Laserfiche WebLink
TIMERS: <br /> See timers K51 L, K51 H, K51 HL in Alarms. <br /> CALCULATIONS: <br /> None <br /> ALARMS: <br /> If Wetwell Level L51 is greater than High setpoint SP51 H <br /> for the duration of alarm delay SPT51 H (timer K51 H), <br /> AND switch U51 H is enabled; <br /> then post LAH51 Wetwell High Level alarm. <br /> If Wetwell Level L51 is less than Low setpoint SP51 L _ <br /> for the duration of alarm delay SPT51 L (timer K51 L), <br /> AND switch U51 is enabled; <br /> then post LAL51 Wetwell Low Level alarm. <br /> If Wetwell Level L51 is greater than High Transducer setpoint SP51 HH <br /> OR Wetwell Level L51 is less than Low Transducer setpoint SP51 LL <br /> for the duration of alarm delay SPT51 HL (timer K51 HL), <br /> AND switch U51 HL is enabled; <br /> then post LAHL51 Wetwell Transducer Fail alarm. <br /> 15 <br />