Laserfiche WebLink
SAN J0AQUIN <br />COUNTY <br />Environmental Health Department <br />Aboveground Petroleum Storage Act Program Inspection Report <br />Facility Name: <br />Facility Address: <br />11477 <br />Date: <br />WILLIAMS TANK LINES <br />TILLIE LEWIS DR STOCKTON <br />August 22 2025 <br />SUMMARY OF VIOLATIONS <br />(CLASS I, CLASS II, or MINOR - Notice to Comply) <br />Item # <br />Remarks <br />57 <br />Code of Fed Regulations 112.7(e), 112.8(c)(6) 4010021 - Written Inspection/testing procedures kept, inspection/testing <br />records signed, kept for 3 years <br />OBSERVATION: The facility failed to keep written procedures and records of inspections and tests, including integrity <br />tests, for at least three years. Copies of inspection and testing records for May 2023 to present were not found on site. <br />REGULATION GUIDANCE: 112.7(e), Conduct inspections and tests required by this part in accordance with written <br />procedures that you or the certifying engineer develop for the facility. You must keep these written procedures and a <br />record of the inspections and tests, signed by the appropriate supervisor or inspector, with the SPCC Plan for a period of <br />three years. Records of inspections and tests kept under usual and customary business practices will suffice for <br />purposes of this paragraph. 112.8(c)(6) Test or inspect each aboveground container for integrity on a regular schedule <br />and whenever you make material repairs. <br />CORRECTIVE ACTION: Inspections and tests must be conducted in accordance with the written procedures developed <br />in the Spill Prevention, Control, and Countermeasure (SPCC) Plan. Records of these inspections and tests must be <br />signed by the appropriate supervisor or inspector and kept on-site with the SPCC Plan for three years. <br />This is a Repeat (Class 2) Violation. <br />Overall Inspection Comments <br />Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br />documenting the corrective actions that have been or will be taken for each violation, and any supporting paperwork, <br />by September 21, 2025. <br />To minimize person to person contact EHD is choosing to write the name of person receiving the report instead of <br />having them sign. Starting July 1, 2025, all in -office CERS help will be provided at EHD hourly rate ($179). To <br />schedule an appointment, please call (209) 468-3420. <br />The following was observed during this inspection: <br />- 12,000 gallon diesel tank <br />- Two 500 gallon motor oil tanks <br />- Two 220 gallon used oil IBC totes <br />- 240 gallon diesel reclaim tank <br />- 69 gallon diesel generator <br />- 55 gallon steel drum transmission fluid <br />- 55 gallon diesel drum <br />AFTER THE COMPLIANCE DATE, EHD WILL BILL FOR ALL TIME AND ACTIVITIES ASSOCIATED WITH BRINGING THIS <br />FACILITY BACK INTO COMPLIANCE. <br />THIS FACILITY IS SUBJECT TO REINSPECTION AT ANY TIME AT EHD'S CURRENT HOURLY RATE. <br />Received by: Date: August 22, 2025 <br />Inspector: <br />Inspector Phone: <br />Printed Name and Title: <br />Allen ASIo, EHS <br />(209) 616-3031 <br />Mark Lill, General Manager <br />EHD - CUPA Inspection Report IS02 <br />Page 5 of 5 FA0010602 PR0523160 4541786 8/22/2025 <br />1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />