Laserfiche WebLink
r. Standpipe valves shall be non-pressure reducing valves, non-pressure restricting valves, <br /> standpipe valves shall be U-Angle Hose Valves consisting of a 2.5"inlet and 2.5"outlet. <br /> Preferred brand Elkhart Brass. <br /> s. Valve outlet shall point at a 90-degree angle outward toward landing <br /> y <br /> 4. Underground Piping for Fire Sprinkler Systems: <br /> a. All underground piping for fire sprinkler systems must be approved by the Fire <br /> Department before permit issuance. <br /> 5. Protection;of Gas Meters and Piping: <br /> a. Above-ground gas meters,regulators, and exposed piping shall be protected from <br /> vehicular damage in an approved manner. <br /> 6. Fire Suppression Systems: <br /> a. All buildings must have an approved monitored automatic sprinkler system in <br /> compliance with NFPA 13, CFC, and CBC. <br /> b. Fire alarm/sprinkler monitoring shall be Point ID. <br /> 7. Fire Suppression Approval: <br /> a. Plans and specifications for fire suppression systems must be submitted for review and <br /> approval before construction. <br /> b. Any deviations from approved plans require submission of"As-Built"plans before final <br /> inspection. <br /> 8. Deferred Submittals: <br /> a. Plans listed as deferred submittals must be clearly labeled on the building permit <br /> submittal cover sheet. <br /> 9. Fire Protection Inspections: <br /> a. Fire protection systems (hydrants,water mains, etc.)must be installed,tested, and <br /> approved by the AHJ before any building permits are issued. <br /> b. The Fire Department must witness all system and acceptance tests. <br /> c. A minimum of 24-hour notice is required before any system or acceptance tests. (Submit <br /> requests at www.frencheampfire.com) <br />