Laserfiche WebLink
Underground Storage Tank <br /> Monitoring System Certification Form <br /> 8. IN-TANK GAUGING TESTING <br /> El Check this box if tank gauging is used only for inventory control. <br /> ❑ Check this box if NO tank gauging equipment is installed. Yes No NA <br /> Do not complete this section if either box is checked. <br /> All wiring has been: 1) visually inspected for kinks, breaks and proper entry and ❑ ❑ ❑ <br /> termination; and 2 tested for ground faults? <br /> Were all in-tank gauging probes visually inspected for damage and residue buildup ❑ ❑ ❑ <br /> to ensure that floats move freely, functionally tested, and confirmed operational? <br /> Was accuracy of system's product level readings tested? ❑ ❑ ❑ <br /> Was accuracy of system's water level readings tested? ❑ ❑ ❑ <br /> Were all probes reinstalled properly? ❑ ❑ ❑ <br /> Were all items on the equipment manufacturer's maintenance checklist completed? ❑ ❑ I ❑ <br /> Probe ID Probe Model Tanks Monitored Pass Fail <br /> ❑ ❑ <br /> ❑ ❑ <br /> ❑ ❑ <br /> ❑ ❑ <br /> ❑ ❑ <br /> ❑ ❑ <br /> 9. COMMENTS <br /> Describe all answers marked "No"or "Fail'and proposed remedy. <br /> List all monitoring equipment either replaced or repaired. <br /> HAD A FEW ISSUES TODAY ON SITE , H2O IN SUMPS, UANSWERED ALARMS. <br /> ACTIVE ALARM CONDITIONS: <br /> L - 17 87 OCTANE FILL SUMP, IN LIQUID. <br /> L - 22 91 FILL SUMP & BRINE SENSORS, ALARM WOULDN'T CLEAR , CLEANED SENSOR, TESTED SENSOR <br /> AND PUT BACK IN SERVICE. BRINE RESERVOIR IS EMPTY. HOWEVER THIS IS THE ONLY SENSOR SETUP THAT <br /> USES THE 2 -1 SENSOR BLOCK, BOTH OF THESE SESNORS ARE WORKING FAULTY THESE ARE BOTH A FAIL <br /> AND NEED REPAIR/ RETEST. <br /> L - 24 DIESEL S T P SUMP BRINE , SENSOR TESTED GREAT. RESERVOIR IS EMPTY. <br /> L - 26 DIESEL FILL SUMP BRINE , SENSOR TESTED GREAT . RESERVOIR IS EMPTY. <br /> ALL THREE FILL SUMPS ARE ALSO FULL OF H20 , AT CONCLUSION OF TESTING WE REMOVED ALL LIQUID <br /> AND PLACED IN ON SITE CONTAINMENT. <br /> WE FOUND TWO BAD SENSORS DURING TESTING AS WELL, <br /> L - 12 DISPENSER 11/12 BRINE SENSOR DOES NOT FUNCTION, RESERVOIR HOLDS LIQUID. <br /> L - 22 91 FILL SUMP -2 0 8 DOES NOT ALARM. - BRINE ALARM AT ARRIVAL. <br /> IN THE TANK FIELD , ALL SUMP RESERVOIRS ARE LOW OR EMPTY. <br /> Page 5 of 6 <br />