Laserfiche WebLink
Underground Storage Tank <br /> Overfill Prevention Equipment Inspection Report <br /> 6. OVERFILL PREVENTION EQUIPMENT DETAILS <br /> T2 T1 T3 <br /> Tank ID (one OPE per column) <br /> Are both vent and tank riser piping a Yes r: Yes r. Yes r Yes <br /> secondarily contained? r No c, No No r No <br /> OPE Model OPw OPw OPw <br /> r Shut off W Shut off fW Shut off r Shut off <br /> Flow Flow Flow Flow <br /> F Restricts r Restricts F Restricts r Restricts <br /> What is the OPE response when activated? Flow Flow Flow Flow <br /> (Check all that apply) r Audible r Audible F Audible F Audible <br /> Alarm Alarm Alarm Alarm <br /> F Visual F Visual F Visual F Visual <br /> Alarm Alarm Alarm Alarm <br /> Are flow restrictors installed on vent piping r Yes* Yes* r Yes* Yes* <br /> that may interfere with the OPE operation? r No No r. No No <br /> At what level in the tank is the OPE set to 103.75 98.125 100.25 <br /> activate? (Inches from bottom of tank) <br /> What is the percent capacity of the tank at <br /> which the OPE activates? 93.4 90 90.5 <br /> Is the OPE in proper operating condition to G Yes Yes Yes Yes <br /> respond when the stored substance reaches r No No No No <br /> the designated regulatory level? <br /> 7. SUMMARY OF TESTING RESULTS <br /> OPE Inspection Results G Pass Pass Pass Pass <br /> r Fail Fail Fail Fail <br /> 8. COMMENTS <br /> Describe all results marked "Fail"and each proposed remedy. <br /> *Mark here if: <br /> F Flow restrictors interfere with overfill prevention and equipment repairs required. <br /> Additional copies of this page may be attached. <br /> Attach tank chart(s), measurements, calculations, and In-Tank Setup report(s) <br />