Laserfiche WebLink
Underground Storage Tank <br /> Spill Container Testing Report Form <br /> Test Type ❑ Pressure ❑ Vacuum x Hydrostatic <br /> Tank ID T1:87 West T1:87 East T2: 91 T3: DIESEL <br /> Spill Container Manufacturer: Phil-Tite Phil-Tite Phil-Tite Phil-Tite <br /> Method of Cathodic Protection xNonmetallic xNonmetallic xNonmetallic xNonmetallic <br /> ❑Other ❑Other ❑Other ❑Other <br /> Is the spill container minimum xYes xYes xYes xYes <br /> capacity five gallons excluding riser ❑No* ❑No* ❑No* ❑No* <br /> volume? <br /> xDrain xDrain xDrain xDrain <br /> Method to keep spill container ❑Pump El Pump ❑Pump ❑Pump <br /> empty ❑Other ❑Other ❑other ❑Other <br /> Spill Container Test Results xPass xPass xPass xPass <br /> []Fail ❑Fail ❑Fail ❑Fail <br /> Tank ID <br /> Spill Container Manufacturer: <br /> Method of Cathodic Protection ❑Nonmetallic ❑Nonmetallic ❑Nonmetallic ❑Nonmetallic <br /> ❑Other ❑Other El Other ❑Other <br /> Is the spill container minimum El Yes ❑Yes ❑Yes ❑Yes <br /> capacity five gallons excluding riser ❑No* ❑No* ❑No* ❑No* <br /> volume? <br /> ❑Drain ❑Drain ❑Drain ❑Drain <br /> Method to keep spill container ❑Pump ❑Pump ❑Pump ❑Pump <br /> empty ❑Other ❑Other ❑Other ❑Other <br /> Spill Container Test Results ❑Pass ❑Pass ❑Pass ❑Pass <br /> ❑Fail ❑Fail ❑Fail ❑Fail <br /> 8. COMMENTS <br /> Describe allanswers marked "Other,""No,"or "Fail"and each proposed remedy. <br /> 1) The drain valve spill bucket 0-rings were replaced in the 87 fills. <br /> 2) The 91 drain valve and 0-ring were replaced <br /> * Mark here if: <br /> ❑ Spill containers do not have a minimum capacity of five gallons and require replacement. <br /> Additional copies of this page may be attached. <br /> Page 2of2 <br />