I-1' MIN. -I <br />TYPICAL SECTION THRU <br />THRUST BLOCK <br />NOTES: <br />1. ALL THRUST BLOCKS SHALL <br />BE POURED AGAINST <br />UNDISTURBED SOIL, <br />2. RESTRAINT SYSTEM FOR <br />VERTICAL PIPE BENDS SHALL <br />BE APPROVED BY THE <br />AGENCY. <br />3. THRUST RESTRAINT SYSTEMS <br />FOR PIPES LARGER THAN 12" <br />SHALL BE DESIGNED ON A <br />CASE BY CASE BASIS AND <br />SHALL BE APPROVED BY THE <br />AGENCY. <br />THRUST BLOCK <br />IF <br />THRUST BLOCK AREA <br />THE BRANCH LINE. <br />IS BASED ON THE SIZE OF <br />ALLOWABLE SOIL <br />1000 LBS. PER <br />BEARING <br />SQ. FT. <br />6" LINE OR SMALLER <br />a <br />"B" <br />22 1/2- <br />° d D <br />'. <br />"B" <br />e <br />°TV <br />° <br />nB"e <br />2'-0" <br />90' <br />p... ° d <br />2'-6" <br />° D <br />2'-6" <br />2'- 0 <br />DEAD END <br />(TYP-) <br />SERVICE _� 9 <br />SADDLE 1 90° CONCRETE OR <br />8 LINE <br />1 BRICK BLOCKING <br />22 1/2- <br />2 -0 <br />2 -0 <br />compaction of 95%* / <br />3-0 <br />2- <br />90' <br />4'-0- <br />3'- 0 <br />d1' <br />3'- 0 <br />3' -0 - <br />-0DEAD <br />DEAD END <br />3'_0- <br />3 -0 <br />10 LINE <br />VALVES FOR FIRE <br />NOTES: <br />2T-1 2' <br />3'- 0 <br />2 -0' <br />45' <br />3 -6 <br />3'-0- <br />-090' <br />90* <br />5 -0 <br />4'-0" <br />TEE OUTLET <br />4-0 <br />MIN. <br />DEAD END <br />� <br />1' MIN <br />12" <br />12 LINE <br />� A <br />PORT (FOR <br />22 1/2' <br />3'-0" <br />3'- 0 <br />45' <br />4'-0' <br />4 -0 <br />90' <br />7'- 0 <br />4 -O <br />MIN. <br />TYPICAL THRUST BLOCK <br />TYPICAL <br />THRUST BLOCK <br />TYPICAL THRUST BLOCK <br />BEND <br />SIDEWALK AREA. <br />TEE OUTLET <br />DEAD END <br />45° MAX. <br />Approved by <br />12" MIN. SUPPORT <br />GRADE TO NUT. <br />TYPICAL TRENCH BACKFILL <br />(ALL BOXES LOCATED IN DRIVEWAY AREAS TO HAVE TRAFFIC COVERS.) <br />B. TRACE WIRE MAY BE USED WHERE APPROVED BY AGENCY. <br />(TYP. FOR ALL <br />ANGLES) <br />REVISION <br />DATE <br />COUNTYWIDE IMPROVEMENT STANDARDS <br />INSTALL UNION <br />Drawn by JLD <br />10, BALL ANGLE METER STOP WITH LOCK LUG. <br />I-1' MIN. -I <br />TYPICAL SECTION THRU <br />THRUST BLOCK <br />NOTES: <br />1. ALL THRUST BLOCKS SHALL <br />BE POURED AGAINST <br />UNDISTURBED SOIL, <br />2. RESTRAINT SYSTEM FOR <br />VERTICAL PIPE BENDS SHALL <br />BE APPROVED BY THE <br />AGENCY. <br />3. THRUST RESTRAINT SYSTEMS <br />FOR PIPES LARGER THAN 12" <br />SHALL BE DESIGNED ON A <br />CASE BY CASE BASIS AND <br />SHALL BE APPROVED BY THE <br />AGENCY. <br />THRUST BLOCK <br />AREA REQUIRED <br />ADJUST BOX TO GRADE <br />FITTINGS <br />ALLOWABLE SOIL <br />1000 LBS. PER <br />BEARING <br />SQ. FT. <br />6" LINE OR SMALLER <br />"A" <br />"B" <br />22 1/2- <br />V-6" __T__ <br />TYP. <br />45' <br />2'-0" <br />2'-0" <br />90' <br />3'-0' <br />2'-6" <br />TEE OUTLET <br />2'-6" <br />2'- 0 <br />DEAD END <br />(TYP-) <br />SERVICE _� 9 <br />SADDLE 1 90° CONCRETE OR <br />8 LINE <br />1 BRICK BLOCKING <br />22 1/2- <br />2 -0 <br />2 -0 <br />compaction of 95%* / <br />3-0 <br />2- <br />90' <br />4'-0- <br />3'- 0 <br />TEE OUTLET <br />3'- 0 <br />3' -0 - <br />-0DEAD <br />DEAD END <br />3'_0- <br />3 -0 <br />10 LINE <br />VALVES FOR FIRE <br />NOTES: <br />2T-1 2' <br />3'- 0 <br />2 -0' <br />45' <br />3 -6 <br />3'-0- <br />-090' <br />90* <br />5 -0 <br />4'-0" <br />TEE OUTLET <br />4-0 <br />3-6 <br />DEAD END <br />-0 <br />4=T- <br />0 METERS SHALL BE AS SPECIFIED BY AGENCY. METERS SHALL BE FURNISHED AND <br />12" <br />12 LINE <br />Re of":kWj,� <br />PORT (FOR <br />22 1/2' <br />3'-0" <br />3'- 0 <br />45' <br />4'-0' <br />4 -0 <br />90' <br />7'- 0 <br />4 -O <br />TEE OUTLET <br />5'-0" <br />4'-0" <br />DEAD END <br />5'-0" <br />4'- 0 " <br />4. CONCRETE SHALL BE CLASS B. <br />„REVISION DATE COUNTYWIDE IMPROVEMENT STANDARDS APPROVED BY <br />COUNTY OF SAN JOAQUIN <br />SAN JOAQUIN COUNTY DATE <br />DIRECTOR OF PUBLIC WORKS JUNE 1997 <br />THRUST BLOCK CHART IMPROVEMENT <br />STANDARD NO. <br />CW -w4 <br />Install <br />Freeze Protection Cover <br />4" Cone. Slab (zippered fiberglass) <br />0 12 #4 bar (typ.) <br />W � <br />9„ <br />1 III ' T1 -III I I I In Thrust blocks I,I. I I I <br />2 Water -I per Detail 2 Water <br />2 Meter <br />Meter Box SECTION VIEW <br />NOTE: <br />Concrete shall be Class B. <br />as <br />Reduced Pressure <br />Backflow Prevention <br />Device Edge of slab <br />I <br />9" min. <br />Meter Box <br />2" Meter 3" clear <br />#4 bar (typ.) <br />BOW <br />r ri <br />4 A <br />Exist. <br />4 Sidewalk <br />C\2 1 <br />n ,I <br />---- --- <br />PLAN VIEW <br />CONCRETE SLAB at METER/ B.P. DEVICE <br />NO SCALE <br />S:\Projects\2009\09016\dwg\09016-EASTVIEW-DETAIL-6-30-09.dwg 7/2/2009 12:43:01 PM PDT <br />F,-935 <br />o PROFESS/0N <br />E. <br />NO. 42764 <br />EXP.3/31 /1 <br />STgTF QF CAL\F 0`��\ <br />�- -D % <br />ADJUST BOX TO GRADE <br />better than the existing pavement y <br />PER COUNTYWIDE STANDARDS <br />and base in quality. New pavement <br />--14-1/4" 6 <br />PIL <br />TYP. <br />New base shall be 1" thicker than <br />FINISHED GRADE <br />Existing <br />����j BY OWNER <br />D <br />30" MIN. 2" 12 <br />9.. 6 �5' MAX <br />(TYP-) <br />SERVICE _� 9 <br />SADDLE 1 90° CONCRETE OR <br />1I2r` I b o ° r ALSO SEE NOTE 70 <br />1 BRICK BLOCKING <br />/ \ <br />a min. relative <br />N.T.S. <br />compaction of 95%* / <br />STOP 2 <br />CONCRETE COLLAR <br />__________ / pavement. / <br />GW'ATER <br />Variable __-- --_= r Compact in 24" max. -- - <br />RISING STEM <br />10 -*3/8" <br />O.D./2 Compact ,in 6" la ers � <br />(NOT TO SCALE) <br />n3 <br />VALVES FOR FIRE <br />NOTES: <br />nrr D \\\ <br />0. D. 0. D. <br />0 1" DIA. MIN. LINE TO EACH LOT. <br />NOTES: <br />1 SERVICE PIPE TO BE CONTINUOUS (NO JOINTS) BETWEEN MAIN AND ANGLE METER STOP. <br />1. VALVE BOX AND LID SHALL BE CHRISTY NO. G5 OR AS APPROVED BY THE AGENCY. <br />NOTES: I <br />0 <br />2. ALL LIDS SHALL HAVE MACHINED SEATING SURFACES. <br />INSERTS MAY BE USED !"THERE APPROVED BY AGENCY, <br />l VALVE BOX RISERS SHALL BE AS MANUFACTURED FOR THE VALVE BOX SUPPLIED. <br />method No. California 216 or 231. <br />0 METERS SHALL BE AS SPECIFIED BY AGENCY. METERS SHALL BE FURNISHED AND <br />VALVE BOX RISER TO BE ONE CONTINUOUS PIECE AND CENTERED ON VALVE. <br />Re of":kWj,� <br />PORT (FOR <br />SHOULD BE RISER OR 8" 0, CLASS 100 PVC. <br />a 3 year bond. <br />PART OF THE CONNECTION FEE. <br />SEE NOTE 5. <br />REDUCED <br />DUCTILE IRON, <br />4. FOR BLOWOFF INSTALLATION, REFER TO DRAWING NO. CW -W6. <br />5. Special bedding requirements may be shown on the plans or specified in <br />5. THE LOCATION OF THE SERVICE SADDLE SHALL BE A MIN. OF 24" FROM ANOTHER <br />5. ALTERNATIVE VALVE BOX AND RISERS MAY BE USED WHERE APPROVED BY THE AGENCY. <br />OR STEEL. <br />SERVICE SADDLE, BELL, SPIGOT, OR OTHER FITTING. <br />6. CONCRETE COLLAR NOT REQUIRED WHEN VALVE BOX IS LOCATED 1N CONCRETE <br />- <br />DEVICE) <br />SIDEWALK AREA. <br />'sol" NONE <br />PRIOR APPROVAL OF THE AGENCY. <br />EIS VALVE STEM EXTENSIONS MAY BE USED TO COMPLY WITH 5' MAX. DISTANCE FROM <br />Approved by <br />12" MIN. SUPPORT <br />GRADE TO NUT. <br />TYPICAL TRENCH BACKFILL <br />(ALL BOXES LOCATED IN DRIVEWAY AREAS TO HAVE TRAFFIC COVERS.) <br />B. TRACE WIRE MAY BE USED WHERE APPROVED BY AGENCY. <br />30" MAX. (3" & LARGER) <br />REVISION <br />DATE <br />COUNTYWIDE IMPROVEMENT STANDARDS <br />INSTALL UNION <br />Drawn by JLD <br />10, BALL ANGLE METER STOP WITH LOCK LUG. <br />COUNTY OF SAN JOAQUIN <br />OR FLANGE, <br />(AFTER FLUSHING SERVICE, INSTALL LOCK SUPPLIED BY AGENCY) <br />Chucked by <br />11 RADIO/TOUCH READ PAD PER AGENCY REQUIREMENTS. (PROVIDE AT LEAST 4 FEET OF WIRE.) <br />SAN JOAQUIN COUNTY DATE <br />12 RADIO/REMOTE READ TRANSCEIVER PER AGENCY REQUIREMENTS, SUPPORTED BY <br />DEPARTMENT Or PUBLIC WORKS <br />DIRECTOR OF PUBLIC WORKS JUNE 1997 <br />--I <br />MXU CERTIFICATE MAY BE ACCEPTED BY AGENCY IN LOU OF TRANSCEIVER INSTALLATION. <br />VALVE BOX DETAILS <br />IMPROVEMENT <br />REVISION DATE <br />COUNTYWIDE IMPROVEMENT STANDARDS <br />APPROVED BY <br />cW-w5 <br />STANDARD NO. <br />N.T,S. CONCRETE SHALL BE CLASS B <br />COUNTY OF. SAN JOAQUIN <br />o PROFESS/0N <br />E. <br />NO. 42764 <br />EXP.3/31 /1 <br />STgTF QF CAL\F 0`��\ <br />�- -D % <br />P.L. <br />better than the existing pavement y <br />NO CONNECTIONSI SEE DETAIL A <br />FROM AGENCY MAIN TO RP DEVICE <br />and base in quality. New pavement <br />a ?,t 'V <br />PIL <br />C <br />New base shall be 1" thicker than <br />WATER METER ` <br />Existing <br />����j BY OWNER <br />Pavement <br />30" MIN. 2" 12 <br />(TYP-) <br />SERVICE _� 9 <br />SADDLE 1 90° CONCRETE OR <br />PLAN VIEW <br />1 BRICK BLOCKING <br />a min. relative <br />N.T.S. <br />compaction of 95%* / <br />STOP 2 <br />__________ / pavement. / <br />GW'ATER <br />Variable __-- --_= r Compact in 24" max. -- - <br />RISING STEM <br />TEST COCKS <br />O.D./2 Compact ,in 6" la ers � <br />(NOT TO SCALE) <br />to a minimum reative <br />..� compaction of 90%. <br />VALVES FOR FIRE <br />NOTES: <br />0. D. 0. D. <br />0 1" DIA. MIN. LINE TO EACH LOT. <br />SPRINKLER SYSTEMS <br />1 SERVICE PIPE TO BE CONTINUOUS (NO JOINTS) BETWEEN MAIN AND ANGLE METER STOP. <br />NOTES: I <br />0 <br />1. Relative compaction of materials shall be tested in accordance with <br />INSERTS MAY BE USED !"THERE APPROVED BY AGENCY, <br />DISCHARGE <br />method No. California 216 or 231. <br />0 METERS SHALL BE AS SPECIFIED BY AGENCY. METERS SHALL BE FURNISHED AND <br />2. All existing pavement shall be neatly cut to line prior to trench excavation. <br />Re of":kWj,� <br />PORT (FOR <br />PIPE SHALL BE <br />a 3 year bond. <br />PART OF THE CONNECTION FEE. <br />4. When shown by soil composition and compactobility, ninety percent (90%) <br />REDUCED <br />DUCTILE IRON, <br />5. Special bedding requirements may be shown on the plans or specified in <br />5. THE LOCATION OF THE SERVICE SADDLE SHALL BE A MIN. OF 24" FROM ANOTHER <br />PRESSURE <br />OR STEEL. <br />SERVICE SADDLE, BELL, SPIGOT, OR OTHER FITTING. <br />SAN JOAQUIN COUNTY DATE <br />DIRECTOR OF PUBLIC WORKS JUNE 1997 <br />- <br />DEVICE) <br />as measured from the edge of pavement. <br />'sol" NONE <br />PRIOR APPROVAL OF THE AGENCY. <br />Approved by <br />12" MIN. SUPPORT <br />TYPICAL TRENCH BACKFILL <br />(ALL BOXES LOCATED IN DRIVEWAY AREAS TO HAVE TRAFFIC COVERS.) <br />30" MAX. (3" & LARGER) <br />8: APPURTENANCES PER AGENCY REQUIREMENTS. <br />Director of Public Works <br />INSTALL UNION <br />Drawn by JLD <br />10, BALL ANGLE METER STOP WITH LOCK LUG. <br />OR FLANGE, <br />(AFTER FLUSHING SERVICE, INSTALL LOCK SUPPLIED BY AGENCY) <br />Chucked by <br />11 RADIO/TOUCH READ PAD PER AGENCY REQUIREMENTS. (PROVIDE AT LEAST 4 FEET OF WIRE.) <br />TYP. EA. SIDE <br />12 RADIO/REMOTE READ TRANSCEIVER PER AGENCY REQUIREMENTS, SUPPORTED BY <br />DEPARTMENT Or PUBLIC WORKS <br />'I (TYP) <br />--I <br />MXU CERTIFICATE MAY BE ACCEPTED BY AGENCY IN LOU OF TRANSCEIVER INSTALLATION. <br />4" MIN. DETAIL A <br />REVISION DATE <br />COUNTYWIDE IMPROVEMENT STANDARDS <br />APPROVED BY <br />N.T,S. CONCRETE SHALL BE CLASS B <br />COUNTY OF. SAN JOAQUIN <br />NOTES: <br />No. 2 By VA AUGUST 200e <br />1. <br />INSTALLED DEVICE MUST BE ON AGENCY APPROVED BACKFLOW PREVENTION DEVICE LIST. <br />2. <br />DEVICE SHALL BE INSTALLED <br />ABOVE GROUND. <br />3. <br />TEST COCKS AND SHUT-OFF VALVES MUST BE SUPPLIED AND INSTALLED AS SHOWN. <br />STANDARD NO. <br />4. <br />DISCHARGE PORT MUST BE KEPT CLEAR OF OBSTRUCTION AT ALL TIMES, <br />5. <br />ANY DEVIATION FROM THE INSTALLATION SHOWN ABOVE MUST RECEIVE PRIOR APPROVAL. <br />© <br />ALL PIPING & APPURTENANCES SHALL BE AWWA RATED 200 PSI FOR FIRE SPRINKLER <br />SYSTEMS. <br />7. <br />AGENCIES MAY REQUIRE <br />INSULATION TO PREVENT FREEZING OF EXPOSED PIPE, <br />8. <br />VALVES FOR FIRE SPRINKLER SYSTEMS SHALL BE CHAIN LOCKED IN AN OPEN POSITION <br />AT ALL TIMES. <br />REVISION DATE <br />COUNTYWIDE IMPROVEMENT STANDARDS <br />COUNTY OF SAN JOAQUIN <br />APPROVED BY <br />REDUCED PRESSURE/DOUBLE CHECK VALVE <br />SAN COUNTY DATE <br />DIRECTOORR OOF F PPUUBLIC WORKS _ JUNE 1997 <br />BACKFLOW PREVENTION <br />IMPROVEMENT <br />DEVICE INSTALLATION <br />CW -W24 <br />STANDARD NO. <br />o PROFESS/0N <br />E. <br />NO. 42764 <br />EXP.3/31 /1 <br />STgTF QF CAL\F 0`��\ <br />�- -D % <br />P.L. <br />better than the existing pavement y <br />I <br />11 <br />and base in quality. New pavement <br />a ?,t 'V <br />pavement, minimum of 0.25 feet. <br />C <br />New base shall be 1" thicker than <br />, ^ <br />10 <br />4 <br />Existing <br />����j BY OWNER <br />Pavement <br />30" MIN. 2" 12 <br />(TYP-) <br />SERVICE _� 9 <br />SADDLE 1 90° CONCRETE OR <br />Compact in 12" max. <br />1 BRICK BLOCKING <br />a min. relative <br />CORPORATION <br />compaction of 95%* / <br />STOP 2 <br />__________ / pavement. / <br />GW'ATER <br />Variable __-- --_= r Compact in 24" max. -- - <br />MAIN <br />O.D./2 Compact ,in 6" la ers � <br />(NOT TO SCALE) <br />to a minimum reative <br />..� compaction of 90%. <br />NOTES: <br />0. D. 0. D. <br />0 1" DIA. MIN. LINE TO EACH LOT. <br />+ 20" Min. + 20" Min. <br />1 SERVICE PIPE TO BE CONTINUOUS (NO JOINTS) BETWEEN MAIN AND ANGLE METER STOP. <br />NOTES: I <br />90' COMP, x COMP. ELL., 'JAMES JONES' J-2610 W/J-2806 OR EQUAL. <br />1. Relative compaction of materials shall be tested in accordance with <br />INSERTS MAY BE USED !"THERE APPROVED BY AGENCY, <br />LOCATOR WIRE <br />method No. California 216 or 231. <br />0 METERS SHALL BE AS SPECIFIED BY AGENCY. METERS SHALL BE FURNISHED AND <br />2. All existing pavement shall be neatly cut to line prior to trench excavation. <br />Re of":kWj,� <br />INSTALLED BY THE CONTRACTOR. AGENCIES MAY ELECT TO PROVIDE THE METER AS <br />INSTALLATION <br />a 3 year bond. <br />PART OF THE CONNECTION FEE. <br />4. When shown by soil composition and compactobility, ninety percent (90%) <br />APPROVED BY <br />❑4. GATE VALVE IS REQUIRED PRIOR TO ANY POINT OF CONNECTION, <br />5. Special bedding requirements may be shown on the plans or specified in <br />5. THE LOCATION OF THE SERVICE SADDLE SHALL BE A MIN. OF 24" FROM ANOTHER <br />special provisions. <br />Ch-kdby <br />SERVICE SADDLE, BELL, SPIGOT, OR OTHER FITTING. <br />SAN JOAQUIN COUNTY DATE <br />DIRECTOR OF PUBLIC WORKS JUNE 1997 <br />provisions but in no case shall the shoulder be less than three feet wide <br />METER BOX MAY BE PLACED ADJACENT TO PROPERTY OR EASEMENT LINE WITH <br />as measured from the edge of pavement. <br />'sol" NONE <br />PRIOR APPROVAL OF THE AGENCY. <br />Approved by <br />RADIO/TOUCH READ METER BOX PER AGENCY REQUIREMENTS, <br />TYPICAL TRENCH BACKFILL <br />(ALL BOXES LOCATED IN DRIVEWAY AREAS TO HAVE TRAFFIC COVERS.) <br />Feb. 1996 PD <br />8: APPURTENANCES PER AGENCY REQUIREMENTS. <br />Director of Public Works <br />Ej LOCATOR WIRE REQUIRED BY AGENCY, <br />Drawn by JLD <br />10, BALL ANGLE METER STOP WITH LOCK LUG. <br />(AFTER FLUSHING SERVICE, INSTALL LOCK SUPPLIED BY AGENCY) <br />Chucked by <br />11 RADIO/TOUCH READ PAD PER AGENCY REQUIREMENTS. (PROVIDE AT LEAST 4 FEET OF WIRE.) <br />Date JUNE 1997 <br />12 RADIO/REMOTE READ TRANSCEIVER PER AGENCY REQUIREMENTS, SUPPORTED BY <br />DEPARTMENT Or PUBLIC WORKS <br />1/2" SCH. 80 CONDUIT (24" MIN.) (PROVIDE 1" CLEARANCE BELOW LID) <br />--I <br />MXU CERTIFICATE MAY BE ACCEPTED BY AGENCY IN LOU OF TRANSCEIVER INSTALLATION. <br />REVISION DATE <br />COUNTYWIDE IMPROVEMENT STANDARDS <br />APPROVED BY <br />No, 1 By CC JUNE 2005 <br />COUNTY OF. SAN JOAQUIN <br />No. 2 By VA AUGUST 200e <br />WATER SERVICE <br />SAN JOAQUIN COUNTY DATE <br />DIRECTOR OF PUBLIC WORKS <br />IMPROVEMENT CW_W8 <br />INSTALLATION <br />STANDARD NO. <br />o PROFESS/0N <br />E. <br />NO. 42764 <br />EXP.3/31 /1 <br />STgTF QF CAL\F 0`��\ <br />�- -D % <br />Backfill with materials equal to or <br />better than the existing pavement y <br />PUMPER OUTLET FACING STREET <br />0 <br />2" MIN. <br />16" MIN. 4" MAX. 7 <br />20" MAX, , STANDARD <br />and base in quality. New pavement <br />shall be 1" thicker than existing <br />pavement, minimum of 0.25 feet. <br />e 4"CLEARANCE <br />HYDRANT "T" <br />MECHANICAL JOINT <br />❑5 \ I <br />New base shall be 1" thicker than <br />existing base, minimum of 0.5 feet. <br />Existing <br />Pavement <br />(TYPf) 6„ 6„ �- 6" Min. <br />(TYP-) <br />THRUST BLOCK <br />Compact in 12" max. <br />3'�0" lavers to 3'-0" <br />a min. relative <br />ECTI O N I GATE VALVE BLOCK <br />SECTION <br />compaction of 95%* / <br />under pavement and _-________ <br />90% outside Variable <br />__________ / pavement. / <br />1. HYDRANT MODEL TO BE APPROVED BY AGENCY. <br />Variable __-- --_= r Compact in 24" max. -- - <br />O0, _ r layers to a min. relative r <br />compaction of 85%. O' OD+12" <br />O' <br />O.D./2 Compact ,in 6" la ers � <br />3. HYDRANTS SHALL BE CLEAN AND FREE OF CONCRETE. <br />to a minimum reative <br />..� compaction of 90%. <br />10" Min. 0. D. 10" Min. 10" Min. O.D. 10" Min. <br />0. D. 0. D. <br />5 6" DIA. PVC PIPE (AWWA C-900 WITH CIP EQUIVALENT O.D.) <br />+ 20" Min. + 20" Min. <br />RIGID CONDUIT FLEXIBLE CONDUIT <br />i <br />NOTES: I <br />NEAR THE FIRE HYDRANT AS APPROVED BY THE AGENCY. <br />1. Relative compaction of materials shall be tested in accordance with <br />the State of California, Dept. of Transportation Testing Manuals, test <br />LOCATOR WIRE <br />method No. California 216 or 231. <br />CONNECTION TO HYDRANT. <br />2. All existing pavement shall be neatly cut to line prior to trench excavation. <br />Re of":kWj,� <br />3. Jetting or ponding will be permitted within the street Right of Way with <br />INSTALLATION <br />a 3 year bond. <br />DATE <br />4. When shown by soil composition and compactobility, ninety percent (90%) <br />APPROVED BY <br />compaction may be used, when approved by the Director of Public Works. <br />5. Special bedding requirements may be shown on the plans or specified in <br />special provisions. <br />Ch-kdby <br />6. Shoulders shall be as shown on the plans or specified in the special <br />SAN JOAQUIN COUNTY DATE <br />DIRECTOR OF PUBLIC WORKS JUNE 1997 <br />provisions but in no case shall the shoulder be less than three feet wide <br />DEPARTMENT OF PUBLIC WORKS <br />as measured from the edge of pavement. <br />'sol" NONE <br />No. Revised By <br />Approved by <br />TYPICAL TRENCH BACKFILL <br />Feb. 1996 PD <br />Director of Public Works <br />Drawn by JLD <br />Chucked by <br />COUNTY OF SAN JOAQUIN <br />Date JUNE 1997 <br />Scala NONE <br />DEPARTMENT Or PUBLIC WORKS <br />Drawing No. R-29 <br />--I <br />o PROFESS/0N <br />E. <br />NO. 42764 <br />EXP.3/31 /1 <br />STgTF QF CAL\F 0`��\ <br />�- -D % <br />i <br />HYDRANT <br />box <br />PUMPER OUTLET FACING STREET <br />0 <br />2" MIN. <br />16" MIN. 4" MAX. 7 <br />20" MAX, , STANDARD <br />e 8 VALVE BOX <br />Riser pipe g <br />e 4"CLEARANCE <br />HYDRANT "T" <br />MECHANICAL JOINT <br />❑5 \ I <br />i <br />f�Atia <br />Wire not #10 AWG, single strand, soft drawn <br />required copper wire; bare along pipe, 4/64" See I <br />between o� polyvinyl chloride insulation outside detail j <br />these valves of valve riser pipe and into the below <br />if within 10' valve box <br />of tee <br />THRUST BLOCK <br />VALVE DETAIL <br />CONCRETE BLOCK - THRUST <br />electrical tape <br />ECTI O N I GATE VALVE BLOCK <br />SECTION <br />Splice runs together 7 <br />NOTES: <br />Insulation into Soldered <br />1. HYDRANT MODEL TO BE APPROVED BY AGENCY. <br />I <br />2. SEE STANDARDS FOR LOCATION OF HYDRANT. <br />SPLICE DETAIL <br />3. HYDRANTS SHALL BE CLEAN AND FREE OF CONCRETE. <br />TYPICAL LAYOUT <br />4. HYDRANTS SHALL BE PAINTED YELLOW, IN ACCORDANCE WITH AGENCY STANDARDS, <br />1) Wire to be continuous between valve boxes, <br />5 6" DIA. PVC PIPE (AWWA C-900 WITH CIP EQUIVALENT O.D.) <br />except as noted. <br />FIRE HYDRANT LATERALS GREATER THAN 100 LF, SHALL HAVE A GATE VALVE INSTALLED <br />3 Locating wire to be laid at bottom of trench, <br />NEAR THE FIRE HYDRANT AS APPROVED BY THE AGENCY. <br />next to pipe. <br />7Q BREAK AWAY SPOOL WITH HOLLOW BREAK -OFF BOLTS WITH NUT ON BOTTOM AT <br />LOCATOR WIRE <br />A?p+d by <br />CONNECTION TO HYDRANT. <br />Re of":kWj,� <br />® EXPANSION JOINT MATERIAL WHERE HYDRANT IS PLACED IN CONCRETE. <br />INSTALLATION <br />REVISION <br />DATE <br />COUNTYWIDE IMPROVEMENT STANDARDS <br />APPROVED BY <br />COUNTY OF SAN JOAQUIN <br />Ch-kdby <br />FIRE HYDRANT <br />SAN JOAQUIN COUNTY DATE <br />DIRECTOR OF PUBLIC WORKS JUNE 1997 <br />DEPARTMENT OF PUBLIC WORKS <br />IMPROVEMENT CW -W18 <br />STANDARD NO. <br />'sol" NONE <br />ASSEMBLY <br />o PROFESS/0N <br />E. <br />NO. 42764 <br />EXP.3/31 /1 <br />STgTF QF CAL\F 0`��\ <br />�- -D % <br />Valve <br />box <br />Riser pipe g <br />i <br />f�Atia <br />Wire not #10 AWG, single strand, soft drawn <br />required copper wire; bare along pipe, 4/64" See I <br />between o� polyvinyl chloride insulation outside detail j <br />these valves of valve riser pipe and into the below <br />if within 10' valve box <br />of tee <br />VALVE DETAIL <br />Cover splice with <br />electrical tape <br />Splice runs together 7 <br />keep clear of fitting <br />Insulation into Soldered <br />valve box (remove connection, bare <br />at splice) wire along pipe <br />SPLICE DETAIL <br />TYPICAL LAYOUT <br />NOTES: i <br />1) Wire to be continuous between valve boxes, <br />except as noted. <br />2) Bare wire not to touch valves or fittings. <br />3 Locating wire to be laid at bottom of trench, <br />next to pipe. <br />No. Revteed By <br />LOCATOR WIRE <br />A?p+d by <br />Re of":kWj,� <br />INSTALLATION <br />D.- by J L D <br />Ch-kdby <br />COUNTY OF SAN JOAQUIN <br />SEPT. 1991 j <br />DEPARTMENT OF PUBLIC WORKS <br />D_"N No. W - 8 <br />'sol" NONE <br />o PROFESS/0N <br />E. <br />NO. 42764 <br />EXP.3/31 /1 <br />STgTF QF CAL\F 0`��\ <br />�- -D % <br />