Laserfiche WebLink
CONTROL SCHEMATIC <br />CONTROL FOR CONTROL FOR <br />PUMP #1 PUMP #3 <br />C <br />TRANSFORMER TRANSFORMER <br />480/120 VOLTS 480/120 VOLTS <br />HAND -OFF -AUTO SWITCH HAND -OFF -AUTO SWITCH <br />STARTER OVER HAND OFF AUTO STARTER <br />ND OFF -AUTO -O <br />HA <br />VER <br />COIL COAD COILS LOAD <br />ly <br />PRESSURE \ <br />PRESSURE SWITCH <br />SWITCH SPIN BUBBLER SPIN <br />BUBBLER DOWN ETM MIDDLE DOWN ETM <br />PUMP #1 TIME LEVEL TIME <br />LOW LEVEL DELAY DELAY <br />SPIN PIN <br />OWN DOWN <br />TIM TIME <br />DELA DELAY\ <br />—0 <br />-E 130ol—LE Oa S�wt�1o� �ti'='coon <br />PRESSURE PRESSURE -1* t <br />SWITCH SWITCH our o1= 'PLG <br />BUBBLER BUBBLER <br />PUMP #2 ALARM <br />ENGINE DRIVEN VERY <br />HIGH LEVEL HIGH LEVEL 0 <br />ELECTRICAL CONTRACTORS <br />WORK REQUIRED MATERIAL REQUIRED <br />1. PROVIDE THE COMBINATION MOTOR STARTER AS DESCRIBED. 1. QUAN 1, COMBINATION MOTOR STARTER, TO INSTALL IN THE <br />2. PROVIDE THE CONDUCTOR AND CONDUIT AS DESCRIBED. SPACE BELOW THE EXISTING MOTOR STARTER. THE STARTER <br />3. REMOVE THE BUBBLER CONTROL FROM THE PANEL SHALL BE A DUPLICATE OF THE EXISTING MOTOR CONTROLS, <br />INCLUDING DRAWOUT BUCKET, IF AVAILABLE; OR EQUIVALENT <br />DOOR AND INSTALL ON THE DOOR OF THE PANEL BELOW SQUARE D, GE, OR CH WITH DRAWOUT BUCKET IF AVAILABLE, <br />THE PG&E METER PANEL. NEMA SIZE #3, FVNR, WITH CIRCUIT PROTECTOR, HOA SWITCH, <br />4. INSTALL ANOTHER PRESSURE SENSOR FOR PUMP #2. RED RUNNING LIGHT, GREEN OFF LIGHT, RUNNING TIME METER, <br />6. INSTALL THIS MOTOR STARTER IN THE SPACE BELOW THE CONTROL TRANSFORMER, AND RESET BUTTON. <br />EXISTING MOTOR STARTER. 2. #4 AWG, CU, THHN CONDUCTOR. <br />5. INSTALL THE CONDUCTOR AND CONDUIT AS SHOWN BETWEEN 3• #6 AWG, CU, THHN CONDUCTOR. <br />THE MOTOR STARTER AND THE MOTOR. RUN TO BE UNDER THE 4. #8 AWG, CU, THHN CONDUCTOR. <br />5. 1" RIGID STEEL GALVANIZED AND NECESSARY <br />FLOOR. SUPPORT AS REQUIRED BY THE CODE. FITTINGS. <br />6. OTHER WORK AS NECESSARY TO PROVIDE A SYSTEM THAT 6. PRESSURE SENSING SWITCH FOR THIRD PUMP, SQUARE D <br />OPERATES PROPERLY. CLASS 9012, TYPE AMWI, RANGE 0.25 TO 2.5 # <br />7. CLEAN UP OF THE SITE TO RETURN IT AT LEAST TO THE DIFFERENTIAL 0.2 TO 2.0 # <br />CONDITION PRIOR TO THE START OF THE WORK. 7. MISCELLANEOUS EQUIPMENT NECESSARY TO COMPLETE <br />THE JOB, PROVIDE A WORKING SYSTEM, AND MEET ALL THE <br />APPLICABLE CODE REQUIREMENTS. <br />REFERENCES <br />1. Tn1F a. ARTICLE 6, 1540. (a). I <br />DrASION INDUSTRIAL SAFETY. <br />CONSTRUCTION SAFETY ORDERS <br />2. WILE 7110. <br />CONTRACTORS LICENSE LAW <br />—1-800-227-2600 — <br />SPECIFICATIONS <br />1. PART 3, TITLE 24, CALIFORNIA CODE OF REGULATIONS <br />(CALIFORNIA ELECTRICAL CODE) <br />2. UL OR APPROVED EQUAL TESTING ORGANIZATION. <br />3. CITY OF STOCKTON AND COUNTY OF SAN JOAQUIN <br />REGULATIONS. <br />4. OSHA REGULATIONS. <br />5. SEISMIC REQUIREMENTS FOR ZONE #3. <br />GEIB ENGINEERING <br />7315 WOODSIDE DRIVE <br />STOCKTON, CA 95207 <br />PHONE 209-473-2230 <br />FAX 209-478-0272 <br />ORIGINAL SCALE IN INCHES <br />FOR REDUCED PLAN <br />0 1 2 3 <br />CHECKED BY: A� 7/'1f7 <br />DATE <br />F., C/ Y/-//19- <br />SENIOR ENGINEER: .�,►�7 <br />DATE <br />APPROVAL RECOMMENDED- <br />DATE <br />ELECTRICAL SCHEMATIC <br />PG&E <br />INCOMING <br />SERVICE <br />MAIN CIRCUIT <br />BREAKER <br />200 AMP <br />3 POLE <br />480 VOLTS <br />TRANSFORMER <br />480/120 VOLT <br />1 PHASE <br />MODIFIED INCOMING <br />SERVICE AND <br />CONTROL PANEL <br />TO LIGHTS, <br />RECEPTACLES <br />BATTERY CHARGER <br />PURGE CONTROL <br />SAMPLER <br />MISCELLANEOUS <br />C NEMA 1, SIZE #3 <br />COMBINATION FVNR <br />PUMP#3 MOTOR STARTER <br />COMBINATION WITH HOA, RTM, OFF <br />STARTER AND RUN LIGHTS. <br />RESET BUTTON, <br />AND CONTROL <br />TRANSFORMER <br />3—#6 AWG CU THHN & <br />1—#8 AWG CU THHN GND. <br />IN 1 " RIGID STEEL <br />GALVANIZED CONDUIT. <br />PUMP #3 <br />30 HP <br />MOTOR <br />0 <br />1 <br />PUMP#1 C <br />COMBINATION <br />STARTER <br />aaw I By <br />PUMP #1 <br />30 HP <br />MOTOR <br />NEMA 1, SIZE #3 <br />COMBINATION FVNR <br />MOTOR STARTER <br />WITH HOA, RTM, OFF <br />AND RUN LIGHTS. <br />RESET BUTTON, <br />AND CONTROL <br />TRANSFORMER <br />Coll <br />RECORD D AWING <br />Corrections By <br />No Changes By <br />Date �llll� <br />Any Person Using This Drawing Should Vorlfy <br />All Information By Inspecting The Site Of Work - <br />K KJ ELDSEN <br />S SINNOCK <br />N NEUDECK <br />INC. Consulting Engineers <br />and Land Surveyors <br />Post Office Box 844 <br />1113 W. Fremont Street <br />Stockton, CA 95201-0844 <br />(209) 946-0268 <br />WEST LANE HEIGHTS <br />PUMPING PLANT EXPANSION <br />L <br />ELECTRICAL REQUIREMENTS <br />DEPARTMENT OF PUBLIC WORKS <br />CITY OF STOCKTON, CALIFORNIA <br />SCALE: NO SCALE APPROVED BY: DATE: SHEET NO. <br />DESIGNED BY: CEG 1p 6 <br />DRAWN BY: CEG OF 6 SHTS <br />CHECKED BY: KLK PROJECT NO. <br />CITY ENGINEER <br />RECORD DWG: STOCKTON, CALIF. <br />3 9'? /. 5G <br />0 <br />SWITCHBOARD <br />300 AMP, 480 VOLT, 3 PHASE, <br />4 WIRE <br />LIGHTING <br />PANEL <br />4��D <br />MAIN <br />CIRCUIT <br />CIRCUIT <br />BREAKER <br />BREAKER <br />200 AMP <br />LIGHTING PANEL <br />F <br />PG&E <br />CIRCUIT <br />PUMP #1 <br />PROTECTOR <br />30 HP <br />METERING <br />FVNR <br />O <br />STARTER <br />HOA <br />WITH <br />O <br />DISCONNECT <br />RESET RTM <br />PANEL <br />CIRCUIT <br />PROTECTOR <br />PUMP #3 <br />30 HP <br />FVNR <br />O <br />STARTER <br />HOA <br />WITH <br />O <br />K <br />DISCONNECT <br />RESET RTM <br />ON <br />1,.jC>7_PULL <br />SECTION <br />PULL SECTION <br />RECORD D AWING <br />Corrections By <br />No Changes By <br />Date �llll� <br />Any Person Using This Drawing Should Vorlfy <br />All Information By Inspecting The Site Of Work - <br />K KJ ELDSEN <br />S SINNOCK <br />N NEUDECK <br />INC. Consulting Engineers <br />and Land Surveyors <br />Post Office Box 844 <br />1113 W. Fremont Street <br />Stockton, CA 95201-0844 <br />(209) 946-0268 <br />WEST LANE HEIGHTS <br />PUMPING PLANT EXPANSION <br />L <br />ELECTRICAL REQUIREMENTS <br />DEPARTMENT OF PUBLIC WORKS <br />CITY OF STOCKTON, CALIFORNIA <br />SCALE: NO SCALE APPROVED BY: DATE: SHEET NO. <br />DESIGNED BY: CEG 1p 6 <br />DRAWN BY: CEG OF 6 SHTS <br />CHECKED BY: KLK PROJECT NO. <br />CITY ENGINEER <br />RECORD DWG: STOCKTON, CALIF. <br />3 9'? /. 5G <br />0 <br />