Laserfiche WebLink
CALCULATIONS: <br /> F74V - Averaging Flow is calculated as follows: _. <br /> F74V = ((F74 - F74V)/SP74K) + F74V <br /> FIQ74A- Total Flow totalization is the total pulse counts (Q74) (non- -- <br /> resettable). <br /> FIQ74B - Total Flow totalization is the total pulse counts (Q74) since the - <br /> value was manually reset by the operator R74R. <br /> ALARMS: <br /> If F74 is greater than High Transducer setpoint SP74HH <br /> OR F74 is less than Low Transducer setpoint SP74LL _ <br /> for the duration of alarm delay SPT74HL (timer K74HL), <br /> AND switch U74HL is enabled, <br /> then post FAHL74 Flow Transducer Fail alarm. <br /> The FAHL74 shall be latched in upon being set until operator manually resets <br /> via register Station Reset R99B OR SCADA Reset R99D. <br /> 17 <br />