Laserfiche WebLink
SAN J0AQUIN Environmental Health Department <br /> COUNTY <br /> Aboveground Petroleum Storage Act Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> PANELLA TRUCKING LLC 15000 E FREMONT ST STOCKTON June 20 2025 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I, CLASS II, or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 11 Code of Fed Regulations 112.7 4010012 - SPCC in writing, follows code seq/cross ref, good eng practice, mgt <br /> approval, items not in place <br /> OBSERVATION: The Spill Prevention, Control, and Countermeasure (SPCC) Plan failed to have the full approval of <br /> management at a level of authority to commit the necessary resources to fully implement the Plan. <br /> - The "Administrative Facility Management Certification"only contained the signature and date of the Secondary <br /> Emergency Coordinator, Davis Winters. There is no signature or date for the Authorized Facility Management <br /> Representative, Robert Panella. There is also no signature or date for the Authorized Facility Emergency Coordinator, <br /> Augustine Calvillo. <br /> REGULATION GUIDANCE: The Plan must have the full approval of management at a level of authority to commit the <br /> necessary resources to fully implement the Plan. <br /> CORRECTIVE ACTION: Immediately obtain required management approval for the SPCC Plan for this facility. Provide <br /> proof of correction to the EHD. <br /> ---------------------------------------------------------------------------------------------------------- <br /> OBSERVATION: The Spill Prevention, Control, and Countermeasure (SPCC) Plan reviewed at the time of inspection, <br /> dated June 2023, did not follow the order or requirements of 40 CFR Part 112.7. It doesn't include adequate cross- <br /> reference. <br /> Section 4.1 Compliance with Applicable Requirements- mentions that Appendix F indicates the facility inspection <br /> schedule. Instead, Appendix F is a blank page titled "Records of Tank Integrity and Pressure Tests". <br /> REGULATION GUIDANCE: If you are the owner or operator of a facility subject to this part you must prepare a Plan in <br /> accordance with adequate cross reference. <br /> CORRECTIVE ACTION: Ensure that your SPCC Plan complies with the following requirements: It follows the required <br /> SPCC rule sequence and/or includes adequate cross-reference. Provide proof of correction to the EHD. <br /> This is a (Minor)Violation. <br /> 22 Code of Fed Regulations 112.7(a)(3vi), 112.7(a4) 4010017- SPCC contains procedures for reporting a discharge <br /> OBSERVATION: The Spill Prevention, Control, and Countermeasure (SPCC) Plan Emergency Contact list failed to <br /> include the phone number for the San Joaquin County Environmental Health Department. Additionally, the phone <br /> number was not included elsewhere in the SPCC plan. <br /> REGULATION GUIDANCE: The SPCC plan shall include: (vi) Contact list and phone numbers for the facility response <br /> coordinator, National Response Center, cleanup contractors with whom you have an agreement for response, and all <br /> appropriate Federal, State, and local agencies who must be contacted in case of a discharge as described in § 112.1(b). <br /> CORRECTIVE ACTION: Immediately amend the SPCC Plan to include the phone number of the Environmental Health <br /> Department of San Joaquin County. Submit proof of correction to the EHD. <br /> This is a Repeat (Class 2)Violation. <br /> EHD-CUPA Inspection Report IS02 Page 5 of 7 FA0003907 PR0527046 4519005 6/24/2025 <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />