<br />GENERAL NOTES
<br />G1. ALL CIRCUITRY SHOWN ON THESE DOCUMENTS IS DONE PER THE "ROUNDHOUSE"
<br />METHOD. FOR EVERY GROUP OF THREE (3) CONSECUTIVE CIRCUITS IN PHASE
<br />ORDER, THERE IS A DEDICATED NEUTRAL. FOR EXAMPLE, A HOMERUN
<br />COMPRISED OF CIRCUITS 1, 3 AND 5 CONTAINS FOUR (4) CONDUCTORS;
<br />THREE (3) HOTS AND ONE (1) NEUTRAL. A HOMERUN COMPRISED OF NON–
<br />CONSECUTIVE NUMBERS OUT OF PHASE ORDER. I.E. 1, 9 AND 11 OR 3, 5,
<br />7 CONTAINS FIVE (5) CONDUCTORS; THREE (3) HOTS AND TWO (2) NEUTRALS.
<br />GROUND CONDUCTORS TYPICALLY ARE NOT SHOWN AS PART OF THE WIRE
<br />COUNT.
<br />G2. INSTALL AND CONNECT AN INSULATED COPPER GROUNDING CONDUCTOR OF SIZE
<br />SHOWN OR PER CODE IN ALL BRANCH CIRCUIT RUNS.
<br />G3 FURNISH AND INSTALL ALL PANELBOARDS WITH CIRCUIT BREAKERS AS SHOWN
<br />ON PANELBOARD SUMMARY SCHEDULES.
<br />G4 REFER TO ELECTRICAL SPECIFICATIONS FOR THE FIXTURE SCHEDULE.
<br />G5 REFER TO ELECTRICAL ONE LINE DIAGRAM AND FEEDER SCHEDULE FOR
<br />THE SIZE OF CONDUITS AND CONDUCTORS BETWEEN MAJOR POWER
<br />COMPONENTS OF THE ELECTRICAL SYSTEM.
<br />G6 THE CONTRACTOR SHALL VISIT THE JOBSITE AND VERIFY ALL EXISTING
<br />CONDITIONS BEFORE BIDDING AND SHALL INCLUDE IN THE BID THE
<br />NECESSARY COSTS TO CONSTRUCT THIS PROJECT IN ACCORDANCE WITH THE
<br />ELECTRICAL DRAWiNGS, SPECIFICATIONS AND ALL APPLICABLE CODES.
<br />G7 ALL ELECTRICAL MATERIALS AND EQUIPMENT SHALL BE LISTED BY UNDER–
<br />WRITERS LABORATORIES AND BEAR THEIR LABEL.
<br />G8 NOTE THAT LOCATIONS SHOWN ON THE DRAWINGS FOR ELECTRICAL
<br />DEVICES ARE APPROXIMATE AND THAT THE FINAL LOCATIONS ARE TO
<br />BE COORDINATED IN THE FIELD WITH THE ARCHITECT.
<br />G9 CONTRACTOR SHALL REMOVE ALL LEFT OVER CONDUIT, WIRE, SCRAPS,
<br />ETC. AND LEAVE PREMISES CLEAN AND FREE OF TRASH OR DEBRIS
<br />RESULTING FROM HIS WORK.
<br />G10 CONTRACTOR SHALL REPORT TO THE ARCHITECT ANY OBSERVATIONS
<br />OF CONDITIONS WHICH ARE DISCOVERED ON THE SITE WHICH WOULD
<br />PREVENT 'THE CORRECT INSTALLATION OF THE ELECTRICAL SYSTEM.
<br />G11 CIRCUIT NUMBERING SYSTEM FOR MULTI–POLE CIRCUIT BREAKERS SHALL BE
<br />AS FOLLOWS: FOR TWO POLE CIRCUIT BREAKERS, THE CIRCUIT NUMBER
<br />USED FOR IDENTIFICATION SHALL BE THE TOP POLE OF THE TWO POLE USED
<br />(I.E. BREAKER INSTALLED AT POLE NUMBERS 8, 10 IS IDENTIFIED AS CIRCUIT
<br />No. 8). FOR THREE POLE CIRCUIT BREAKERS, THE CIRCUIT NUMBER USED
<br />FOR IDENTIFICATION WILL BE THE CENTER POLE OF THE THREE POLES USED
<br />(I.E. BREAKER INSTALLED AT POLE NUMBERS 8, 10, 12 IS IDENTIFIED AS
<br />CIRCUIT No. 10).
<br />SITE NOTES
<br />S1. DRAWINGS ARE DIAGRAMMATIC AND INDICATE GENERAL ARRANGEMENT OF
<br />SYSTEMS AND WORK. FOLLOW DRAWINGS IN LAYING OUT WORK AND CHECK
<br />DRAWINGS OF OTHER TRADES TO VERIFY SPACE CONDITIONS.
<br />S2. REFER TO CIVIL DRAWINGS FOR LOCATIONS OF LIGHTING FIXTURES ON HARD
<br />SURFACES. REFER TO LANDSCAPE DRAWINGS FOR LOCATIONS OF LIGHTING
<br />FIXTURES IN EARTH AND LANDSCAPE AREAS.
<br />S3. PULLBOXES ARE TO BE GENERALLY LOCATED AS FOLLOWS:
<br />1. BEHIND SIDEWALKS: LENGTHWISE PARALLEL TO SIDEWALK WITH EDGE OF
<br />PULLBOX 3" FROM EDGE OF SIDEWALK. SHERE PULLBOX IS ADJACENT
<br />TO POLEBASE, INSTALL ON SIDE OF POLE OPPOSITE SIDEWALK.
<br />2. IN MEDIAN STRIPS: CENTERED WITH LENGTH PARALLEL TO LENGTH
<br />OF MEDIAN.
<br />3. IN BERM AREAS: LENGTHWISE PARALLEL TO CURB WITH EDGE OF PULLBOX
<br />3" FROM BACK EDGE OF CURB.
<br />S4. POWER PEDESTALS ARE TO BE INSTALLED GENERALLY AT LOCATIONS SHOWN.
<br />COORDINATE WITH ARCHITECT PRIOR TO INSTALLATION.
<br />S5. SIZE PULLBOXES AS SHOWN ON DRAWINGS. OBTAIN
<br />ARCHITECTS APPROVAL OF ANY PULLBOX(ES) ADDED TO FACILITATE THE
<br />INSTALLATION OF CONDUITS SHOWN ON THE PLANS.
<br />S6. ALL WORK SHALL BE LOCATED IN PUBLIC UTILITY EASEMENT. EQUIPMENT
<br />AND DUCT BANKS IN GENERAL ARE SHOWN LOCATED IN EASEMENTS.
<br />CONTRACTOR SHALL REFER TO EASEMENT DRAWINGS DURING CONSTRUCTION
<br />TO MAINTAIN ALL EQUIPMENT AND DUCTS WITHIN EASEMENTS.
<br />S7. COORDINATE LOCATIONS OF ALL SITE PULLBOXES, TRANSFORMER PADS
<br />AND TRENCHING WITH LANDSCAPE ARCHITECT PRIOR TO INSTALLATION.
<br />S8. REFER TO THE CIVIL DRAWINGS FOR BERM INFORMATION AND LANDSCAPE
<br />DRAWINGS FOR LOCATION AND TYPE OF TREES.
<br />S9. REFER TO CIVIL AND LANDSCAPE DRAWINGS FOR EXACT LOCATIONS OF
<br />ILLUMINATED SIGNS.
<br />CONDUIT NOTES
<br />C1. CONDUIT ROUTING (WHERE SHOWN) IS ESSENTIALLY DIAGRAMMATIC.
<br />CONTRACTOR SHALL LAYOUT RUNS TO SUIT FIELD CONDITIONS AND THE
<br />COORDINATION REQUIREMENTS OF UTILITIES AND OTHER TRADES.
<br />C2. INSTALL A POLYETHYLENE PULLING ROPE IN ALL EMPTY CONDUITS.
<br />NUMBERED NOTES
<br />1� PROVIDE BASE ONLY FOR FIXTURE TYPE F1A AT THIS LOCATION. PROVIDE
<br />COVER OVER BOLTS FOR PROTECTION . INCLUDE ALL CONDUITS INTO AND
<br />OUT OF BASE. FURNISH ONE FIXTURE TYPE F1A TO OWNER FOR HIS
<br />INSTALLATION AT A FUTURE DATE.
<br />0 AT THIS LOCATION PROVIDE A TEMPORARY 15' HIGH WOODEN LIGHT POLE
<br />WITH ONE FIXTURE TYPE F6 MOUNTED AT THE TOP. REFER TO CIVIL
<br />DRAWIGS FOR DETAIL OF WOODEN POLE AND FEED. MAKE LIQUIDTIGHT CONDUIT
<br />CONNECTION TO FIXTURE.
<br />0 STUB 2" CONDUIT 12" BEYOND PERIMETER OF POLE BASE. PROVIDE
<br />CONDUIT MARKER PER DRAWING E7.1, DETAIL A.
<br />® PROVIDE CONDUIT STUB MARKER PER DRAWING E-7.1, DETAIL A.
<br />0 PROVIDE 2" CONDUIT BETWEEN POINTS SHOWN. TERMINATE 12" 13EYOND
<br />SIDEWALK WHERE APPLICABLE AND 24" BEYOND CURB WHERE NO SIDEWALK
<br />EXISTS. PROVIDE CONDUIT STUB MARKER PER DRAWING E7.1, DETAIL
<br />A AT EACH END.
<br />© PHASE 1A.3 SIDE SHALL BE DONE FIRST PER CIVIL PHASING DRAWING.
<br />STUB CONDUIT TO EDGE OF PHASE 1A.3 WORK, CAP AND INSTALL
<br />CONDUIT STUB MARKER. WHEN PRASE 1A.3 IS COMPLETE, PERFORM THE
<br />WORK IN PHASE 1A.4-5 BY EXTENDING THE CONDUIT AS SHOWN AND
<br />INSTALLING AND CONNECTION WIRING.
<br />0 STUB 2-2" MT SIGNAL AND 1-2" MT EMERGENCY CONDUITS INTO MEDIAN
<br />STRIP AND STUB UP 6" VERTICALLY. COORDINATE EXACT LOCATION OF
<br />STUBUPS WITH ARCHITECT PRIOR TO INSTALLING.
<br />0 REFER TO SECTION 165,35 FOR DETAILS CONCERNING SURFACE FLOODLIGHTS
<br />AND DIRECTIONAL LANDING LIGHTS. LOCATE LIGHTS AS SHOWN ON
<br />DRAWING C1.52.INSTALL PER MANUFACTURERS RECOMMENDATIONS AND
<br />CIVIL DRAWING DETAILS.
<br />SYSTEMS AND DEVICES DENOTED BY THIS NUMBERED NOTE SHALL
<br />BE INSTALLED DURING PHASE 1A.3. CARE SHALL BE TAKEN DURING THE
<br />CONSTRUCTION IN SUBSEQUENT PHASES TO PROTECT THE SYSTEMS
<br />AND DEVICES FROM DAMAGE AND TO INSURE THAT THEY REMAIN OPERATIONAL.
<br />0 STUB CONDUITS TO THE EDGE OF THE BORDER BETWEEN PHASE 1A AND 113
<br />AND CAP. PROVIDE CONDUIT STUB MARKER PER DRAWING E7.1,
<br />DETAIL A.
<br />01 TEMPORARY CONNECTION BETWEEN NORMAL AND EMERGENCY PULLBOXES FOR
<br />NORMAL FEED TO EMERGENCY FIXTURES. CIRCUITS WILL BE SPLIT AT
<br />END OF PHASE 1 B.
<br />0 INSTALL FIXTURE TYPE F5 AT LOCATION WHICH CORRESPONDS TO LOCATION
<br />OF TEMPORARY SIGN. INSTALL 8' FROM SIGN AT CENTERPOINT OF SIGN.
<br />COORDINATE WITH CIVIL DRAWINGS. AT SUCH TIME AS PERMANENT
<br />INTERNALLY LIGHTED SIGN IS INSTALLED, MAKE CONNECTION TO PERMANENT
<br />SIGN, DISCONNECT TEMPORARY SIGN LIGHT, REMOVE LIGHT AND TURN
<br />OVER TO OWNER.
<br />0 INSTALL FIXTURE TYPE F5 AT LOCATION WHICH CORRESPONDS TO LOCATION
<br />OF TEMPORARY SIGN. INSTALL 8' FROM SIGN AT CENTERPOINT OF SIGN.
<br />COORDINATE WITH CIVIL DRAWINGS.
<br />LOCATION OF TEMPORARY ELECTRIC DISTRIBUTION BOARD PROVIDED
<br />BY CIVIL DRAWINGS. SEE DETAIL 16, DRAWING C1.04. ADJACENT TO THAT
<br />EQUIPMENT, PROVIDE A WP, PADMOUNT 30KVA 240V, 10,2W TO 277/480V
<br />10, 3W TRANSFORMER.
<br />3 APPROXIMATE LOCATION OF OWNER FURNISHED PANELBOARD TOPD. MAKE
<br />CONNECTIONS TO TOPD AS REQUIRED BY SITE CIRCUITING.
<br />0 PROVIDE BASE AND CONDUIT STUBS FOR ONE FIXTURE TYPE F3
<br />AT THIS LOCATION.
<br />SYMBOLS
<br />----
<br />CONDUIT RUN CONCEALED IN SLAB, UNDER SLAB OR UNDERGROUND.
<br />—
<br />CROSSMARKS ON BRANCH CIRCUIT CONDUIT RUNS INDICATE THE QUANTITY
<br />OF CONDUCTORS AS FOLLOWS:
<br />1 . NO CROSSMARKS INDICATES TWO #8 & 1#8 GND CONDUCTORS, UON.
<br />2. THREE OR MORE CROSSMARKS INDICATES THE QUANTITY OF #8 AWG
<br />CONDUCTORS, UON. INCLUDE 1#8 GND IN ALL RUNS. THIS CONDUCTOR
<br />IS NOT SHOWN.
<br />NO SUBSCRIPT INDICATES NORMAL SYSTEM FEEDER. 'E' SUBSCRIPT INDICATES
<br />EMERGENCY SYSTEM FEEDER.
<br />S —
<br />CROSSMARKS ON BRANCH CIRCUIT CONDUIT RUNS INDICATE THE QUANTITY
<br />OF CONDUCTORS AS FOLLOWS:
<br />D•
<br />H.I.D. CUTOFF LIGHTING FIXTURE, POLE MOUNTED, SINGLE HEAD.
<br />DOE]
<br />H.I.D. CUTOFF LIGHTING FIXTURE, POLE MOUNTED, DOUBLE HEAD.
<br />.O
<br />BOLLARD OR POLE MOUNTED FIXTURE.
<br />J[]
<br />IN GRADE PULLBOX, SIZE AS SHOWN ON THE DRAWINGS. N INDICATES
<br />NORMAL SYSTEM, E INDICATES EMERGENCY SYSTEM, S INDICATES
<br />SECURITY SYSTEM.
<br />10
<br />NUMBERED NOTE:
<br />APPLIES TO ALL DRAWINGS.
<br />Stone
<br />Marraccini
<br />Patterson
<br />Architecture
<br />Planning
<br />Interior Architecture
<br />One Market Plaza
<br />Spear Street Tower
<br />Suite 400
<br />San Francisco
<br />CA 94105
<br />415 227-0100
<br />Architect,AIA
<br />Tech. Checked Tech.
<br />Coord. Arch.
<br />RUTHERFORD & CHEKENE
<br />303 Second St. Suite 800 N.
<br />San Francisco, CA 94107
<br />Structural Engineer
<br />GUTTMAN & MacRITCHIE
<br />631 Howard Street, Suite 500
<br />San Francisco, CA 94105
<br />Mechanical Engineer
<br />THE ENGINEERING ENTERPRISE
<br />1305 Marina Village Parkway
<br />Alameda, CA 94501
<br />Electrical Engineer
<br />Approvals
<br />Revisions
<br />No.
<br />SAN JOAQUIN
<br />GENERAL HOSPITAL
<br />REPLACEMENT PROJECT
<br />PHASE 1A
<br />ELECTRICAL NOTES,
<br />SYMBOLS AND
<br />DETAILS
<br />Scale: As Noted
<br />Project No.
<br />53000.09
<br />Date
<br />23 MAR 1992
<br />Date
<br />Drawing No.
<br />E 1.0