Laserfiche WebLink
CONTROL: <br /> HS1 - HAND Position -" <br /> Hand control is done from the hand switch at Pedestal and the running of <br /> the Pump is independent of the LLC. -- <br /> HS1 - OFF Position <br /> Stops Pump independent of the LLC and lockouts the Pump from LLC <br /> control. <br /> HS1 - AUTO Position <br /> If the switch (HS1) status Y1 is in READY position, <br /> AND no Pump fail lockout UAY1X has been posted, - <br /> AND sequential timer K10M has exceeded SPT10M; <br /> then upon receipt of Call signal X1 U <br /> set X1 to call pump P1 to operate. <br /> If the switch (HS1) status Y1 is in not READY position, <br /> OR Pump fail lockout UAY1 X has been posted, <br /> OR pump call X1 U has been removed; <br /> then remove X1 pump P1 call. <br /> If a Pump has just stopped as indicated by N1 OR N2 OR N3 OR N4; -- <br /> then the PID calculation shall be set to MANUAL, set to increment SP20D <br /> speed for SPT20D seconds (timer K20D); <br /> the PID will be then set to AUTO. <br /> TIMERS: <br /> If a Pump is started as indicated by N1 OR N2 OR N3 OR N4; <br /> then clear the timer K1 OM to restart sequential time delay. <br /> Pumps shall be sequentially restarted with the SPT10M time delay before <br /> the first Pump is started when LLC is placed in RUN mode and between <br /> each Pump called thereafter. <br /> CALCULATIONS: <br /> None. <br /> ALARMS: <br /> None. <br /> 25 <br />