Laserfiche WebLink
SANJ0AQUIN Environmental Health Department <br /> COUNTY <br /> Aboveground Petroleum Storage Act Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> CRST-EQUIPMENT SOLUTIONS 12577 W YOSEMITE AVE MANTECA June 19 2025 <br /> 10 Code of Fed Regulations 112.5(b)4010009- 5 year review performed on SPCC and documented <br /> OBSERVATION: The facility failed to perform the 5-year review of the SPCC plan. The Spill Prevention, Control, and <br /> Countermeasure (SPCC) Plan was last reviewed on 03/18/2019. <br /> REGULATION GUIDANCE: (b) Notwithstanding compliance with paragraph [112.5] (a)of this section, complete a review <br /> and evaluation of the SPCC Plan at least once every five years from the date your facility becomes subject to this part; <br /> or, if your facility was in operation on or before August 16, 2002, five years from the date your last review was required <br /> under this part. As a result of this review and evaluation, you must amend your SPCC Plan within six months of the <br /> review to include more effective prevention and control technology if the technology has been field-proven at the time of <br /> the review and will significantly reduce the likelihood of a discharge as described in § 112.1(b)from the facility. You must <br /> implement any amendment as soon as possible, but not later than six months following preparation of any amendment. <br /> You must document your completion of the review and evaluation, and must sign a statement as to whether you will <br /> amend the Plan, either at the beginning or end of the Plan or in a log or an appendix to the Plan. The following words will <br /> suffice, "I have completed review and evaluation of the SPCC Plan for(name of facility) on (date), and will (will not) <br /> amend the Plan as a result." <br /> CORRECTIVE ACTION: Immediately complete and document the 5-year review of the SPCC Plan and make any <br /> necessary amendments (a Professional Engineer must certify any technical amendments). Submit verification of <br /> adequate SPCC plan review completion to the EHD. <br /> This is a (Class 2)Violation. <br /> 32 Code of Fed Regulations 112.7(f)(3)4020002- Spill prevention briefings are conducted annually <br /> OBSERVATION: Failure to conduct spill prevention briefing for oil-handling personnel at least once a year to assure <br /> adequate understanding of the SPCC Plan, including: <br /> 1. Known discharges or failures. <br /> 2. Malfunctioning components. <br /> 3. Any recently developed precautionary measures. <br /> REGULATION GUIDANCE: (f)(3) Schedule and conduct discharge prevention briefings for your oil-handling personnel at <br /> least once a year to assure adequate understanding of the SPCC Plan for that facility. Such briefings must highlight and <br /> describe known discharges as described in § 112.1(b) or failures, malfunctioning components, and any recently <br /> developed precautionary measures. <br /> CORRECTIVE ACTION: Discharge prevention briefings for oil handling personnel must be scheduled and conducted at <br /> least once a year to assure adequate understanding of the SPCC Plan for that facility. Conduct all required spill <br /> prevention briefings. Provide compliance verification to the EHD. <br /> This is a Repeat (Class 2)Violation. <br /> 55 4030014-Tanks inspected and tested by qualified person in accordance with industry standards <br /> OBSERVATION: Facility failed to ensure that tanks are inspected and tested by an appropriately qualified person in <br /> accordance with industry standards. The two 10,000 gallon double walled ASTs were not tested on schedule. The SPCC <br /> plan stated that the tank integrity test was due in 2019. Paint flaking was observed on the surface of the two 10,000 <br /> gallon ASTs. <br /> REGULATION GUIDANCE: 112.8(c)(6)Test or inspect each aboveground container for integrity on a regular schedule <br /> and whenever you make material repairs. <br /> CORRECTIVE ACTION: Immediately ensure that all tanks are inspected and tested by an appropriately qualified person <br /> in accordance with industry standards. Submit proof of correction/test results to the EHD. <br /> This is a Repeat (Class 2)Violation. <br /> EHD-CUPA Inspection Report IS02 Page 5 of 7 FA0010976 PR0513264 4518566 6/19/2025 <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />