Laserfiche WebLink
_ anknology 111 1100 Field Test Apparatus Page 1 of 1 <br /> TLine Leak Detector Test <br /> Work Order: 2387481 Date: 1/5/2026 <br /> Site Name/ID: CHEVRON 201761 /201761 <br /> Address: 1103 S.MAIN ST. PERMIT NUMB. N-3315 <br /> City: MANTECA State: CA Zip: 95337 <br /> Tank ID T3 Regular 1 T1 Supreme <br /> Product REGULAR SUPREME <br /> Product Line 1 1 <br /> Tested From 3 11 <br /> Existing/New Existing Existing <br /> Mechanical/Electronic Electronic Electronic <br /> Manufacturer/Model Veeder Root PLLD Veeder Root PLLID <br /> Serial No. 015618 404907 <br /> Pump Operating Pressure(psi) 40.00 40.00 <br /> Calibrated Leak(ml/min) 189.0 189.0 <br /> Calibrated Leak(gph) 3.00 3.00 <br /> Holding PSI <br /> N/A for Electronic LD's <br /> Resiliency(ml) <br /> N/A for Electronic LD's <br /> Metering PSI <br /> N/A for Electronic LD's <br /> Opening Time(sec) <br /> N/A for Electronic LD's <br /> Test Results Pass Pass <br /> Technician Comments: <br /> Technician Name: Jesus Saldivar Certification#: 115237 <br /> Technician Signature: 4L J/./. Expire Date: 10/22/2027 <br /> Environmental Compliance for Petroleum Systems <br /> @2026 Tanknology Inc.,Austin,TX. All rights reserved. tanknology.com <br />