1 2 3 4 5 6 7 8
<br />CONTROL DIAGRAM SYMBOLS WIRING DEVICES MOTORS AND EQUIPMENT ONE-LINE DIAGRAM SYMBOLS
<br />120V CONTROL RELAY SWITCHES: (-Y-Tn POWER TRANSFORMER.
<br />CONTROL TRANSFORMER, PRIMARY 2 OPERATING COIL DISCONNECT SWITCH, NON-FUSED I SIZE 2 COMBINATION FULL VOLTAGE
<br />AND SECONDARY VOLTAGES SHOWN, NON-REVERSING MAGNETIC STARTER 5.757 Z 480/277V IMPEDANCE SHOWN
<br />SIZE AS SHOWN OR SPECIFIED CR CR = CONTROL RELAY UNLESS OTHERWISE SPECIFIED, ALL SWITCHES MCP SIZED BY MANUFACTURER
<br />120V U = UNLATCH ARE WALL MOUNTED. MOT=MOTOR (OVERLOAD RELAY NOT SHOWN)
<br />FUNCTION L = LATCH M SV=SOLENOID VALVE RV = REDUCED VOLTAGE
<br />CV=CONTROL VALVE 2S2W = TWO-SPEED TWO-WINDING 480V
<br />CIRCUIT BREAKER, THERMAL- TOGGLE SWITCH, SINGLE POLE, A=ADJUSTABLE SPEED DRIVE 2 = SIZE 2 30, 4W GENERATOR. POWER RATING, 40A RATING IN AMPS 125 = 125HP 600KW T
<br />MAGNETIC, 3 POLE, LION, OL 20 AMP 12 FREQUENCY, VOLTAGE,
<br />I THERMAL OVERLOAD RELAY 60HZ
<br />GANGED SWITCHES IN COMMON BOX � FIELD INSTRUMENT SHOWN
<br />2CR 2CR
<br />DESIGNATES PLC INPUT $ $ WITH COMMON WALL PLATE 400/3 -_
<br />n TERMINATION OR CONTROL F- �/�— OUTPUT CONTACTS 3 CURRENT TRANSFORMER WITH
<br />Ip
<br />PANEL TERMINATION SUPERSCRIPT INDICATES CIRCUIT CONTROL STATION. SEE CONTROL DIAGRAMS FOR DEVICES REQUIRED 3 RATIO AND NUMBER OF UNITS
<br />_
<br />FUSE 2 TIMING RELAY CONTROLLED: a, b, c, ETC. MAY BE 200 AMP SHOWN
<br />TR OPERATING COIL A COMBINED WITH CIRCUIT NUMBER. 200A
<br />MODIFIERS: EXAMPLE: la, 4b, ETC.
<br />CLF = CURRENT LIMITING FUSE ON or OFF DELAY 3 TELEPHONE & COMMUNICATION SYSTEMS
<br />DE = DUAL ELEMENT RANGE:SEC/MIN B MAIN SERVICE METER
<br />F = CLASS F FUSE WITH
<br />SET:SEC/MIN
<br />Ip SUBSCRIPT MODIFIER INDICATES: FU BLOWN INDICATOR
<br />1_2 = DOUBLE POLE UNLESS OTHERWISE SPECIFIED, TELEPHONE
<br />O O PUSHBUTTON, MOMENTARY CONTACT, 3 = THREE WAY OUTLETS SHALL BE MOUNTED AT SAME HEIGHT
<br />DESCPTN NORMALLY OPEN NOROMA LY NORC OSE Y 4 = FOUR WAY AS THE RECEPTACLES, VERIFY. MF MULTI-FUNCTION ELECTRONIC METER
<br />ID
<br />K = KEY OPERATED EXTERNAL LINE OR PLANT PHONE f
<br />3 PUSHBUTTON, MOMENTARY CONTACT, 2TR 2TR OR DELAY ON COIL MC = MOMENTARY CONTACT, THREE SYSTEM OUTLET
<br />O I O NORMALLY CLOSED O OR � ENERGIZATION POSITION ,
<br />DESCPTN TC TO ON DELAY MS = MANUAL (MOTOR) STARTER OR MODIFIERS:
<br />ID SWITCH T TELEPHONE
<br />STOP PUSHBUTTON WITH LOCKOUT �O 0—:T0R = RHEOSTAT (DIMMER, SPEED� POSITION (LIMIT)
<br />SWITCH CONTROL)
<br />DESCPTN RECEPTACLES:
<br />O GROUNDING GENERAL NOTES
<br />ID TEMPERATURE
<br />SWITCH UNLESS OTHERWISE SPECIFIED, ALL RECEPTACLES
<br />O ARE 125 VOLT, SINGLE PHASE, STRAIGHT BLADE,
<br />H A NON LOCKING, GROUNDING STYLE. O GROUND ROD 1. THIS DRAWING IS GENERAL IN NATURE. SOME SYMBOLS SHOWN HEREON MAY NOT BE
<br />PRESSURE
<br />O USED ON THE CONTRACT DRAWINGS.
<br />SWITCH �Q} GROUND ROD WITH GROUND WELL 2. IDENTIFICATIONS (ID), SIZES, RATINGS, LOCATIONS AND SIMILAR INFORMATION SHOWN
<br />SELECTOR SWITCH DUPLEX RECEPTACLE, 20 AMP, `CY 3 WIRE ASSOCIATED WITH SYMBOLS ARE OPTIONAL; EXAMPLES OF SUCH INFORMATION ARE
<br />3 POSITION MAINTAINED CONTACT SHOWN WITH SOME SYMBOLS FOR CLARITY.
<br />X = CONTACTS CLOSED RECEPTACLE MODIFIERS: GROUND CONNECTION, BOLTED TYPE
<br />3. THE ELECTRICAL DRAWINGS USE THE ONE-LINE DIAGRAMS AND PANEL SCHEDULES IN
<br />GROUND CONNECTION, COMPRESSION CONJUNCTION WITH SHOWING THE LOCATION OF THE ELECTRICAL/INSTRUMENTATION
<br />46 L = LENS COLOR: WP = WEATHER PROOF TYPE SOURCES AND LOADS/DEVICES SHOWN ON THE PLAN DRAWINGS TO DEPICT THE WORK.
<br />GF = GROUND FAULT CIRCUIT THE CONTRACTOR SHALL USE THESE DOCUMENTS TO DETERMINE AND PROVIDE THE
<br />A =AMBER INTERRUPTER NECESSARY RACEWAY AND WIRING SYSTEM FOR EACH CIRCUIT. ALL INDOOR RACEWAY
<br />B = BLUE H = HAZARDOUS AREA- G GROUNDING CONDUCTOR, MINIMUM SHALL BE RUN EXPOSED, AND ROUTED BY THE CONTRACTOR, UNLESS OTHERWISE
<br />G = GREEN EXPLOSION PROOF #2/0 BARE COPPER NOTED. THE TYPE OF RACEWAY AND WIRE USED SHALL BE AS SPECIFIED IN THE
<br />R = RED SPECIFICATIONS UNLESS OTHERWISE NOTED.
<br />LINEW = WHITE DOUBLE DUPLEX RECEPTACLE, 4. THE LOCATION OF THE CONTROL STATIONS SHOWN ON THE PLAN DRAWINGS ARE
<br />INDICATING LIGHT INSTRUMENT CABLE SHIELD GROUND DIAGRAMMATIC AND THE ACTUAL LOCATION SHALL BE COORDINATED IN THE FIELD WITH
<br />L
<br />THE OWNER.
<br />PUSH TO TEST, TEST —_
<br />LEGEND VOLTAGE TERMINAL SHOWN 5. THE EXACT LOCATION OF THE MOTORS AND ACCESSORIES ARE NOT SHOWN. THE
<br />CONTRACTOR SHALL COORDINATE AND REFER TO OTHER DRAWINGS FOR CONDUIT
<br />STUBOUT AND TERMINATION LOCATIONS.
<br />STANDARD ABBREVIATIONS LIGHTING CIRCUITS AND RACEWAYS MISCELLANEOUS 6. ALL EQUIPMENT SHALL BE LABELED WITH NAMEPLATES. DESCRIPTION OF EQUIPMENT
<br />SHALL BE IN ACCORDANCE WITH THE ONE-LINE DIAGRAM DESCRIPTION. A LIST OF THE
<br />NAMEPLATES SHALL BE SUBMITTED TO THE CONSTRUCTION MANAGER PRIOR TO
<br />ENGRAVING.
<br />FIXTURE IDENTIFIER: "" OVERHEAD POWER LINES
<br />A AMMETER 1 7. UNLESS OTHERWISE NOTED, ALL CONVENIENCE OUTLETS SHALL BE MOUNTED AT
<br />AUTOMATIC TRANSFER SWITCH - RACEWAY IN CONCRETE TYPICAL DETAIL DESIGNATION 48-INCHES ABOVE FINISHED FLOOR. ALL LIGHT SWITCHES SHALL BE MOUNTED AT
<br />ATS NUMBER OF FIXTURES (SHOWN TYP E-7 54-INCHES ABOVE FINISHED FLOOR.
<br />CONDUIT BCW BARE COPPER WIRE ONLY WHEN REQUIRED FOR
<br />C CONDUIT ONLY (EMPTY CONDUIT) CLARITY) — — — RACEWAY CONCEALED (UNDERGROUND) 8. EACH CONVENIENCE OUTLET AND LIGHTING CIRCUIT SHALL BE PROVIDED WITH A #12AWG
<br />C.O.
<br />CP CONTROL PANEL II� GROUND CONNECTION GREEN GROUNDING CONDUCTOR
<br />CPT CONTROL POWER TRANSFORMER FIXTURE TYPE REFER TO FIXTURE RACEWAY TURNED TOWARD
<br />CS CONTROL SWITCH SCHEDULE TYPE APPLIES TO ALL THE VIEWER. PROGRAMMABLE LOGIC 9. IN GENERAL, LANDFILL SITE IS CONSIDERED AS CLASSIFIED HAZARDOUS LOCATION. ALL
<br />CT CONTACTOR (HEAVY DUTY) FIXTURES OF THE SAME SHAPE CONTROLLER 1/0 CONDUITS ENTERING OR LEAVING UNDERGROUND SHALL BE PROVIDED WITH "EYS" SEALS
<br />FS FLOAT SWITCH WITHIN A ROOM OR AREA.RACEWAY TURNED DOWN FILLED WITH COMPOUND RECOMMENDED BY SEAL MANUFACTURER AFTER CONDUCTORS
<br />G GROUND ARE INSTALLED.
<br />HZ HERTZ O THERMOSTAT
<br />KVAR REACTIVE POWER R MOUNTING: EXPOSED RACEWAY
<br />KW K I LOWATT
<br />KWHR KILOWATTHOUR 5 XX C = CEILING R = RECESSED HH23 O NOTE DESIGNATION
<br />1/0 INPUT/OUTPUT 2/408-6 PP = POLE S = STANCHION MANHOLE (MH) OR HANDHOLE (HH),
<br />LOS LOCKOUT STOP P = PENDANT W = WALL DESIGNATES EQUIPMENT OR
<br />MOTOR CONTROL CENTER p
<br />MCC DEVICE LOCATED AT LOAD Underground Service Alert
<br />MCP MOTOR CIRCUIT PROTECTOR IN THE FIELD
<br />MF MULTI-FUNCTION METER DISPLAY MOUNTING HEIGHT, FLOOR TO O JUNCTION BOX. o Call: TOLL FREE
<br />MIN MINIMUM 1-800
<br />MSGR MAIN SWITCHGEAR BOTTOM OF FIXTURE LION. DESIGNATES EQUIPMENT OR 227-2600
<br />NC NORMALLY CLOSED AHAP = AS HIGH AS POSSIBLE. TB TERMINAL BOX. DEVICES LOCATED IN MCC
<br />TWO WORKING DAYS
<br />NIC NOT IN CONTRACT BEFORE YOU DIG
<br />NO NORMALLY OPEN 3#10 AWG DESIGNATES EQUIPMENT OR
<br />PAIR OR PR TWISTED, SHIELDED PAIRS NUMBER OF LAMPS/LAMP WATTAGE DEVICES LOCATED IN IF SHEET IS LESS THAN 24" BY 36", THEN IT IS A REDUCED PRINT-SCALE REDUCED ACCORDINGLY.
<br />PB PULL BOX + #10 AWG G, 1 C CONTROL PANEL E
<br />PLC PROGRAMMABLE LOGIC CONTROLLER LIGHTING FIXTURE SHAPES AND SCALE ARE RACEWAY SIZE WITH CONDUCTOR
<br />PP POWER POLE REPRESENTED WHERE POSSIBLE. THE CONTENTS AND SIZES. PUMP CONTROLLERS
<br />OH OVERHEAD REV DATE DESCRIPTION DRN APP
<br />RESISTANCE THERMAL DETECTOR EXAMPLES SHOWN BELOW ARE TYPICAL LP-1 DISCRETE OUTPUT
<br />RTD APPLICATIONS.
<br />RTU REMOTE TERMINAL UNIT CIRCUIT HOMERUN W/ DESTINATION
<br />SCADA SUPERVISORY CONTROL & DATA ACQUISITION NOTED (2#12, #12 GND MIN.) IONIZATION SMOKE DETECTOR Geosynte&
<br />SSRS
<br />SOLID STATE REDUCED VOLTAGE STARTER ENGINEERS, INC.
<br />SWGR SWITCHGEAR FLUORESCENT FIXTURE �� TELEPHONE SYSTEM CONDUIT consultants Oakland, San Francisco, Orange County, CA
<br />THD HARMONIC DISTORTION T El END—OF—LINE DEVICE
<br />TS TEMPERATURE SWITCH / WITH PULLING NYLON ROPE 1111 BROADWAY, 6TH FLOOR 1611 TELEGRAPH ABENUE, SUITE 609 1810 EAST HAMILTON AVENUE
<br />V VOLTMETER OAKLAND, CA 94607 OAKLAND, CA 94612 STOCKTON, CA 95205
<br />VFD VARIABLE FREQUENCY DRIVE LIGHT CIRCUIT W/ CONDUCTOR �F FIRE ALARM PULLSTATION PHONE: 510.636.3034 PHONE: 510.267.0441 PHONE: 209.466.3000 WP WEATHER PROOF (NEMA 4X) I 0 I _o WALL MOUNTED FIXTURE
<br />XFMR TRANSFORMER QUANTITY INDICATED TITLE:
<br />ELECTRICAL LEGEND AND GENERAL NOTES
<br />FVNV FULL VOLTAGE NON-REVERSING STARTER
<br />MDP-4XX DESIGNATES 480V CIRCUIT �F COMBINATION STROBE LIGHT/HORN
<br />PROJECT:
<br />\ \ EMERGENCY LIGHTING UNIT. PS-21 XX DESIGNATES 21 KV CIRCUITCONSTRUCTION OF AREA 2A
<br />SELF CONTAINED. FIREALARM CONTROL PANEL
<br />ZULF SPACE HEATER SITE: FOOTHILL SANITARY LANDFILL
<br />SAN JOAQUIN COUNTY, CALIFORNIA f
<br />THIS DRAWING MAY NOT BE ISSUED QqpFESS10 DESIGN BY: TP DATE: NOVEMBER 2014
<br />FOR PROJECT TENDER OR Q `�
<br />CONSTRUCTION, UNLESS SEALED. y O }� AWN BY: LD PROJECT NO.: WG1780
<br />v
<br />CHECKED BY: DN FILE: WG1780_EO01
<br />SI TURE REVIEWED BY: DTN DRAWING NO.: E-1
<br />D �OAL PROVED BY: DTN 14 of 25