Laserfiche WebLink
Tank Wall <br />Volume <br />Vol wall <br />Wttk_dry <br />Wallsg wat <br />788gal  volume of the tank wall itself not <br />including annular space and rib volumes <br />but does include the materials that form <br />the ribs <br />Number of Ribs Noribs 10 number of ribs on the tank <br />Vol as Noribs 2.49gal ID tk 48in=if <br />Noribs 3.70gal ID tk 72in=if <br />Noribs 4.71gal ID tk 92in=if <br />Noribs 15.09gal IDtk 120in=if <br />Noribs 17.33gal IDtk 138in=if <br />0gal otherwise <br /> Tank Annular <br />Space or Rib <br />Volume Values provided by the <br />tank manufacturer. This <br />is the volume under the <br />ribs. <br />Vol as 151gal <br />Tank Annular <br />Space Fluid Weight <br />Brinewt_factor 80% Factor to adjust the calculated brine weight to <br />be conservative. Normally 80% <br />BFbrine Volas Brinesg wat Annular_Space "Wet"=if <br />0lbf otherwise <br /> <br />BFbrine BFbrine Brinewt_factor 1310lbf  factored brine weight <br />total <br />buoyant <br />force for the <br />tank volume <br />Tank Buoyant <br />Force <br />BFtk Vol tk Vol wallVol as tk_wat BFbrine105599lbf  <br />Tank Buoyancy, Rotten Robbie No 69, <br />Manteca CA, dwg 17366-001, 10ft DWT <br />Date Printed: 9/7/2023 Page 13 of 46