Laserfiche WebLink
16" min <br />20" max <br />Hydrant <br />Pumper outlet <br />(Facing street) <br />2" min <br />4" max <br />1 • <br />u <br />Standard - <br />valve box <br />4" Clearance <br />/_ Mechanical Joint <br />��\��\\,/`� Gate valve <br />Thrust block �' �- Concrete block <br />TYPICAL ASSEMBLY <br />Hydrant "T" <br />Thrust block <br />NOTES: <br />1. Hydrant model to be approved by agency. <br />2. See standards for proper location of hydrant. <br />3. Hydrant shall be clean and free of concrete. <br />4. Hydrants shall be painted yellow, in accordance with agency standards. <br />5U 6" dia PVC pipe (AWWA C-900 with CIP equivalent OD) <br />© Fire hydrant laterals greater than 100 LF, shall have a gate valve installed <br />near the fire hydrant as approved by the agency. <br />7❑ Break—away spool with hollow break—off bolts (nut on bottom at connection to hydrant). <br />® Expansion joint material where hydrant is placed in concrete. <br />9❑ Blue reflective marker shall be placed 12" towards hydrant from center of street. <br />1101 Clow Valve Company breakoff check valve Model LBI 400A or equal. <br />FIRE HYDRANT ASSEMBLY <br />No. Revision Description Date <br />COUNTY OF SAN JOAQUIN <br />Ai I DEPARTMENT OF PUBLIC WORKS <br />Wwung for YOU I I Date: DEC 2014 Std. Dwg. No. W -Z <br />