TYPICAL DETAIL: PMI BOX PAD INSTALLATIONTYPICAL DETAIL: PMI BOX PAD INSTALLATIONLOCATION 3 & 8 DETAIL SCALE - 1" = 5'LEGENDEXISTING DESCRIPTIONINSTALLLOCPRIMARY CABLE: 3-1/0AL EPR 25kV IN 1-4" CONDUITPRIMARY CABLE: 3-1100AL EPR 25kV IN 1-6" CONDUITVACANT CONDUIT: 1-4"VACANT CONDUIT: 1-6"APPLICANT NOTESWORK AGENT RESPONSIBILITIESAPPLICANTAPPLICANTAPPLICANTN/AAPPLICANTPG&EPG&EPG&E TO INSTALL ELECTRIC DISTRIBUTION FACILITIES TO INSTALL DISTRIBUTION CONDUIT & SUBSTRUCTURES TO INSTALL ELECTRIC SERVICE FACILITIES (NON-RES) TO INSTALL SERVICE CONDUITS & SUBSTRUCTURES TO PERFORM ALL TRENCHING AND EXCAVATION TO PERFORM JOINT TRENCH COMPOSITE (35174735) TO PERFORM ALL TIE-IN WORK TO PERFORM ALL POLE WORK14. APPLICANT TO PROVIDE ADEQUATE P.U.E'S AND/OR ROW'S FOR PG&E FACILITIES. ANY ADDITIONAL REQUIREDRIGHTS OF WAY ARE TO BE SURVEYED AND DOCUMENTED BY PG&E AT THE APPLICANT'S EXPENSE.CONDUIT, TRENCHING, AND BACKFILL:1. ALL DIMENSIONS AND LOCATIONS ARE ESTIMATED, APPROXIMATE AND MAY BE SUPERSEDED BY A JOINTTRENCH DRAWING. REFER TO THE JOINT TRENCH COMPOSITE DRAWING FOR EXACT TRENCH LOCATION2. MAINTAIN MAXIMUM PRACTICABLE HORIZONTAL CLEARANCE BETWEEN PG&E FACILITIES AND "WET" UTILITIES(WATER, SEWER, STORM DRAIN, ETC.). THE MIN. ALLOWABLE SEPARATION BETWEEN PG&E FACILITIES ANDANY PARALLEL "WET" UTILITY IS 3/FT. WITH A PRESENCE OF 1/FT. OF UNDISTURBED EARTH OR THEINSTALLATION OF A SUITABLE BARRIER. THIS MEASUREMENT IS BETWEEN THE OUTER EDGE OF THE PG&EFACILITY AND THE OUTER EDGE OF THE PARALLEL "WET" FACILITY. IF 3/FT. CANNOT BE MAINTAINED, AFORMAL VARIANCE MUST BE OBTAINED FROM PG&E WORK WITH THE PG&E INSPECTOR (REFERENCE PG&EUO STANDARD S5453).3. BOX, PAD, AND CONDUIT SIZES AND LOCATIONS SHALL CONFORM TO THE PG&E ELECTRIC CONSTRUCTIONDRAWING.4. PROVIDE LONG CONDUIT SWEEPS WHERE INDICATED. RECOMMENDED SWEEP RADIUS (10' OF RADIUS PERINCH OF CONDUIT DIAMETER) EXAMPLE: 4" CONDUIT = 40' RADIUS5. DO NOT EXCEED 300 DEGREES OF BENDS IN ANY CONDUIT RUN (INCLUDING FEED LOCATION). NOTE:SECONDARY AND SERVICE RUNS OF 200 FEET OR LESS MAY HAVE UP TO 315 DEGREES OF BENDS (REFERENCEPG&E DOCUMENT 038193, REV. 7, DATED 6-28-13).6. MANUFACTURED BENDS OR APPLICATION OF HEAT SHALL NOT BE USED TO OBTAIN LONG CONDUIT SWEEPS.7. ALL CONDUITS SHALL BE PROVEN AND A POLYESTER PULLING TAPE INSTALLED.8. MANUFACTURED BENDS ARE NOT TO BE CUT, SHORTENED, OR ALTERED IN ANY WAY.9. IDENTIFY ENDS OF BURIED CONDUIT WITH AN ELECTRONIC MARKER AND A VERTICAL CONDUIT SCRAPINSTALLED FROM RIGID CAP TO GROUND LEVEL.10. CONDUITS ENTERING PRIMARY BOXES SHALL BE AT A RIGHT ANGLE TO THE WINDOW OR WALL.11. STUB CONDUITS AT RISER POLES IN QUADRANTS AS SHOWN. AT IDENTIFIED POLE LOCATIONS, THE TRENCHINGAGENT IS TO EXCAVATE TO TRENCH DEPTH AND INSTALL A 30" DIAMETER CARDBOARD TUBE. THE RISERCONDUIT BEND IS TO BE PLACED OUTSIDE AND ADJACENT TO THE TUBE AT THE POLE QUADRANT INDICATED.BACKFILL AROUND AND INSIDE TUBE WITH CLEAN NATIVE FILL.12. LS2 STREET LIGHT CONDUIT GOING TO PG&E BOXES OR PEDESTALS NOT DESIGNATED AS P.O.S. (INCLUDINGTRANSFORMERS) WILL NOT BE ACCEPTED OR CONNECTED.13. ONLY ONE LS2 STREET LIGHT (P.O.S.) CONNECTION PER BOX OR PEDESTAL.REFER TO ELECTRIC & GAS SERVICE REQUIREMENTS (GREEN BOOK) OR SEPARATE PG&E STANDARD DRAWINGS.CONTACT YOUR PG&E REPRESENTATIVE FOR COPIES, OR ACCESS. WWW.PGE.COM/GREENBOOKLAND RIGHTS AND EASEMENTS:SAFETY AND WORKMANSHIP:15. CALL 811 (UNDERGROUND SERVICE ALERT) 48 HOURS PRIOR TO EXCAVATION FOR UNDERGROUND UTILITYLOCATIONMARKING.16. 48 HOUR NOTICE REQUIRED FOR UNDERGROUND INSPECTION.17. MATERIALS AND WORKMANSHIP SHALL BE FIRST QUALITY IN EVERY RESPECT, PLUMB AND TRUE, ANDACCORDING TO THE SPECIFIC REQUIREMENTS OF THE DRAWINGS AND THE ABOVE APPLICABLE NOTES ANDSPECIFICATIONS.18. THE APPLICANT IS TO VERIFY ALL PROPOSED INSTALLATIONS, CONDITIONS & SPECIFICATIONS PRIOR TOCOMMENCING WITH ANY PORTION OF WORK. ANY DISCREPANCIES, DELETIONS OR INCONSISTENCIES ARE TOBE REPORTED TO THE PG&E REPRESENTATIVE IMMEDIATELY. THE APPLICANT SHALL COMPLY WITH ALLAPPLICABLE SPECIFICATIONS. ANY VARIATIONS FROM PLANS OR SPECIFICATIONS RELIEVES PG&E OF ALLRESPONSIBILITY FOR THE SUBSTRUCTURE OR DESIGN.THE MINIMUM ALLOWABLE SEPARATION BETWEEN THE EDGE OF THE JOINT TRENCHAND THE EDGE OF ANY "WET" FACILITY TRENCH IS 3' WITH THE PRESENCE OF AMINIMUM OF 1' OF UNDISTURBED EARTH OR THE INSTALLATION OF A SUITABLEBARRIER.THE MINIMUM ALLOWABLE SEPARATION BETWEEN THE EDGE OF THE JOINT TRENCHAND THE EDGE OF ANY "DRY" NON-UTILITY FACILITY TRENCH IS 2' WITH NO LESS THAN1' OF UNDISTURBED EARTH OR THE INSTALLATION OF A SUITABLE BARRIER.WET AND DRY UTILITY CLEARANCESN/AN/AN/AREQUIRED TRAFFIC CONTROL PLAN / FLAGGING ENCROACHMENT PERMIT VEGETATION REMOVALREQUIREDREQUIREDWORK REQUIREMENTSOVERHEAD SWITCHRISERJOINT POLEFUSED CUTOUTSOVERHEAD TRANSFORMERPMI-9TT | 1 INTERRUPTER IN "SWITCH MODE"SOLELY OWNED ANCHOR | SIZE AS SHOWNADDITONAL LAND RIGHTS REQUIRED SURROUNDINGTHE SUBSTRUCTURES, INCLUDING WORKING SPACE.LAND RIGHTS REQUIRED