Laserfiche WebLink
Section 15060 <br /> PIPING SYSTEMS <br /> PIPING SYSTEM SPECIFICATION <br /> SERVICE: SANITARY SEWER FORCE MAIN SYMBOL: <br /> SSFM <br /> FLUID: WASTEWATER <br /> PRESSURE(PSIG) TEMPERATURE(°F) <br /> WORK: 120 MAX: 150 TEST: 150 NORMAL: MAX: <br /> TEST MEDIUM: WATER TEST DURATION: <br /> PIPE AND FITTING SPECIFICATION <br /> SIZE EXPOSURE PIPE FITTINGS <br /> 6", 10" Buried Ductile Iron pipe,AWWA C150, push-on, Ductile Iron,AWWA C110, mechanical <br /> joint or flanged, lined as pipe, per Section <br /> (non-HDD) epoxy lined per Section 15068. 15068. <br /> 10" Buried HDPE per Section 15072. AWWA C906 per Section 15072. <br /> (HDD) <br /> GENERAL VALVE SPECIFICATIONS,UNLESS OTHERWISE SPECIFIED IN VALVE SCHEDULE <br /> SIZE EXPOSURE DUTY SPECIFICATION OPERATOR <br /> 10" Buried Isolation Gate valves,flanged,per Section 15101 Manual per Section <br /> 15101 <br /> 10" Buried Backflow Check valve, AWWA C508 per Section 15105 Swing check <br /> prevention <br /> REMARKS: Restrained joints shall be furnished for all ductile iron sanitary sewer force main. <br /> Walnut Grove Sewer Project(Conformed) 15060-18 SA0160401 <br /> March 2008 n:\sa0160401\specs\wg conform\div 15\15060.doc <br />