Laserfiche WebLink
2 � 3 <br />VICINITY MAP <br />1. INSTALL NEW (5) ANODE, VERTICAL SHALLOW ANODE BED WITH 5 FT SPACING AT -38.024164 -121.081857. <br />2. INSTALL NEW RECTIFIER ON POLE AT 38.023977 -121.081933 <br />3. INSTALL 2 - NEW CU GROUND RODS PER GS&S 0-11.1 <br />4. INSTALL 2 - NEW CATHODE LEADS TO - 2 INCH GAS MAIN <br />5. ANODE WIRES AND NEW CATHODE LEADS TO BE LANDED IN NEW AJB PER GS&S 0-13.2 <br />6. INSTALL WATCHDOG SCOUT RMU TO NEW RECTIFIER <br />7. INSTALL NEW 1OA/40V POLE MOUNTED RECTIFIER PER 0-11.3, LOCATED AT 38.023977 -121.081933 <br />8. PERMIT REQUIRED <br />4 <br />5 <br />6 <br />7 <br />V CA� S A _0VV BED C <br />1. PRIOR TO STARTING WORK, CONTACT LOCAL AREA CORROSION SUPERVISOR REGARDING CATHODIC PROTECTION REQUIREMENTS AND I&R SUPERVISOR REGARDING ANY SHUTDOWN, ABANDONMENT, <br />OR TIE-IN OF ANY MAINS WHICH MAY AFFECT ANY DISTRICT REGULATOR STATION. <br />2. ALL STEEL TIE-INS, CUT OFFS AND CAPPING OF CAST IRON AND STEEL MAIN PER A-36 AND C-37. <br />3. ALL PLASTIC CONNECTIONS TO BE PERFORMED IN ACCORDANCE WITH THE APPROPRIATE PROCEDURES LISTED IN TD -4170S. <br />4. UNLESS OTHERWISE NOTED, CONSTRUCTION TO REFERENCE TD -4125P-09 TO DETERMINE EXISTING STEEL PIPE SPECS. <br />5. ALL ARC WELDING IS TO BE PERFORMED IN ACCORDANCE WITH THE GAS WELDING CONTROL MANUAL TD -4160M. REFER TO TD-416OP-20 FOR GENERAL WELDING REQUIREMENTS. <br />6. PURGE MAINS 10" IN DIAMETER & LESS PER GS&S A-38, ATTACHMENT A, PROCEDURE 2. PURGE MAINS GREATER THAN 10" IN DIAMETER PER GS&S A-38, ATTACHMENT A, PROCEDURE 3. <br />7. ABANDON ALL UNDERGROUND GAS FACILITIES PER UTILITY PROCEDURE TD-950OP-16 & GS&S A-93.2. <br />8. PLACE ELECTRONIC MARKING SYSTEM (EMS) DEVICES ON ALL CUT OFF ENDS AND SECTIONALIZING POINTS OF DEACTIVATED PIPE PER TD-950OP-16. <br />9. FOLLOW ALL MINIMUM INSTALLATION DEPTHS FOR TRANSMISSION, DISTRIBUTION AND SERVICE PIPE BY CLASS LOCATION AND SOIL TYPES OUTLINED IN GS&S A-04. <br />10. ALL GAS RISERS ARE TO BE INSTALLED IN ACCORDANCE WITH GS&S J-15 & J-15.1. <br />11. INSTALL METER PROTECTION PER GS&S J-95. <br />12. VENT REGULATORS PER GS&S H-93. <br />13. LOCATION OF EXISTING UTILITIES ARE APPROXIMATE. CALL UNDERGROUND SERVICES ALERT (USA) TO CONFIRM. GAS PIPELINES MUST BE INSTALLED WITH AT LEAST 3' OF SEPARATION (5' <br />PREFERRED) ON ANY PARALLELED INSTALLATION FROM ANY WET UTILITY AND 12" MINIMUM FROM ANY PERPENDICULAR CROSSING PER U.O. STANDARD S5453. <br />14. CONSTRUCTION SHALL NOTIFY MAPPING WITHIN 24 HOURS OF ALL OPERATIONAL CHANGES TO MAINS, INCLUDING EVERY TIE-IN, CUT OFF, UPRATE, ETC. PER U.O. STANDARD S4412. <br />15. ALL STEEL RISERS ARE TO BE REPLACED WITH NON CORRODIBLE RISERS OR REPLACED BY USING THE RISER INSERT RENEWAL INSTALLATION PER GS&S A-90. <br />16. ALL SERVICES AND MAINS TO BE TESTED PRIOR TO TIE-IN PER GS&S A-34. <br />17. INSTALL PLASTIC MAIN, SERVICES, & LOCATING WIRE PER GS&S A-34, A-90, A-90.2, A-90.3, A-91, A-93, A-93.1, A-93.3, UTILITY STANDARD TD -4170S, D-34 & CORROSION CONTROL <br />STANDARD TD -4181S. <br />18. INSTALL ANODES PER CORROSION CONTROL MANUAL 0-13.1. <br />19. INSTALL ELECTROLYSIS TEST STATIONS PER CORROSION CONTROL MANUAL 0-10 AND 0-10.1. IF PRACTICAL, INSTALL ETS STATION OUT OF THE ROADWAY. <br />20. ALL EXCAVATION TO BE PERFORMED PER TD -5811M, TD -5811P-301, TD -5811P-105, TD -4412P-05, AND TD -4621S. STANDBY REQUIRED IF EXCAVATING WITHIN 5' OFA CRITICAL FACILITY, <br />BORING ACTIVITY THAT CROSSES OR THAT PARALLELS WITHIN 10' OF A CRITICAL FACILITY. CONTACT THE CONSTRUCTION SUPERVISOR. <br />21. NOTIFY SCHOOLS AND HOSPITALS WITHIN 500' OF PROPOSED EXCAVATION FOR GAS FACILITIES A MINIMUM OF 3 DAYS PRIOR TO DIGGING PER AB 1937. <br />22. ANY PIPE REPLACEMENT VIA SPLITTING TO BE DONE PER TD -4634P-01 & TD -4634P-02. <br />23. CAMERA INSPECTION (PRE/POST) FOR TRENCHLESS METHODS TO BE PERFORMED PER TD -4632P-01. <br />24. WARNING TAPE IS TO BE INSTALLED IN OPEN TRENCH INSTALLATION OVER GAS PIPELINES IN BOTH TRANSMISSION AND DISTRIBUTION FACILITIES. THIS INCLUDES BELL HOLES, EXCAVATIONS FOR <br />REPAIR PURPOSES AND RISER REPLACEMENTS PER GS&S L-16. <br />25. DEVIATIONS FROM THIS APPROVED DESIGN SHALL BE PROCESSED IN ACCORDANCE WITH TD -4014P-05 "FIELD DESIGN CHANGE PROCESS FOR DISTRIBUTION LINES AND DUAL -ASSET FACILITIES." <br />26. ALL TRENCH SPOILS AND BACKFILL MUST BE USED OR DISPOSED WITH AS REQUIRED BY PG&E SPECIFICATIONS AND ANY LOCAL CITY, COUNTY OR STATE REQUIREMENTS. <br />27. PG&E TO INSTALL/RESTORE TEMPORARY AND/OR PERMANENT PAVING IN ACCORDANCE WITH PG&E SPECIFICATIONS AND ANY LOCAL CITY, COUNTY OR STATE REQUIREMENTS. <br />28. STAND-BY REQUIREMENTS MUST BE IN ACCORDANCE WITH TD -5811P-301, TD -5811P-105 & TD -581113-005 WITH WORKING NEAR ANY CRITICAL FACILITIES. <br />29. MONUMENT PRESERVATION AS REQUIRED BY THE PROFESSIONAL LAND SURVEYORS' ACT (BUSINESS AND PROFESSION CODE SUB -SECTION 8700-8805) SECTION 8771; PRIOR TO THE START OF <br />CONSTRUCTION, ALL SURVEY MONUMENTS, WITHIN THE PROJECT LIMITS THAT HAVE THE POSSIBILITY OF BEING DAMAGED OR DESTROYED DURING CONSTRUCTION, MUST BE LOCATED, AND <br />REFERENCED BY A LICENSED LAND SURVEYOR, AND A CORNER OF RECORD OR RECORD OF SURVEY SHALL BE FILED WITH THE COUNTY SURVEYOR. IF ANY OF THESE SURVEY MONUMENTS ARE <br />DESTROYED, DAMAGED OR COVERED OVER DURING CONSTRUCTION, A NEW MONUMENT AND MONUMENT BOX MUST THEN BE SET IN ITS PLACE, AT THE ORIGINAL LOCATION, BY A LICENSED <br />LAND SURVEYOR, AND ANOTHER CORNER OF RECORD OR RECORD OF SURVEY FILED WITH THE COUNTY SURVEYOR. <br />30. CONSTRUCTION MEANS AND METHODS MAY DEVIATE PER FIELD VERIFIED CONDITIONS IN ACCORDANCE WITH LOCAL JURISDICTION REQUIREMENTS. IF THERE ARE ANY QUESTIONS, CONTACT <br />RESPONSIBLE ENGINEER. <br />5231 COX RD <br />LINDEN, CA <br />PLAN VIEW <br />DR 0 <br />DICARLO o x <br />Uj <br />1'.- <br />d <br />TIED HP HP <br />EX.2"PL-3'-1979 <br />82 <br />1 /2 "PL 982 <br />_rq,,,X <br />00 <br />=i <br />J J �♦� <br />N 15' <br />i5 <br />i <br />5' <br />0+7 <br />i <br />i <br />i <br />5267 d <br />150' <br />i <br />i <br />a <br />T � <br />------------------ <br />32' <br />-----------j32' i <br />i <br />0 <br />J= <br />N <br />N <br />W <br />N o <br />Ln <br />8 <br />X006-1 <br />- HP <br />EXISTING GAS MAIN (SIZE NOTED) <br />- - - - - - <br />) <br />0 <br />MONTE VISTA DR <br />- ANODE WIRES (INSTALL) <br />< <br />Co <br />X <br />WORK SITE <br />z <br />DEEP WELL ANODE (INSTALL) <br />0 <br />SHALLOW ANODE (INSTALL) <br />0 0 <br />�:;u z <br />mz <br />z <br />�:;u <br />z <br />GROUND ROD (INSTALL) <br />C") cr) <br />-I <br />o o <br />z>< <br />DI CAR LO CT <br />RECTIFIER (EXISTING) <br />© <br />C/ 0 <br />PLANNING ENGINEER <br />PG&E POLE (EXISTING) <br />HAILEY IRIRBARNE <br />E GRACE ST <br />707-836-6002 <br />COLIN MOXON <br />D <br />z <br />TBA <br />WORKING FOREMAN A <br />TBA <br />TBA <br />GC FIELD ENGINEER <br />TBA <br />JOB DATA <br />U) <br />i <br />C� <br />CITY: LINDEN <br />U S2 <br />COUNTY: SAN JOAQUIN <br />1. INSTALL NEW (5) ANODE, VERTICAL SHALLOW ANODE BED WITH 5 FT SPACING AT -38.024164 -121.081857. <br />2. INSTALL NEW RECTIFIER ON POLE AT 38.023977 -121.081933 <br />3. INSTALL 2 - NEW CU GROUND RODS PER GS&S 0-11.1 <br />4. INSTALL 2 - NEW CATHODE LEADS TO - 2 INCH GAS MAIN <br />5. ANODE WIRES AND NEW CATHODE LEADS TO BE LANDED IN NEW AJB PER GS&S 0-13.2 <br />6. INSTALL WATCHDOG SCOUT RMU TO NEW RECTIFIER <br />7. INSTALL NEW 1OA/40V POLE MOUNTED RECTIFIER PER 0-11.3, LOCATED AT 38.023977 -121.081933 <br />8. PERMIT REQUIRED <br />4 <br />5 <br />6 <br />7 <br />V CA� S A _0VV BED C <br />1. PRIOR TO STARTING WORK, CONTACT LOCAL AREA CORROSION SUPERVISOR REGARDING CATHODIC PROTECTION REQUIREMENTS AND I&R SUPERVISOR REGARDING ANY SHUTDOWN, ABANDONMENT, <br />OR TIE-IN OF ANY MAINS WHICH MAY AFFECT ANY DISTRICT REGULATOR STATION. <br />2. ALL STEEL TIE-INS, CUT OFFS AND CAPPING OF CAST IRON AND STEEL MAIN PER A-36 AND C-37. <br />3. ALL PLASTIC CONNECTIONS TO BE PERFORMED IN ACCORDANCE WITH THE APPROPRIATE PROCEDURES LISTED IN TD -4170S. <br />4. UNLESS OTHERWISE NOTED, CONSTRUCTION TO REFERENCE TD -4125P-09 TO DETERMINE EXISTING STEEL PIPE SPECS. <br />5. ALL ARC WELDING IS TO BE PERFORMED IN ACCORDANCE WITH THE GAS WELDING CONTROL MANUAL TD -4160M. REFER TO TD-416OP-20 FOR GENERAL WELDING REQUIREMENTS. <br />6. PURGE MAINS 10" IN DIAMETER & LESS PER GS&S A-38, ATTACHMENT A, PROCEDURE 2. PURGE MAINS GREATER THAN 10" IN DIAMETER PER GS&S A-38, ATTACHMENT A, PROCEDURE 3. <br />7. ABANDON ALL UNDERGROUND GAS FACILITIES PER UTILITY PROCEDURE TD-950OP-16 & GS&S A-93.2. <br />8. PLACE ELECTRONIC MARKING SYSTEM (EMS) DEVICES ON ALL CUT OFF ENDS AND SECTIONALIZING POINTS OF DEACTIVATED PIPE PER TD-950OP-16. <br />9. FOLLOW ALL MINIMUM INSTALLATION DEPTHS FOR TRANSMISSION, DISTRIBUTION AND SERVICE PIPE BY CLASS LOCATION AND SOIL TYPES OUTLINED IN GS&S A-04. <br />10. ALL GAS RISERS ARE TO BE INSTALLED IN ACCORDANCE WITH GS&S J-15 & J-15.1. <br />11. INSTALL METER PROTECTION PER GS&S J-95. <br />12. VENT REGULATORS PER GS&S H-93. <br />13. LOCATION OF EXISTING UTILITIES ARE APPROXIMATE. CALL UNDERGROUND SERVICES ALERT (USA) TO CONFIRM. GAS PIPELINES MUST BE INSTALLED WITH AT LEAST 3' OF SEPARATION (5' <br />PREFERRED) ON ANY PARALLELED INSTALLATION FROM ANY WET UTILITY AND 12" MINIMUM FROM ANY PERPENDICULAR CROSSING PER U.O. STANDARD S5453. <br />14. CONSTRUCTION SHALL NOTIFY MAPPING WITHIN 24 HOURS OF ALL OPERATIONAL CHANGES TO MAINS, INCLUDING EVERY TIE-IN, CUT OFF, UPRATE, ETC. PER U.O. STANDARD S4412. <br />15. ALL STEEL RISERS ARE TO BE REPLACED WITH NON CORRODIBLE RISERS OR REPLACED BY USING THE RISER INSERT RENEWAL INSTALLATION PER GS&S A-90. <br />16. ALL SERVICES AND MAINS TO BE TESTED PRIOR TO TIE-IN PER GS&S A-34. <br />17. INSTALL PLASTIC MAIN, SERVICES, & LOCATING WIRE PER GS&S A-34, A-90, A-90.2, A-90.3, A-91, A-93, A-93.1, A-93.3, UTILITY STANDARD TD -4170S, D-34 & CORROSION CONTROL <br />STANDARD TD -4181S. <br />18. INSTALL ANODES PER CORROSION CONTROL MANUAL 0-13.1. <br />19. INSTALL ELECTROLYSIS TEST STATIONS PER CORROSION CONTROL MANUAL 0-10 AND 0-10.1. IF PRACTICAL, INSTALL ETS STATION OUT OF THE ROADWAY. <br />20. ALL EXCAVATION TO BE PERFORMED PER TD -5811M, TD -5811P-301, TD -5811P-105, TD -4412P-05, AND TD -4621S. STANDBY REQUIRED IF EXCAVATING WITHIN 5' OFA CRITICAL FACILITY, <br />BORING ACTIVITY THAT CROSSES OR THAT PARALLELS WITHIN 10' OF A CRITICAL FACILITY. CONTACT THE CONSTRUCTION SUPERVISOR. <br />21. NOTIFY SCHOOLS AND HOSPITALS WITHIN 500' OF PROPOSED EXCAVATION FOR GAS FACILITIES A MINIMUM OF 3 DAYS PRIOR TO DIGGING PER AB 1937. <br />22. ANY PIPE REPLACEMENT VIA SPLITTING TO BE DONE PER TD -4634P-01 & TD -4634P-02. <br />23. CAMERA INSPECTION (PRE/POST) FOR TRENCHLESS METHODS TO BE PERFORMED PER TD -4632P-01. <br />24. WARNING TAPE IS TO BE INSTALLED IN OPEN TRENCH INSTALLATION OVER GAS PIPELINES IN BOTH TRANSMISSION AND DISTRIBUTION FACILITIES. THIS INCLUDES BELL HOLES, EXCAVATIONS FOR <br />REPAIR PURPOSES AND RISER REPLACEMENTS PER GS&S L-16. <br />25. DEVIATIONS FROM THIS APPROVED DESIGN SHALL BE PROCESSED IN ACCORDANCE WITH TD -4014P-05 "FIELD DESIGN CHANGE PROCESS FOR DISTRIBUTION LINES AND DUAL -ASSET FACILITIES." <br />26. ALL TRENCH SPOILS AND BACKFILL MUST BE USED OR DISPOSED WITH AS REQUIRED BY PG&E SPECIFICATIONS AND ANY LOCAL CITY, COUNTY OR STATE REQUIREMENTS. <br />27. PG&E TO INSTALL/RESTORE TEMPORARY AND/OR PERMANENT PAVING IN ACCORDANCE WITH PG&E SPECIFICATIONS AND ANY LOCAL CITY, COUNTY OR STATE REQUIREMENTS. <br />28. STAND-BY REQUIREMENTS MUST BE IN ACCORDANCE WITH TD -5811P-301, TD -5811P-105 & TD -581113-005 WITH WORKING NEAR ANY CRITICAL FACILITIES. <br />29. MONUMENT PRESERVATION AS REQUIRED BY THE PROFESSIONAL LAND SURVEYORS' ACT (BUSINESS AND PROFESSION CODE SUB -SECTION 8700-8805) SECTION 8771; PRIOR TO THE START OF <br />CONSTRUCTION, ALL SURVEY MONUMENTS, WITHIN THE PROJECT LIMITS THAT HAVE THE POSSIBILITY OF BEING DAMAGED OR DESTROYED DURING CONSTRUCTION, MUST BE LOCATED, AND <br />REFERENCED BY A LICENSED LAND SURVEYOR, AND A CORNER OF RECORD OR RECORD OF SURVEY SHALL BE FILED WITH THE COUNTY SURVEYOR. IF ANY OF THESE SURVEY MONUMENTS ARE <br />DESTROYED, DAMAGED OR COVERED OVER DURING CONSTRUCTION, A NEW MONUMENT AND MONUMENT BOX MUST THEN BE SET IN ITS PLACE, AT THE ORIGINAL LOCATION, BY A LICENSED <br />LAND SURVEYOR, AND ANOTHER CORNER OF RECORD OR RECORD OF SURVEY FILED WITH THE COUNTY SURVEYOR. <br />30. CONSTRUCTION MEANS AND METHODS MAY DEVIATE PER FIELD VERIFIED CONDITIONS IN ACCORDANCE WITH LOCAL JURISDICTION REQUIREMENTS. IF THERE ARE ANY QUESTIONS, CONTACT <br />RESPONSIBLE ENGINEER. <br />5231 COX RD <br />LINDEN, CA <br />PLAN VIEW <br />DR 0 <br />DICARLO o x <br />Uj <br />1'.- <br />d <br />TIED HP HP <br />EX.2"PL-3'-1979 <br />82 <br />1 /2 "PL 982 <br />_rq,,,X <br />00 <br />=i <br />J J �♦� <br />N 15' <br />i5 <br />i <br />5' <br />0+7 <br />i <br />i <br />i <br />5267 d <br />150' <br />i <br />i <br />a <br />T � <br />------------------ <br />32' <br />-----------j32' i <br />i <br />0 <br />J= <br />N <br />N <br />W <br />N o <br />Ln <br />8 <br />X006-1 <br />- HP <br />EXISTING GAS MAIN (SIZE NOTED) <br />- - - - - - <br />- GROUND WIRES (INSTALL) <br />- - - - - - <br />- ANODE WIRES (INSTALL) <br />JASON ZEPEDA <br />CATHODE WIRES (INSTALL) <br />0 <br />DEEP WELL ANODE (INSTALL) <br />0 <br />SHALLOW ANODE (INSTALL) <br />T <br />RECTIFIER (INSTALL) <br />510-697-4422 <br />GROUND ROD (INSTALL) <br />0 <br />DEEP WELL ANODE (EXISTING) <br />T <br />RECTIFIER (EXISTING) <br />© <br />GROUND ROD (EXISTING) <br />PLANNING ENGINEER <br />PG&E POLE (EXISTING) <br />LOCAL CONTACT INFO: <br />NAME <br />TITLE <br />CELL PHONE <br />JASON ZEPEDA <br />CORROSION MECHANIC <br />916-539-8545 <br />DAVID DURHAM <br />CORROSION SUPERVISOR <br />925-383-6468 <br />KEN KALEMKARIAN <br />CORROSION SPECIALIST <br />510-697-4422 <br />JESSE LEE <br />SENIOR DISTRIBUTION ENGINEER <br />650-773-9234 <br />JOE LEE <br />DISTRIBUTION ENGINEER <br />925-658-0845 <br />DAVE RYMERS <br />PLANNING ENGINEER <br />209-942-1626 <br />HAILEY IRIRBARNE <br />ESTIMATOR <br />707-836-6002 <br />COLIN MOXON <br />ADE <br />707-296-4343 <br />TBA <br />WORKING FOREMAN A <br />TBA <br />TBA <br />GC FIELD ENGINEER <br />TBA <br />NOTIFIED U.S.A. <br />DATE: <br />TICKET # <br />BY: <br />CATHODIC PROTECTION IN WORK AREA <br />ATTENTION FOREMAN: <br />NOTIFY THE CORROSION DEPT. AT <br />925-383-6468, 48 HOURS PRIOR TO <br />START OF WORK. <br />ATTENTION FOREMAN <br />PRIOR TO STARTING JOB, CONSULT AREA <br />CORROSION MECHANIC FOR LOCATING WIRE <br />INSTALLATION AND CATHODIC PROTECTION <br />REQUIREMENTS <br />Installation Tested or Inspected <br />and Noted on Drawing. <br />All Corrosion Levels Satisfactory per <br />PG&E Gas Utility Standard TD -4181S. <br />Qualified Employee Date <br />Corrosion mechanic's signature is required when a <br />CPA boundary is within the scope of the project <br />6 5 <br />10 <br />N M U') O Co <br />O � co M N <br />OO <br />C� 1 -to o O CO <br />CO CO C" r N <br />M O) r__ U') <br />00 N W N C" LO <br />O N <br />O O O N O �_ O <br />r-- r-- r-- C" N a N <br />Q W <br />N p = <br />' ^V7 <br />Q uM J <br />D W <br />W 00 <br />LU <br />O W O d7 <br />CD Uj LO <br />¢� J CD <br />Uj � -/- <br />J O ZO D N L J <br />2 UULU RL <br />l� <br />W Q � 0- Z a - <br />z � <br />< <br />w w <br />o� <br />U CD p <br />z E <br />JEl-wc¢ y <br />w p O as <br />D <br />QC-) 3� <br />O z Uotj <br />Q ¢ o z Y <br />Q�ccV) U_ it <br />CD w C; <br />w <br />U z <br />I� C <br />C-) z <br />< w <br />Z <br />Cl - <br />CD <br />CD W <br />UP <br />Cn <br />w <br />0 <br />W o <br />o <br />r4-) <br />� � <br />C/) I <br />U <br />z o 0 <br />o w <br />M X U <br />• <br />o o <br />w <br />0 <br />c z <br />c�¢n <br />JOB DATA <br />o <br />CITY: LINDEN <br />U S2 <br />COUNTY: SAN JOAQUIN <br />PLAT: 2950-G3-12 <br />C/ -)w <br />< <br />CPA: 3006-1 <br />( <br />TBA: X-02 <br />MAOP: 60 PSIG <br />NOP: 54 PSIG <br />APD: 40 PSIG <br />EZ: 16 -ST -07-B <br />Z <br />0 <br />4 3 2 1 INCH 0 <br />