Laserfiche WebLink
NOTES* <br />1. ALL PIPING, VALVES Sc EQUIPMENT SHOWN ARE <br />INCLUDED IN THE CONTRACT PRICE FOR PUMPING <br />& ELECTRICAL EQUIPMENT. <br />2. ALL COLORS TO BE SELECTED BY OWNER WITH <br />APPROVAL BY THE DIRECTOR OF PUBLIC WORKS. <br />3. ALL BUILDING CONSTRUCTION LABOR AND <br />MATERIALS WILL BE IN COMPLIANCE WITH THE UBC. <br />4. NO VENTS BETWEEN CHLORINE ROOM <br />AND MAIN EQUIPMENT ROOM. <br />5. PRIOR TO CONSTRUCTION THE CONTRACTOR SHALL VERIFY <br />THE ADEQUACY OF THE GENERATOR PAD. <br />6. THE CONTRACTOR SHALL VERIFY THE ADEQUACY OF THE PROPOSED <br />VENTILATION WITH THE GENERATOR SUPPLIER AND, IF NECESSARY, <br />INCREASE THE VENTILATION AS RECOMMENDED BY THE SUPPLIER. <br />C <br />PROVIDE TWO <br />2 SF VENTS, <br />EVENLY SPACED <br />16' <br />3:. <br />A <br />5 <br />3.5' <br />EXIST WELL HEAD-/' <br />8' CHECK <br />DRESSER COU <br />16' <br />MUFFLED ALLOW FOR CLEARANCE <br />GENERATOR EXHAUST FOR CONTROL PAM DOOR. <br />C V <br />3 <br />GENERATOR PAD <br />d � 17 <br />i <br />�� <br />._V <br />9i <br />ABOVE <br />I <br />I <br />I If <br />I <br />D_ <br />D <br />D <br />D <br />4"9 CONDUIT W/PULL <br />ROPE TO JUNCnON BOX <br />f9 � <br />I <br />I <br />—WALL TO BE SOLID TO � I <br />ROOFIJNE (NO VENTING I <br />BETWEEN CHLORINE ROOMI <br />& MAIN EQUIP, ROOM). I <br />I I <br />© I <br />I <br />© I <br />I <br />I <br />I <br />�® II <br />R I <br />I <br />TANK <br />--------------J <br />A <br />NOT TO SCALE <br />STUDS ® 16' O/C <br />214 TREATED SU.L PLATE <br />2-#4 BARS, CONT. ATN 1/2" 0 s 10' <br />AB ® 48 0/C <br />4" THICK CLASS "B" CONC <br />SLAB W/6x6W1.5 W.W.F. <br />SECTION C -C <br />NOT TO SCALE <br />NORTHWESTERLY ELEVATION <br />SCAIE:1"=3' <br />1/2'a6' ASPHALT IMPREGNATED <br />EXPANSIONSION JOINT --\() AIR COMPRESSOR, 'AIR RITE', MODEL D610 H.P., MOUNTED ON TANK. (REFER TO SHEET 15 ITEM 14 ) <br />1-#'4 CRD 40 BAR, CONT. -\ \ 02 DELETED <br />6s6W1.5 W.W.F. <br />6" 0 <br />7 <br />12" - <br />0 <br />SECTION B -B ,D <br />NOT TO SCALE <br />11 <br />l2 <br />13 <br />14 <br />15 <br />IB <br />17 <br />18 <br />19 <br />20 <br />2x4 STUDS ® 16" 0/C <br />- NO VENTS BETWEEN <br />CHLORINE ROOM & MAIN <br />EQUIPMENT ROOM. <br />2x4 P.T.D.F. MUDSILL WITH <br />1/2"x10" FOUNDATION <br />BOLTS 4' 0/C. <br />1/2" PLYWOOD PANEL FOR MOUNTING PRESSURE GAUGE. <br />IL°Hf TGE. W/PmvRE duct, AWOFF N0,1406 OR F.QDAL,,.: i <br />VANDAL RESISTANT FIXTURE W/POLYCARBONATE LENSE AND 100 MATT INCANDESCENT LAMP. <br />TWO - 2'-0"x6'-8" VANDAL PROOF STEEL DOORS AND 18 GAGE STEEL JAMB WITH FIXED PIN HINGE. PROVIDE, <br />ONE HEAVY DUTY CASE-HARDENED SAFETY RASP BOLTED THROUGH DOOR. <br />DELETED i <br />J' PVC COWIT FROM TANK TO PRESSURE, 'q - <br />MAIN CONTROL PANEL AND ELECTRICAL SERVICE. PROVIDE 4"0 PVC CONDUIT W/PULL ROPE ' <br />55 GAL HYPOCHLORITE TANK: CONTRACTOR TO PROVIDE SEISMIC CALCULATIONS FOR ANCHORAGE. <br />CHLORINE SOLUTION LINE TO PUMP <br />CHLORINE METERING PUMP (BLUE WHITE INDUSTRIES). REFER TO PROJECT SPECIFICATIONS. <br />e' P.E. PIPE IN CONDUIT <br />PVC INJECTION VALVE <br />CHLORINE INJECTION <br />BRONZE CURB STOP M/NOZZLE <br />GENERATOR SET: ONAN NO. 80 DGDA. <br />TRANSFER SNITCH PANEL <br />20 POUND FIRE EXTINGUISHER WITH A -B -C RATING. <br />4' THICK CLASS 'B" CONCRETE SLAB W/6X6W1.5 M.W.F. OVER 6" NATIVE SOIL COMPACTED TO 90% RELATIVE <br />COMPACTION. <br />gl CHLORINE ROOM: FINISH SOUTHEASTERLY WALLS AND CEILING WITH r TAPED SHEET ROCK. ANY HOLES MADE <br />BY CONDUIT SHALL BE SEALED AIR TIGHT. <br />© METER PANEL <br />® EMERGENCY EYE MASH & SHOWER (DRAIN TO PAVEMENT) <br />® PORCELAIN LAMP FIXTURE W/75 WATT INCANDESCENT LAMP AND PROTECTION SAFETY COVER <br />q5 24'x36" LOUVERED MALL VENT <br />26 PROVIDE DUPLEX RECEPTACLE AT 40' ABOVE FLDOR FOR POWER. <br />©ONE - 3'-O"x6'-8" VANDAL PROOF STEEL DOORS AND 18 GAGE STEEL JAMB WITH FIXED PIN HINGE. PROVIDE <br />ONE HEAVY DUTY CASE-HARDENED SAFETY HASP BOLTED THROUGH DOOR. <br />©8 LIGHT SWITCH <br />©9 3/4" HOSE BIB <br />RL640161c <br />No. 42764 <br />exp. 31311.6 <br />9i <br />10' <br />MABWOVZ <br />l <br />i <br />CONCRETE APRON TO <br />M CHECK VALVE <br />- <br />13 <br />PLAN VIEW <br />NO <br />4"9 CONDUIT W/PULL <br />ROPE TO JUNCnON BOX <br />f9 � <br />I <br />I <br />—WALL TO BE SOLID TO � I <br />ROOFIJNE (NO VENTING I <br />BETWEEN CHLORINE ROOMI <br />& MAIN EQUIP, ROOM). I <br />I I <br />© I <br />I <br />© I <br />I <br />I <br />I <br />�® II <br />R I <br />I <br />TANK <br />--------------J <br />A <br />NOT TO SCALE <br />STUDS ® 16' O/C <br />214 TREATED SU.L PLATE <br />2-#4 BARS, CONT. ATN 1/2" 0 s 10' <br />AB ® 48 0/C <br />4" THICK CLASS "B" CONC <br />SLAB W/6x6W1.5 W.W.F. <br />SECTION C -C <br />NOT TO SCALE <br />NORTHWESTERLY ELEVATION <br />SCAIE:1"=3' <br />1/2'a6' ASPHALT IMPREGNATED <br />EXPANSIONSION JOINT --\() AIR COMPRESSOR, 'AIR RITE', MODEL D610 H.P., MOUNTED ON TANK. (REFER TO SHEET 15 ITEM 14 ) <br />1-#'4 CRD 40 BAR, CONT. -\ \ 02 DELETED <br />6s6W1.5 W.W.F. <br />6" 0 <br />7 <br />12" - <br />0 <br />SECTION B -B ,D <br />NOT TO SCALE <br />11 <br />l2 <br />13 <br />14 <br />15 <br />IB <br />17 <br />18 <br />19 <br />20 <br />2x4 STUDS ® 16" 0/C <br />- NO VENTS BETWEEN <br />CHLORINE ROOM & MAIN <br />EQUIPMENT ROOM. <br />2x4 P.T.D.F. MUDSILL WITH <br />1/2"x10" FOUNDATION <br />BOLTS 4' 0/C. <br />1/2" PLYWOOD PANEL FOR MOUNTING PRESSURE GAUGE. <br />IL°Hf TGE. W/PmvRE duct, AWOFF N0,1406 OR F.QDAL,,.: i <br />VANDAL RESISTANT FIXTURE W/POLYCARBONATE LENSE AND 100 MATT INCANDESCENT LAMP. <br />TWO - 2'-0"x6'-8" VANDAL PROOF STEEL DOORS AND 18 GAGE STEEL JAMB WITH FIXED PIN HINGE. PROVIDE, <br />ONE HEAVY DUTY CASE-HARDENED SAFETY RASP BOLTED THROUGH DOOR. <br />DELETED i <br />J' PVC COWIT FROM TANK TO PRESSURE, 'q - <br />MAIN CONTROL PANEL AND ELECTRICAL SERVICE. PROVIDE 4"0 PVC CONDUIT W/PULL ROPE ' <br />55 GAL HYPOCHLORITE TANK: CONTRACTOR TO PROVIDE SEISMIC CALCULATIONS FOR ANCHORAGE. <br />CHLORINE SOLUTION LINE TO PUMP <br />CHLORINE METERING PUMP (BLUE WHITE INDUSTRIES). REFER TO PROJECT SPECIFICATIONS. <br />e' P.E. PIPE IN CONDUIT <br />PVC INJECTION VALVE <br />CHLORINE INJECTION <br />BRONZE CURB STOP M/NOZZLE <br />GENERATOR SET: ONAN NO. 80 DGDA. <br />TRANSFER SNITCH PANEL <br />20 POUND FIRE EXTINGUISHER WITH A -B -C RATING. <br />4' THICK CLASS 'B" CONCRETE SLAB W/6X6W1.5 M.W.F. OVER 6" NATIVE SOIL COMPACTED TO 90% RELATIVE <br />COMPACTION. <br />gl CHLORINE ROOM: FINISH SOUTHEASTERLY WALLS AND CEILING WITH r TAPED SHEET ROCK. ANY HOLES MADE <br />BY CONDUIT SHALL BE SEALED AIR TIGHT. <br />© METER PANEL <br />® EMERGENCY EYE MASH & SHOWER (DRAIN TO PAVEMENT) <br />® PORCELAIN LAMP FIXTURE W/75 WATT INCANDESCENT LAMP AND PROTECTION SAFETY COVER <br />q5 24'x36" LOUVERED MALL VENT <br />26 PROVIDE DUPLEX RECEPTACLE AT 40' ABOVE FLDOR FOR POWER. <br />©ONE - 3'-O"x6'-8" VANDAL PROOF STEEL DOORS AND 18 GAGE STEEL JAMB WITH FIXED PIN HINGE. PROVIDE <br />ONE HEAVY DUTY CASE-HARDENED SAFETY HASP BOLTED THROUGH DOOR. <br />©8 LIGHT SWITCH <br />©9 3/4" HOSE BIB <br />RL640161c <br />No. 42764 <br />exp. 31311.6 <br />