Laserfiche WebLink
FS at Actual Tension Including any ASD Load Factors by Anchor Location for Each <br />Anchoring System Component Type <br />IDtk 120 in Strap ult_load 25000lbf Turnbuckleult_load 26000lbf Ultimate Rated Load <br />by ComponentASD Load Factor Wire_Ropeult_load 23000lbf Eye_Boltult_load 26000lbf <br />LF 1.00 <br />Strap FS Turnbuckle FS Wire Rope FS Eye Bolt FS <br />Strap ult_load <br />Tstrap_actual <br />250.0 <br />46.3 <br />250.0 <br /> <br />Turnbuckleult_load <br />Tstrap_actual <br />260.0 <br />48.2 <br />260.0 <br /> <br />Wire_Ropeult_load <br />Tstrap_actual <br />230.0 <br />42.6 <br />230.0 <br /> <br />Eye_Boltult_load <br />Tstrap_actual <br />260.0 <br />48.2 <br />260.0 <br /> <br />ComponentFSreqd 3 required FS for components vs component ultimate loads <br />Check If Tension Load Exceeds Required FS for Components <br />Strap ks if <br />Strap ult_load <br />Tstrap_actualks <br />ComponentFSreqd "OK""Redesign" <br />Turnbuckleks if <br />Turnbuckleult_load <br />Tstrap_actualks <br />ComponentFSreqd "OK""Redesign" <br />Wire_Ropeks if <br />Wire_Ropeult_load <br />Tstrap_actualks <br />ComponentFSreqd "OK""Redesign" <br />Eye_Boltks if <br />Eye_Boltult_load <br />Tstrap_actualks <br />ComponentFSreqd "OK""Redesign" <br />Strap Check Turnbuckle Check Wire Rope Check Eye Bolt Check <br />Strap <br />"OK" <br />"OK" <br />"OK" <br /> Turnbuckle <br />"OK" <br />"OK" <br />"OK" <br /> Wire_Rope <br />"OK" <br />"OK" <br />"OK" <br /> Eye_Bolt <br />"OK" <br />"OK" <br />"OK" <br /> <br />Tank Buoyancy, Rotten Robbie No 69, <br />Manteca CA, dwg 17366-001, 10ft DWT <br />Date Printed: 9/7/2023 Page 46 of 46