR POLISHER (CCVP) SYSTEM <br />A7 MANIFOLDED GASOLINE VENT RISER INSTALL PER MNFR RECOMMENDATIONS AND CURRENT C.A.R13. EXECUTIVE <br />ORDER VR -204-x (REV AD. OR CURRENT). MAINTAIN MATERIAL / EQUIPMENT CLEARANCES PER MNFR INSTALLATION <br />PROCEDURE, <br />4. NEW VACUUM MONITORED, CONTAINED TANK VENT PIPING, FIBERGLASS REINFORCED PLASTIC (FUZP.), MINIMUM PRIMARY <br />PIPE SIZE TO BE 2"0. SLOPE BACK TO TANKS AT 1/8" PER FOOT, MINIMUM, <br />5. NEW DISPENSERS ON NEW DOUBLE -WALLED, LIQUID -FILLED INTERSTICE, UNDER DISPENSER CONTAINMENT (UDC) / SHEAR <br />VALVE SYSTEMS, W/ FLOAT SWITCH SUMP PROBES, TYPICAL. CONFIRM DISPENSING MODELS W/ EQUIPMENT LIST, INSTALL <br />IN -STATION DIAGNOSTICS lI.SD.) VAPOR FLOW METER ABOVE VAPOR SHEAR VALVE, PROVIDE CONDUIT, SEAL -OFFS AND <br />WIRE PER MNFR INSTALLATION PROCEDURES, TYPICAL OF (3) 34Is AND (1) 34 W/ E85. <br />6. INSTALL SINGLE I.S.D. PRESSURE SENSOR AT VENT MANIFOLD (ALT. - IN VAPOR LINE BELOW DISPENSER CLOSEST TO <br />1)570), <br />1. NEW VACUUM MONITORED, CONTAINED PHASE II VAPOR RECOVERY PIPING, F.RP, MINIMUM 31t <br />0 PRIMARY PIPING FROM <br />DISPENSERS TO GASOLINE TANKS, TYPICAL. 2" PRIMARY PIPING OC TO SINGLE DISPENSER SLOPE TO TANKS AT I/8" <br />PER FOOT, MIN. <br />8. NEW VACUUM MONITORED, CONTAINED FRP. PRODUCT PIPE W/ 2110, MINIMUM, PRIMARY PIPE, TYPICAL. SLOPE TO TANKS <br />AT 1/8" PER FOOT, MIN, <br />9. TANK ANNULAR RISER W/ HYDROSTATIC PROBE AND MANWAY, TYPICAL, <br />10. NEW AUTOMATIC TANK GAUGES W/IN TURBINE SUMP, TYPICAL, <br />Il. NEW SUBMERSIBLE TURBINE PUMPS (5TP), TYPICAL, WAN DOUBLE -WALLED, LIQUID -FILLED INTERSTICE, FRP. CONTAINMENT <br />SUMP W/ FLOAT SWITCH SUMP PROBE, LID, AND MANWAY ASSEMBLY, AUTO STP SHUTDOWN ON PROBE ALARM AND IF ANY <br />OF THE MONITORING SYSTEM FAILS OR 15 DISCONNECTED. <br />12. NEW ENHANCED VAPOR RECOVERY (EVR) TANK FILL ASSEMBLY W/ 5 GALLON (MIN.) FILL CONTAINMENT (TYPICAL) <br />AND 5 GALLON (MIN.) CONTAINMENT FOR AT PHASE I VAPOR RECOVERY A7 GA50LINE TANKS (TYPICAL), WAN <br />DOUBLE -WALLED, LIQUID -FILLED INTERSTICE, CONTAINMENT SUMP, W/ FLOAT SWITCH SUMP PROBE, AND MANWAY ASSEMBLY, <br />13. BACKFILL TRENCHES W/ PEA GRAVEL TO LEVEL REQUIRED FOR NEW SLURRY COVER AND PAVING BASE. PROVIDE <br />CONCRETE 4" THICK MIN, OVER PEA GRAVEL, <br />14. NEW CONCRETE DRIVE SLAB, MINIMUM 6" THICK W/ •4 BARS AT 18" O.C. BOTH WAYS, OVER 4" OF 3/4" CRUSHED ROCK <br />OVER 6" AGG. BASE. CONFIRM MIN. PAYING DESIGN MATCHES CIVIL/STRUCTURAL ENGINEERING RECS, AND GEOTECHNICAL <br />REPO"CS- CONFIRM SLAB CONFIGURATION W/ ARCHITECTURAL AND/OR CIVIL SHEETS, <br />I5. NEW 9" TWICK (AT 5'-6" BURY), CONCRETE TANK SLAB W/ •4 REBAR AT 18" O.G. BOTH WAYS. CONFIRM SLAB REQUIREMENTS <br />W/ CIVIL AND/OR STRUCTURAL DOCUMENTS. <br />16. NEW FUEL SYSTEM PANELS, CONTROLS, MONITORING CONSOLE AND ALARM IN (N) BUILDING. INSTALL NEW MONITORING <br />SYSTEM, CONTROLS AND DISPENSER INTERFACE COMPONENTS, AS REQUIRED. <br />Il. OVEF;r-ILL ALARM WITH ACKNOWLEDGMENT SWITCH, MOUNT ON THE VENT RACK VISIBLE FROM THE UST TANKER -FILL <br />POSITION. <br />IB. NEW CONIC. FILLED BOLLARDS, TYPICAL OF FOUR (4) PER DISPENSER 6" SQ, 42" HIGH, INSTALL PER DETAIL. <br />19. l2) NEW EMERGENCY SHUT -OFFS (ESO), (1) INSTALL NEW BOLLARD IN PLANTER AND MOUNT ON BOLLARD W/ VISIBLE SIGN, <br />AND INSTALL (1) ON THE STORE FRONT W/ VISIBLE SIGN. SEE GENERAL NOTES, CONFIRM LOCATIONS W/ FIR= DEPT, <br />APPROVALS, <br />20. CONTRACTOR SHALL PAINT ALL EXPOSED METALS, UNLESS PREFINISHED, W/ SUITABLE PAINT IN APPROVED COLORS, <br />21. PIPING IS SHOWN SCHEMATIC, AND MAY BE EXAGGERATED FOR DRAFTING CLARITY, VARIATIONS DUE TO FIELD <br />CONDITIONS FOUND ARE EXPECTED. <br />PROJECT DATA <br />PG`3®�JG�4 -INSTALL NEW FUEL STORAGE t DISPENSING SYSTEM. <br />a�pdoc�car��� 9 �4Qa®cap©� <br />INCLUDE, BUT SHALL NOT BE LIMITED TO: <br />CALIFORNIA BUILDING CODE ICRC) 2022 <br />CALIFORNIA FIRE CODE (CFC) 2022 <br />CALIFORNIA ELECTRIC CODE (CEC) 2022 <br />CALIFORNIA AIR RESOURCES BOARD (GARB) EXEC, ORDERS, <br />APPROVAL t LOCAL GUIDANCE LETTERS <br />CARE APPROVED INSTALLATION, OPS, t MAINTENANCE MANUALS <br />TITLE 23, CALIFORNIA CODE OF REGULATIONS, CHAPTER I6, <br />UNDERGROUND TANK REGULATIONS (AKA SWRCB UST REG5.) <br />EQUIPMENT MANUFACTURERS' INSTALLATION REQUIREMENTS <br />UNDERWRITER'S LABORATORIES, INC. (UL) <br />LOCAL ORDINANCES <br />Hcv <br />OCCUPANCY - GROUP M <br />FUEL SYSTEM SHEET INDEX <br />PET -I <br />FUEL SYSTEM PIPING PLAN, NOTES <br />PET -2 <br />GASOLINE < DIESEL TANK SECTION AND SLAB <br />PET -3 <br />GASOLINE a E55 TANK SECTION AND SLAB <br />PET -4 <br />FUEL SYSTEM DETAILS <br />PET -5 <br />FUEL SYSTEM DETAILS <br />PET -6 <br />FUEL SYSTEM PARTIAL ELECTRICAL PLAN <br />PET-� <br />FUEL SYSTEM CONDITIONS, LUORKSCOPE, TESTING <br />PET -8 <br />EQUIPMENT LIST, REQUIRED D CUMENTATION <br />PET -9 <br />_ <br />DISPENSER SIGNAGE, 1 <br />DEF <br />PET -ISD <br />VACUUM ZONE DRAWING 3 <br />EXISTING <br />ETR <br />FINAL DRAWING CHANGES 4 <br />EXT. <br />�r�r���doa400a� <br />AFG <br />GENERAL NOTES ISD IN -STATION DIAGNOSTICS (AQJ <br />L.Y. LOW VOLTAGE <br />A. PORTABLE FIRE EXTINGUISHERS SHALL BE PROVIDED IN ACCORDANCE WITH CALIFORNIA FIRE CODE (CFGJ SECTION MNFR MANUFACTURER <br />2305.5 AND 906. INSTALL A7 LEAST TWO PORTABLE FIRE EXTINGUISHER fFE.) W/ A MINIMUM RATING OF 2-A:20-B:C AS M/5 MASTER/SATELLITE ( <br />ABOVE FINISH GRADE <br />AST <br />ABOVEGROUND STORAGE TANK <br />ANN. <br />AIJNULAR TAMC MONITOR /PROBE <br />ATG <br />AUTOMATIC TANK GAUGE (TLM) <br />AQ <br />AIR QUALITY <br />ANl <br />AIR /WATER UNIT <br />G <br />CONDUIT <br />CGVP <br />CARBON CANISTER VAPOR <br />w <br />PROCESSOR / POLISHER <br />DEF <br />DIESEL EXHAUST FLUID <br />(E) <br />EXISTING <br />ETR <br />EXISTING, TO REMAIN <br />EXT. <br />ENHANCED VAPOR RECOVERY <br />EXT. <br />EXTERIOR <br />FB <br />FILL CONTAINMENT SOX <br />FE. <br />FIRE EXTINGUISHER <br />F.N. <br />FIRE HYDRANT <br />FRP <br />FIBEfdaLASS REINFORCED PLASTIC <br />N.V. <br />HIGH VOLTAGE <br />CERTIFICATIONS AND APPROVALS FOR INSTALLATION OF ALL OF THE FUEL SYSTEM RELATED WORK INCLUDING FUEL <br />SYSTEM ELECTRICAL COMPONENTS, AND SHALL PROVIDE A COMPLETE, WORKABLE FUEL SYSTEM PER MANUFACTURERS' E+ <br />AND CODES' REQUIREMENTS, THE FUEL SYSTEM'S ELECTRICAL SYSTEMS INCLUDE, BUT ARE NOT LIMITED 70, HIGH t LOW �7 <br />VOLTAGE POWER MONITORING AND COMMUNICATIONS (INTERCOM t CONTROL) REQUIREMENTS. C�1\ /1R/1�I�tL"►CT�L <br />H <br />n <br />Q <br />w <br />J <br />a <br />v <br />m <br />w <br />DISPENSER) <br />L <br />SHOl1N. THESE EXTINGUISHERS 70 BE AFFIXED TO A LOCATION ON A MOUNTING BRACKET OR IN A FIRE EXTINGUISHER <br />(N) <br />NEW <br />CABINET, AND LOCATED NOT MORE THAN l5 FEET FROM PUMPS, DISPENSERS OR STORAGE TANK FILL -PIPE OPENINGS. <br />m <br />NC <br />NORMALLY CLOSED (SOLENOID) <br />J <br />NO <br />NORMALLY OPEN (SOLENOID) <br />B. <br />A CLEARLY LABELED, MANUALLY OPERATED PUMP MASTER SWITCH SHALL BE PROVIDED IN AN APPROVED LOCATION <br />RECS, <br />RECOMMENDATIONS <br />Q <br />W/IN 100 FEET, BUT NOT NEARER THAN 20 FEET TO, ANY DI6PEN5ER WHERE SUCH MASTER SWITCH 15 NOT VISIBLE FROM <br />JIL <br />REQ'D, <br />REQUIRED <br />d <br />ALL DISPENSERS, THE LOCATION THEREOF SHALL BE INDICATED BY APPROVED SIGNS. SIGNS IDENTIFYING THE RUMP <br />M <br />REQS, <br />REQUIREMENTS <br />MASTER SWITCH SHALL BE LABELED "EMERGENCY FUEL SHUTOFF", THE MASTER SWITCH ON ALL INDIVIDUAL PUMP <br />51DCB <br />STORM DRAIN CATCH BASIN <br />CIRCUIT SWITCHES SHALL BE SET IN THE "OFF" POSITION BEFORE CLOSING THE STATION FOR BUSINESS AT ANY TIME. (CFC <br />SIM. <br />SIMILAR (TO) <br />STP <br />SUBMERGED TURBINE PUMP <br />ICEC 23031.1) HEIGHT. THE HEIGHT OF THE EMERGENCY DISCONNECT SWITCH SHALL BE NOT LE55 THAN 42 INCHES (1061 mm) <br />2 T <br />TRANSITION BOX, PIPING <br />AND NOT MORE THAN 45 INCHES (1219 mm) MEASURED VERICALLY, FROM THE FLOOR LEVEL 70 THE ACTIVATING BUTTON. <br />TLM <br />TANK LEVEL MONITOR (ATG) <br />. . , . , - <br />TYP. <br />TYPICAL <br />C. <br />ALL MATERIALS AND EQUIPMENT SHALL BE INSTALLED AND TESTED PER MANUFACTURER'S INSTRUCTIONS, APPLICABLE <br />UL <br />UL LISTED <br />CODES AND STANDARDS, THE PLANS AND SPECIFICATIONS, AND LOCAL AGENCY REQUIREMENTS. <br />UDC <br />UNDER DISPENSER CONTAINMENT <br />VR <br />VAPOR RECOVERY <br />D. <br />FUEL SYSTEM CONTRACTORS AND INSTALLERS SHALL HAVE ALL CURRENTLY REQUIRED EQUIPMENT MANUFACTURERS' <br />XFR <br />ELECTRICAL TRANSFORMER <br />�'�y �r���� <br />E. TANK t DRIVE SLAB CONCRETE SHALL BE CAPABLE O= PASSING A MINIMUM COMPRESSIVE STRENGTH OF 3500 psi f6�Y1 Vf��IgCR��I,'1EL If7 VAC <br />AFTER 28 DAYS, AND SHALL OTHERWISE FOLLOW THE CONCRETE DESIGN AS SPECIFIED IN THE CIVIL/ARCH DOCUMENTS. <br />C )NC, DESIGN STRENGTH OVER 2500 psi 15 BY OWNER PREFERENCE, NOT DESIGN REQUIREMENTS, AND DOES NOT � ' {h7 <br />REQUIRE SPECIAL INSPECTIONS. EXPANSION JOINTS AT DRIVE AND TANK SLA55 SHALL BE SEALED W/ FUEL CA <br />COMPATIBLE MATERIALS. (20) 3V <br />F. MATERIALS OF CONSTRUCTION FOR UNDERGROUND STORAGE TANKS, PIPING AND SECONDARY CONTAINMENT SYSTEMS <br />SHALL BE COMPATIBLE WITH THE STORED HAZARDOUS SUBSTANCES, INCLUDING ALCOHOLS (METHANOL, ETHANOL, ETC.) <br />AND ALCOHOL -GASOLINE MIXTURES, WHICH SHALL BE DOCUMENTED AS COMPATIBLE BY THE MANUFACTURER AND/OR Bl Awn <br />AN nYmd <br />APPROVED INDEPENDENT TESTING ORGANIZATION. ��MtPro Chang <br />G. CONSPICUOUSLY POST WARNING SIGNS WITHIN SIGHT OF EACH DISPENSER FACE, PER CFC 2305b. Cl AP��ed Wil) See <br />• As Re <br />Cl Disapproved: See Re arks <br />Remarks -- � QZ 00 6 7 P 7 ct <br />r+�7�rE�lr911 �xtenas artly Co that which iS Showa ahEf d <br />!�w'eon acid does n�,± aufhorize or approve sr4y vmissio►i °" °, <br />dev�[at�rt fiaet r�ui:eEs �i siafe 18wiS W iosai ��: <br />ZNwQ <br />I.. WmUW Ln <br />W N <br />WW u>' u <br />Z @ m <br />YV cq W <br />�Q �Nm Q) Q <br />M E Q <br />w <br />W <br />N <br />W <br />� U <br />J <br />PET -1 <br />OF 9 'PET' SHEETS <br />n <br />Q <br />w <br />J <br />a <br />v <br />m <br />w <br />L <br />L <br />L <br />Z <br />m <br />n <br />J <br />J <br />J <br />W <br />Q <br />Z <br />JIL <br />W <br />d <br />1 <br />M <br />IL <br />IL <br />PET -1 <br />OF 9 'PET' SHEETS <br />U <br />U <br />� <br />Z <br />Z <br />J <br />J <br />J <br />J <br />Q <br />Z <br />Z <br />W <br />d <br />1 <br />M <br />IL <br />PET -1 <br />OF 9 'PET' SHEETS <br />