Laserfiche WebLink
SPT11 W - 3rd Stage Start Delay Seconds <br /> SPT11X - 3rd Stage Stop Delay Seconds <br /> TIMERS: <br /> K11 S - 1 st Stage Start Timer Seconds <br /> K1 1T - 1st Stage Stop Timer Seconds <br /> K11 U - 2nd Stage Start Timer Seconds <br /> K11 V - 2nd Stage Stop Timer Seconds <br /> K11W - 3rd Stage Start Timer Seconds <br /> K11 X - 3rd Stage Stop Timer Seconds <br /> COUNTERS/TOTALIZERS: <br /> None <br /> CONTROL: <br /> The following (part a, b) is a typical control for the switch S11A. All switches <br /> (S11 B, -;11C) set/reset shall follow S11A format: <br /> If L5'I is above 1 st stage pump start SP11 S <br /> for the duration of start delay SPT11 S (timer K11 S); <br /> then set 1st stage switch S1 1A. <br /> If: L51 is below 1st stage pump stop SP1 1T <br /> for the duration of stop delay SPT11T (timer K11T); <br /> then reset 1st stage switch S11A. <br /> The sequence of the order for pumps to be called shall be per the code <br /> number set in register SP1 1A. When a new code number is set in register <br /> SP1 1A the sequence shall be changed per the following definitions: <br /> PUMP CALL SEQUENCE <br /> LOGICAL OUTPUT <br /> CODE <br /> NUMBER Pump P1 Pump P2 Pump P3 Pump P4 <br /> SET IN Call X1 U Call X2U Call X3U Call X4U <br /> SP11A Assignment to Assignment to Assignment to Assignment to <br /> 0 Rotate Rotate Rotate Rotate <br /> 123 S'l1A S11B S11C --- <br /> 234 -- S11A S11B S11C <br /> 341 Si 1C -- S11A S11B <br /> 412 S11B S11C -- S11A <br /> 124 S11A S11B -- S11C <br /> 132 S11A S11C S11B -- <br /> 142 S11A S11C -- S11B <br /> 134 S1 1A -- S11B S11 C <br /> 143 S11A -- S11C S11B <br /> 312 S11B S11 C S11A -- <br /> 314 S11B -- S11A S11C <br /> 413 S11B -- S11C S11A <br /> 22 <br />