Laserfiche WebLink
Underground Storage Tank <br /> Overfill Prevention Equipment Inspection Report <br /> 6. OVERFILL PREVENTION EQUIPMENT DETAILS <br /> 87 91 diesel <br /> Tank ID (one OPE per column) <br /> Are both vent and tank riser piping a Yes r Yes r. Yes r Yes <br /> secondarily contained? r No r No r No r No <br /> OPE Model oPw oPw oPw <br /> r Shut off W Shut off r Shut off Shut off <br /> Flow Flow Flow Flow <br /> F Restricts F Restricts r Restricts F Restricts <br /> What is the OPE response when activated? Flow Flow Flow Flow <br /> (Check all that apply) Audible r Audible r Audible F Audible <br /> Alarm Alarm Alarm Alarm <br /> Visual r Visual Visual Visual <br /> Alarm Alarm Alarm Alarm <br /> Are flow restrictors installed on vent piping r Yes* r Yes* r Yes* r Yes* <br /> that may interfere with the OPE operation? r No No No r No <br /> At what level in the tank is the OPE set to 103 101.625 102 <br /> activate? (Inches from bottom of tank) <br /> What is the percent capacity of the tank at <br /> which the OPE activates? 92.8 91.3 92.4 <br /> Is the OPE in proper operating condition to r. Yes r Yes r. Yes r Yes <br /> respond when the stored substance reaches r No r No r No r No <br /> the designated regulatory level? <br /> 7. SUMMARY OF TESTING RESULTS <br /> OPE Inspection Results r Pass t. Pass Pass r Pass <br /> r Fail r Fail r Fail r Fail <br /> 8. COMMENTS <br /> Describe all results marked "Fail"and each proposed remedy. <br /> *Mark here if: <br /> F Flow restrictors interfere with overfill prevention and equipment repairs required. <br /> Additional copies of this page may be attached. <br /> Attach tank chart(s), measurements, calculations, and In-Tank Setup report(s) <br />