PREPARED FOR:
<br /> UTILITY NOTES SINGLE LINE DIAGRAM CD
<br /> 0
<br /> lV
<br /> KEY NOTES: w
<br /> ONEW MYERS/RYCO (OR APPROVED I`
<br /> EQUIVALENT)SWITCHBOARD 600A, • rm
<br /> 120/208, 3PH, 4W- NEMA 3R ENCLOSURE (E) UTILITY POLE ( , �,.�
<br /> #120937061, (NEW �"1 J
<br /> NEW INTEGRATED LOAD CENTER(PANEL VERTICAL BRIDGE U LL
<br /> UTILITY GENERAL NOTES: O A) INTERSECT INC MANUFACTURE (AA POWER P.O.C.) Z
<br /> 300-3R SERIES MODEL AA 3003R-458-6M (N)CONDUCTORS BY PG&E IN �� LU O
<br /> 1. ALL NEW GROUNDINGS FOR ELECTRICAL ROUTE METER MUST BE DONE PER CEC, NEC& LOCAL /� 2 I-
<br /> BUILDING &SAFETY REQUIREMENTS. -3S)W/200AMP/2POLE, ATS, 120/208 V, (1)4"CONDUIT BY GC (±580') `V 2 Q
<br /> 1-PHASE, 3WIRE, 42KAIC W/30 POSITIONS (N)3'X5' SPLICE BOX5 PER 0 W
<br /> 2. ALL NEW CONDUIT FROM ELECTRICAL ROUTE METER TO THE SITE MUST BE RGS CONDUITS. PROVIDED BY VERIZON WIRELESS. PG&E DESIGN C) Q
<br /> • rME4 LL U
<br /> INSTALL WEATHERPROOF PULL BOXES AS REQD. PER CEC, NEC& LOCAL BLDG. & SAFETY NEW AUTOMATIC TRANSFER SWITCH 0 0
<br /> REQUIREMENTS & MUST HAVE TRAFFIC COVERS. O GENERAC ASCO SERIES 300L, 200 AMP, c , 00
<br /> 3. ALL NEW PULL BOXES MUST BE HOT-DIPPED GALVANIZED AND WEATHERPROOF 120/208V, 1PHASE, 3WIRE, 2 POLE,42 KAIC ^ Q
<br /> /a ) 0-
<br /> 4. ALL NEW WIRE SPLICES PULL BOXES DONE PER CEC & NEC. Lo
<br /> NOTE:
<br /> 5. FIELD VERIFY EXACT ELECTRICAL CONDUIT ROUTE. IN ACCORDANCE WITH CEC 110.16 T (N)75 KVA PG&E
<br /> PROVIDE ARC FLASH PROTECTION TRANSFORMER, 600
<br /> 6. VERIZON WIRELESS NEW METER/MAIN NEED TO BE LABELED &ALL CLEARANCE FOR ELECTRICAL WARNING LABLES. LABLES SHALL AMPS,120/208V, 3PHASE
<br /> EQUIPMENT BY CEC& NEC. BE PER ANSI Z635.4 GUIDELINES VENDOR:
<br /> ,
<br /> 7. NEW GROUND RODS MAY BE USED FOR SITE GROUNDING IF DESIRED RESISTANCE IS ACHIEVED. (N)3/4" C W/#2 GROUND CONDUIT CONDUITCOPPER BONDED TO 5/8"X 10, - O
<br /> LONG COPPERCLAD STEEL AREA AREA
<br /> 8. CONTRACTOR TO INSTALL UTILITY CONDUIT(LATERAL). GROUND ROD O
<br /> OUTDOOR ENCLOSURE
<br /> 9. UTILITY POINTS OF SERVICE AND WORK/MATERIALS SHOWN ARE BASED UPON PRELIMINARY EUSERC354
<br /> INFORMATION PROVIDED BY THE UTILITY COMPANY AND ARE FOR BID PURPOSES ONLY. EL CTRIPG&EL METVERIZON WIRELESS
<br /> (N)750QPX BY PG&E IN (2)5"C ELECTRICAL METERING 200 P. MARSHALL &ASSOCIATES
<br /> (U/G-PVC SCH 40±) BY GC, 1#6 CUTLER-HAMMER AMPERE, 120/208 VOLT, 3 PHASE, A CENTERLINE COMMUNICATIONS COMPANY
<br /> 10. CONTRACTOR SHALL COORDINATE WITH UTILITY COMPANY FOR FINAL AND EXACT WORK/
<br /> MATERIALS REQUIREMENTS AND CONSTRUCT TO UTILITY COMPANY ENGINEERING PLANS AND GROUND, COPPER THHN/THWN-2 CIRCUIT BREAKER O 4 WIRE, ESD 35KVA,VD 3.5V
<br /> SPECIFICATIONS ONLY. CONTRACTOR SHALL FURNISH AND INSTALL ALL CONDUIT, PULL ROPES, 600AMPL�K 1000 HOLCOMB WOODS PKWY,SUITE 210
<br /> SOCKETS EUSERC 306 ROSWELL,GA 30076
<br /> CABLES, PULL BOXES, CONCRETE ENCASEMENT OF CONDUIT(IF REQUIRED), TRANSFORMER O OFFICE(678)280-2325
<br /> PAD, BARRIERS, POLE RISERS, TRENCHING, BACKFILL, PAY ALL UTILITY COMPANY FEES AND (N) SWITCHBOARD 600A, 120/208, TEST BLOCKS EUSERC 311
<br /> INCLUDE ALL REQUIREMENTS IN SCOPE OF WORK. 3PH - NEMA 3R ENCLOSURE O O
<br /> METAL COVER
<br /> AND HASP SOCKETS EUSERC 306
<br /> ISSUE STATUS:
<br /> TEST BLOCKS EUSERC 311
<br /> IfREV. DATE DESCRIPTION BY
<br /> PULLSECTION SOCKETS EUSERC 306 A 06/10/25 90% ZONING FA
<br /> EUSERC 327,347
<br /> TEST BLOCKS EUSERC 311 0 07/14/25 100% ZONING FA
<br /> METAL COVERS 1 07/22/25 100% ZONING FA
<br /> AND HASPS
<br /> 200 200 200 200
<br /> G
<br /> CIRCUIT BREAKERS
<br /> ELECTRICAL U/G SERVICE 11101 N UGC 800-3 W6MM8-3PGE ll
<br /> TERMINATION SECTION,
<br /> 600A,120/208V, 3 PHASE
<br /> (N)#2 GROUND COPPER
<br /> •
<br /> (N)3/4" C W/#2 GROUND COPPER
<br /> BONDED TO 5/8"X 8' LONG
<br /> PANEL SCHEDULE COPPERCLAD STEEL GROUND
<br /> ROD
<br /> (N)2"C-3#4/0, 1#6 GROUND,
<br /> COPPER THHN/THWN-2 (UP
<br /> MAIN ELECTRICAL PANEL
<br /> TO 150 FT)
<br /> MANUFACTURED BY INTERSECT, INC MODEL AA3003R SERIES LICENSOR:
<br /> 120/208 V, 1 PHASE, 3 WIRE, 30 kw, 200 AMP BUS, 42KAIC
<br /> 200 AMP/2P MAIN BREAKER (N)200A/2P ILC 120/208 V, 1 PHASE,
<br /> DESCRIPTION %N0.
<br /> PHASE 1 PHASE 2 CKT C DESCRIPTION 3 WIRE, MAIN PANEL BY
<br /> N0. B INTERSECT, INC- NEMA 3R
<br /> 30 1 3,600 - 2 30 NGHTS (TYP. OF 4)) SERVICE ENCLOSURE
<br /> L
<br /> 48VDC POWER PLANT RECTIFIER #1 48VDC POWER PLANT RECTIFIER #5 0
<br /> 2 3 - 3,600 4 /2P�
<br /> 30A 5 3,600 - 6 30A ATs
<br /> 48VDC POWER PLANT RECTIFIER #2 48VDC POWER PLANT RECTIFIER #6 0
<br /> /2P 7 - 3,600 8 /2P
<br /> (N) 3/4"-1#6 GROUND, INTERSECT LOAD CENTETR IT IS A VIOLATION OF LAW FOR ANY
<br /> COPPER BONDED TO MAIN W/30 CIRCUIT POSITIONS PERSONS, UNLESS THEY ARE
<br /> 30A 9 3,600 - 10 30A GROUND SYSTEM ACTING UNDER THE DIRECTION
<br /> 48VDC POWER PLANT RECTIFIER #3 48VDC POWER PLANT RECTIFIER #7 - OF A LICENSED PROFESSIONAL
<br /> 11 - 3,600 12
<br /> ENGINEER, TO ALTER THIS
<br /> 2 2P
<br /> DOCUMENT
<br /> 30 3,600 - 14 30
<br /> 48VDC POWER PLANT RECTIFIER #4 13 48VDC POWER PLANT RECTIFIER #8 (N)6-HR WIND UP PROJECT NAME:
<br /> /2P 15 3,600 16 /2P
<br /> WP/J BOX TIMER SWITCH
<br /> 17
<br /> 1 ,200 - 18 0 S CKT 26 FIBER CABINET/MISC. GFI RECEPTACLE 1 pi W
<br /> SURGE SUPPRESSOR
<br /> 2 19 - 1 ,200 20 0A z
<br /> FIBER CABINET/MISC. GFI RECEPTACLE 2
<br /> (N)2"C-3#1/0, 1#6 GROUND, Z
<br /> 15A Q 1"C-2#12, 1#12 GROUND COPPER, THHN/THWN-2 O O >
<br /> Lu
<br /> 48VDC POWER PLANT INTERIOR OUTLET 1 21 500 - 22 SPARE FOR FUTURE CABINET COPPER, THHN/THWN-2 Q
<br /> 0 - 1 ,200 24 20 TO MISC. CABINET � 0 �
<br /> STANDBY GENERATOR BATT. CHARGER P 23 P SPARE FOR FUTURE CABINET CKT22&24 Z M
<br /> o .4 In
<br /> STANDBY GENERATOR BLOCK HEATER 25 1 ,200 - 26 P SERVICE LIGHTS CKT 98&20 (N) 1"C FOR ALARM J on
<br /> CKTS 1 3 24 57 68 9 11 10 12 13 15 14 16 97 99 & 29 WIRING TO MISC. = Q
<br /> SPACE 27 - 500 28 - SPACE � ' �� �� ' �� �� �� �� �� >� CABINET
<br /> 2 "
<br /> SPACE 29 30 SPACE 2 O
<br /> (N) 1"C-2#12, 1#12 (N) 1"C-2#12, 1#12 F- a
<br /> LOAD PHASE 1 17,300 17,300 LOAD PHASE 2 GROUND, COPPER, GROUND, COPPER, C 4 ER, C-6# 10, 1# 10 GROUND N VERIZON WIRELESS 30KW cn
<br /> THHN/THWN-2 THHN/THWN-2 COPPER, THHN/THWN-2)&3/4" C- ( ) O
<br /> 2#12, 1#12 GROUND, COPPER THHN / KOHLER STANDBY GENERATOR 0
<br /> TOTAL LOAD (PHASE 1 & 2) = 34,600 VA THWN-2 W/164 GALLON DIESEL TANK uj
<br /> In
<br /> BASIN (UL142) ON
<br /> CO
<br /> ADDITIONAL 25% CONTINUOUS LOAD = 125 VA (N) VC-2#12, 1#12 GROUND (N) 10'-0"X 20'-0"CONCRETE PAD N
<br /> 48V COPPER, THHN/THWN-2 (STANDBY C4
<br /> TOTAL LOAD = 34,725 VA FUTURE MISC.
<br /> DC GENERATOR BATTERY CHARGER)
<br /> CABINET CAB/NET POWER
<br /> PLANT/
<br /> TOTAL AMPS = 144.7 AMPS G G G G BA G GY (N) VC-2#12, 1#12 GROUND COPPER,
<br /> THHN/THWN-2 (STANDBY GENERATOR
<br /> TOTAL KVA = 32.2 KVA
<br /> BLOCK HEATER) SHEET TITLE:
<br /> 150A
<br /> 2P M G SINGLE LINE DIAGRAM
<br /> CKT23 PANEL SCHEDULE &
<br /> (N)#2 AWG CKT25 UTILITY NOTES
<br /> G G
<br /> J J J J J J — Eml
<br /> (N)#4 AWG PER GENERAC
<br /> REQUIREMENTS