Laserfiche WebLink
SANJOA IN <br />COUNTY <br />Environmental Health Department <br />CFR 112.7 Failure of plan to fulfill basic requirements including a cross-referencing section <br />CFR 112.7(a)(3)(i) Plan failed to include oil type and storage capacity for each container <br />CFR 112.7(a)(3)(vi); 112.7(a)(4) Plan failed to adequately contain procedures for reporting a <br />discharge <br />CFR 112.7(c) Failure to provide adequate secondary containment, diversionary structures or <br />equipment (This is a repeat violation that should have been marked as Class II repeat) <br />Submit Return to Compliance by January 179 2019 <br />April 19, 2019 Facility remains out of compliance <br />• July 11, 2016- APSA Inspection by Rivera (Attachment 4) <br />Class II <br />CFR 112.3(d) Plan certification by a Professional Engineer (PE) missing or incomplete <br />CFR 112.7 Plan lacks approval of management to fully commit the necessary resources to <br />implement the Plan <br />CFR 112.7(a)(3) Plan failed to address facility layout, operations discharge prevention <br />methods and containers <br />CFR 112.7(c) Failure to provide adequate secondary containment, diversionary structures or <br />equipment to prevent discharge <br />CFR 112.7(e) Failed to conduct inspections or maintain records for 3 years <br />CFR 112.7(f)(1) Failed to train personnel on discharge prevention <br />CFR 112.7(f)(3) Failed to schedule and conduct discharge prevention briefings at least <br />annually <br />CFR 112.7(g) Plan failed to address security of site and valves, lock out/tag out and lighting <br />CFR 112.8(c)(2) Failed to provide and maintain adequate secondary containment <br />CFR 112.8(c)(6) Failed to perform scheduled tank tests and inspections by appropriately <br />qualified personnel <br />CFR 112.8(c)(8)(i4) Failed to provide each container with a high level monitoring device <br />CFR 112.8(d)(4) Failed to regularly inspect aboveground valves, piping, and appurtenances <br />Submit Return to Compliance by August 17, 2016 <br />Return to compliance documents submitted; did not address all violations. Facility was still <br />out of compliance during 2018 inspection. <br />HAZARDOUS WASTE <br />• December 17, 2018- HW Inspection by Baker (Attachment 8) <br />The inspection revealed two Class II violations: <br />Class II <br />3of5 <br />