Laserfiche WebLink
_ anknology LDT 5000 Field Test Apparatus Page 1 of 1 <br /> T Line Leak Detector Test <br /> Work Order: 2387486 Date: 2/4/2026 <br /> Site Name/ID: CHEVRON 209167/209167 <br /> Address: 1234 E.YOSEMITE AVE @ SPRECKLES <br /> City: MANTECA State: CA Zip: 95336 <br /> Tank ID Regular Premium <br /> Product REGULAR SUPREME <br /> Product Line 1 1 <br /> Tested From 11 11 <br /> Existing/New Existing Existing <br /> Mechanical/Electronic Electronic Electronic <br /> Manufacturer/Model Veeder Root PLLD Veeder Root PLLD <br /> Serial No. 336796 115691 <br /> Pump Operating Pressure(psi) 38.00 40.00 <br /> Calibrated Leak(ml/min) 189.0 189.0 <br /> Calibrated Leak(gph) 3.00 3.00 <br /> Holding PSI <br /> N/A for Electronic LD's <br /> Resiliency(ml) <br /> N/A for Electronic LD's <br /> Metering PSI <br /> N/A for Electronic LD's <br /> Opening Time(sec) <br /> N/A for Electronic LD's <br /> est Results Pass Pass <br /> Technician Comments: <br /> Technician Name: Jesus Saldivar Certification#: 115237 <br /> Technician Signature: J,4-1- Expire Date: 10/22/2027 <br /> Environmental Compliance for Petroleum Systems <br /> ©2026 Tanknology Inc.,Austin,Tx. All rights reserved. tanknology.com <br />