Laserfiche WebLink
,# LDT 5000 Field Test Apparatus Page 1 of 1 <br /> Tat"l�Lnoiogy Line Leak Detector Test <br /> Work Order: 2383581 Date: 12/16/2025 <br /> Site Name/ID: 7-ELEVEN#20632, MKT 2368/20632 <br /> Address: 4627 DA VINCI DR @ MARCH LN <br /> City: STOCKTON State: CA Zip: 95207 <br /> Tank ID 87 91 diesel <br /> Product REGULAR PREMIUM Diesel <br /> Product Line 1 1 1 <br /> Tested From 4 4 4 <br /> Existing/New Existing Existing Existing <br /> Mechanical/Electronic Mechanical Mechanical Mechanical <br /> Manufacturer/Model Vaporless LD-2000 Vaporless LD-2000 Vaporless LD-2000 <br /> Serial No. 20091498 20091500 20091499 <br /> Pump Operating Pressure(psi) 30.00 30.00 28.00 <br /> Calibrated Leak(ml/min) 189.0 189.0 189.0 <br /> Calibrated Leak(gph) 3.00 3.00 3.00 <br /> Holding PSI 32.00 30.00 28.00 <br /> *N/A for Electronic LD's <br /> Resiliency(ml) 100.00 80.00 90.00 <br /> *N/A for Electronic LD's <br /> Metering PSI 19 19 17 <br /> *N/A for Electronic LD's <br /> Opening Time(sec) 5 4 5 <br /> *N/A for Electronic LD's <br /> rest Results Pass Pass Pass <br /> Technician Comments: <br /> Technician Name: Benjamin Baunach Certification#: 133637 <br /> Technician Signature: Expire Date: 4/16/2028 <br /> Environmental Compliance for Petroleum Systems <br /> ©2026 Tanknology Inc.,Austin,TX. All rights reserved. tanknology.com <br />