Trench Repair: 6" native soil at 95% relative compaction <br />unless noted as either Aggregate Base or Asphalt Concrete <br />trench repair. See Sheet 3 for trench resurfacing schedule. <br />maximum payment width = pipe O.D. + 40". <br />,,,- Existing Pavement --\ <br />llal <br />IN <br />0 <br />I <br />;�) Compact in 12"max. layers - <br />T to a min. relative compaction <br />Lo of 95% + under pavement <br />and shoulders, and 90% <br />outside shoulder. <br />a <br />0 00 10 to go <br />0 <br />o0 of 00 1 Compact in 24" max. layers <br />to a minimum relative <br />compaction of 85%. <br />Compact in 6" layers <br />to a minimum relative <br />04 T compaction of 90%. <br />0 <br />10" --10. D. 0„ 10" 0. D. 10„ <br />0.D.+20" Min. O.D.+20" Min. <br />RIGID CONDUIT FLEXIBLE CONDUIT <br />NOTES: <br />1. Relative compaction of materials shall be tested by the State of California, Dept, of Transportation <br />Testing Manual, test method No. California 216 or 231. <br />2. All existing pavement shall be neatly cut to line prior to trench excation. <br />i <br />CAST IRON BEND <br />TYPICAL TRENCH BACKFILL <br />NOT TO SCALE <br />45' Max. <br />A_Sr1 <br />��ll ♦ <br />V"1A <br />W ♦ ♦ m ♦ ♦ <br />TEE OUTLET <br />Min. <br />DEAD END TYPICAL SECTION <br />THRU <br />THRUST BLOCK <br />THRUST <br />BLOCK DIMENSIONS <br />ITEM <br />DESCRIPTION <br />hD <br />A <br />V17 <br />A <br />B <br />6 LINE <br />1. <br />10" LINE <br />1'-9" <br />---- <br />22 1/2 <br />1'-fi' <br />CAST IRON BEND <br />TYPICAL TRENCH BACKFILL <br />NOT TO SCALE <br />45' Max. <br />A_Sr1 <br />��ll ♦ <br />V"1A <br />W ♦ ♦ m ♦ ♦ <br />TEE OUTLET <br />Min. <br />DEAD END TYPICAL SECTION <br />THRU <br />THRUST BLOCK <br />NOTES: <br />1. All thrust blocks shall be poured <br />against undisturbed soil and shall <br />be Class "B" Concrete. <br />2. Thrust block dimensions were <br />calculated to allow a soil <br />bearing value of 1,000 pounds <br />per square foot. <br />THRUST BLOCK DETAILS <br />NOT TO SCALE <br />THRUST <br />BLOCK DIMENSIONS <br />ITEM <br />DESCRIPTION <br />FITTINGS <br />A <br />B FITTINGS <br />A <br />B <br />6 LINE <br />1. <br />10" LINE <br />1'-9" <br />---- <br />22 1/2 <br />1'-fi' <br />V-6" <br />3'-0" 1 <br />2'- <br />45 <br />2'-0" <br />2'-O" <br />4'-0" <br />3'-0" <br />90 <br />3'-0" <br />2'-6" <br />5'-6" <br />4'-0 <br />TEE OUTLET <br />3'-0" <br />'-0" <br />4'-0" <br />4'-0" <br />DEAD END <br />3'-0" <br />2'-0" <br />4'-0" <br />4'-0" <br />8 LINE <br />400 <br />12 LINE <br />9. <br />8" GATE VALVE <br />22 1/2 <br />2'-0" <br />2'-0 <br />3'-Y' 1 <br />T- <br />45 <br />3'-0" <br />2'-6" <br />4'- <br />4'- <br />90 <br />4'-0" <br />3'-6" <br />8'-0" <br />4'-0" <br />TEE OUTLET <br />3'-6" <br />3'-0" <br />5'-6" <br />4'-O" <br />DEAD END <br />3'-6" <br />3'-0" <br />5'-6" <br />4'-0" <br />NOTES: <br />1. All thrust blocks shall be poured <br />against undisturbed soil and shall <br />be Class "B" Concrete. <br />2. Thrust block dimensions were <br />calculated to allow a soil <br />bearing value of 1,000 pounds <br />per square foot. <br />THRUST BLOCK DETAILS <br />NOT TO SCALE <br />3/4" Dia. Anchor rods. Field coat with <br />coal tar to prevent corrosion <br />Embed rods at least 2/3 of dimention "A' <br />A' FOR ALL STREET <br />LOCATIONS - <br />B' <br />VERTICAL -DOWNWARD BEND 2" asphalt concrete - <br />BASE BID QUANTIES <br />DIMENSIONS <br />ITEM <br />DESCRIPTION <br />ESTIMATATED <br />UNIT OF <br />NO. <br />Water main <br />QUANTITY <br />MEASURE <br />1. <br />FORCE ACCOUNT <br />1'-9" <br />---- <br />2. <br />CLEARING & GRUBBING <br />L.S. <br />---- <br />3. <br />AGGREGATE BASE (Trench Repair) <br />20 <br />S.Y. <br />4. <br />A.C. MISC. AREAS (Trench- 0.30) <br />50 <br />S.Y. <br />5. <br />A.C. MISC. AREAS (Trench- 0.50') <br />125 <br />S.Y. <br />6. <br />6"DIA. ALT. PIPE <br />35 <br />L. F. <br />7. <br />87DIA. ALT. PIPE <br />15 <br />L. F. <br />8. <br />10"DIA. ALT. PIPE <br />400 <br />L. F. <br />9. <br />8" GATE VALVE <br />2 <br />EA. <br />10. <br />10" GATE VALVE <br />1 <br />EA. <br />11. <br />FIRE HYDRANT W/FITTINGS <br />13 <br />EA. <br />1 Cr LINE <br />AS REQUIRED <br />areas as approved by <br />the fire chief. <br />12. <br />TESTING & DISINFECTION <br />L.S. <br />---- <br />3/4" Dia. Anchor rods. Field coat with <br />coal tar to prevent corrosion <br />Embed rods at least 2/3 of dimention "A' <br />A' FOR ALL STREET <br />LOCATIONS - <br />B' <br />VERTICAL -DOWNWARD BEND 2" asphalt concrete - <br />NOTES FOR VERTICAL BENDS: <br />1. Width of block is trench width. <br />2. For upward vertical bends, <br />use equivalent horizontal thrust block. <br />RN <br />Extensions <br />Existing (L Fairoaks <br />Note <br />Approved Alternative Pipe materials for meeting <br />separation requirements shall be: <br />1. Ductile Iron pipe per AWWA C151. <br />2. Welded steel pipe per AWWA C200, <br />1 /4" thick and lined and wrapped per <br />AWWA C203. <br />3. Class 200 PVC pipe per AWWA C900. <br />4. Reinforced concrete pressure pipe, steel <br />cylinder type per AWWA C300, C301 or C303. <br />Cast iron .locations) <br />seatingRattle-proof, machined <br />. <br />1/8' Finished grade <br />i <br />g' 1717 -FOR OFF STREET <br />LOCATIONS <br />E Concrete base to be <br />N around valve box. <br />Concrete base not <br />necessary when <br />valve box is located <br />in back of sidewalk. <br />No. 10 bare soft drawn <br />copper wire along all non metallic <br />NOTES: pipe <br />1. Valve box and lid shall be Christy No. G-5, <br />Brooks No. I R T or 4 -TT, or equal. <br />2. All lids and grade rings shall have <br />machined seating surfaces. <br />3. Extensions shall be as manufactured for the <br />valve box supplied or pipe of correct size can <br />be used. <br />VALVE BOX <br />NOT TO SCALE <br />q <br />Canal <br />c'➢ <br />I <br />Exist. 36"Dia. Conc. <br />Pipe to remain in \\\\111111 <br />place. <br />V <br />a <br />1'. Min. <br />Provide special construction for separation of water - <br />main from irrigation culvert. Install 18'-0" continuous <br />length of 10"Dia. Alt. Pipe. Center pipe under 36"Dia. <br />culvert. <br />y- <br />°,.��rr< <br />CULVERT CROSSING DETAIL <br />NOT TO SCALE <br />� I <br />W <br />Edge of pavement <br />12" i-�- <br />II <br />I--�----------- <br />I <br />Blue Reflective Pavement Marker <br />Varies <br />PLAN VIEW <br />Variable <br />10"Dia. Alt. Pipe <br />n r „ <br />3" AC <br />pavement <br />T <br />I <br />8' 2' <br />10' <br />R/W <br />2 _i <br />Valve box, frame and lid (At Valpico Rd.) <br />refer to Standard Drawing <br />No. W-4. (See sheet 4) Break -off <br />2" above ground line check valve <br />VERTICAL <br />DIMENSIONS <br />FITTINGS IA <br />B <br />6 LINE <br />Water main <br />22 1/2 <br />1'-9" <br />3'-0" <br />45 <br />1'-9" <br />!::6" <br />90 <br />2'-3" <br />2'-6" <br />Conc. thrust block <br />8 LINE <br />refer to Standard <br />Drawing No. W-5 1 <br />Conc. thrust <br />(See sheet4) <br />22 1 <br />2 <br />2'-0" 1 <br />4'-0 <br />45 <br />2'-6" <br />4'-6" <br />90 <br />3'-0" <br />6'-0" <br />the street. <br />2. Fire hydrants shall be <br />clean and free of concrete. <br />3. Fire hydrants to be American Darling model B -62B, Long Beach model 615, <br />James Jones J-4060, <br />Dresser M & H style 929 "reliant", Mueller "Centurion" <br />or "Modern Centurion", <br />1 Cr LINE <br />Dry barrel in the Stockton area; (2)2 1/2 & (1)4 1/2" wet barrel in other <br />areas as approved by <br />the fire chief. <br />22 1/2 <br />OSHA safety yellow or as approved by the <br />2'-9" <br />5'-0 <br />45 <br />Long Beach Iron Works, model LB 400, or <br />3'-0" <br />5'-6" <br />90 <br />FIRE HYDRANDT <br />3'-6" <br />NOT TO SCALE: <br />NOTES FOR VERTICAL BENDS: <br />1. Width of block is trench width. <br />2. For upward vertical bends, <br />use equivalent horizontal thrust block. <br />RN <br />Extensions <br />Existing (L Fairoaks <br />Note <br />Approved Alternative Pipe materials for meeting <br />separation requirements shall be: <br />1. Ductile Iron pipe per AWWA C151. <br />2. Welded steel pipe per AWWA C200, <br />1 /4" thick and lined and wrapped per <br />AWWA C203. <br />3. Class 200 PVC pipe per AWWA C900. <br />4. Reinforced concrete pressure pipe, steel <br />cylinder type per AWWA C300, C301 or C303. <br />Cast iron .locations) <br />seatingRattle-proof, machined <br />. <br />1/8' Finished grade <br />i <br />g' 1717 -FOR OFF STREET <br />LOCATIONS <br />E Concrete base to be <br />N around valve box. <br />Concrete base not <br />necessary when <br />valve box is located <br />in back of sidewalk. <br />No. 10 bare soft drawn <br />copper wire along all non metallic <br />NOTES: pipe <br />1. Valve box and lid shall be Christy No. G-5, <br />Brooks No. I R T or 4 -TT, or equal. <br />2. All lids and grade rings shall have <br />machined seating surfaces. <br />3. Extensions shall be as manufactured for the <br />valve box supplied or pipe of correct size can <br />be used. <br />VALVE BOX <br />NOT TO SCALE <br />q <br />Canal <br />c'➢ <br />I <br />Exist. 36"Dia. Conc. <br />Pipe to remain in \\\\111111 <br />place. <br />V <br />a <br />1'. Min. <br />Provide special construction for separation of water - <br />main from irrigation culvert. Install 18'-0" continuous <br />length of 10"Dia. Alt. Pipe. Center pipe under 36"Dia. <br />culvert. <br />y- <br />°,.��rr< <br />CULVERT CROSSING DETAIL <br />NOT TO SCALE <br />� I <br />W <br />Edge of pavement <br />12" i-�- <br />II <br />I--�----------- <br />I <br />Blue Reflective Pavement Marker <br />Varies <br />PLAN VIEW <br />Variable <br />10"Dia. Alt. Pipe <br />n r „ <br />3" AC <br />pavement <br />T <br />I <br />8' 2' <br />10' <br />R/W <br />2 _i <br />Valve box, frame and lid (At Valpico Rd.) <br />refer to Standard Drawing <br />No. W-4. (See sheet 4) Break -off <br />2" above ground line check valve <br />DRAWN BY DATE PROJECT ENGINEER DATE CHECKED DATE SUBMITTED DATE APP OVED DATE CONSTRUCTION NOTES SHEET TOTAL <br />J.C. White 6/,4,9 COUNTY OF SAN JOAQUIN SCALE: None FAIROAKS WATER SYSTEM NO. SHEETS <br />Q' �7/9z )&-,�✓J - �91271?7_�� G b i��ti: G� ' �i� AND DETAILS <br />INTERCONNECTS PHASE 1 4 4 <br />T77 <br />FILE NAME DRAWER SHEET N0. ACAD <br />D:\FOWSI\SHEET4 <br />Flanged by ring -tate adaptor <br />(as required) <br />Water main <br />' <br />2' x 4' concrete <br />anchor block <br />Conc. thrust block <br />refer to Standard <br />Drawing No. W-5 1 <br />Conc. thrust <br />(See sheet4) <br />block refer to <br />6" flanged or flanged by <br />Standard Drawing <br />ring-tite gate valve <br />No. W-5. <br />Existing Tee <br />NOTES: <br />1. Fire hydrants shall be <br />placed with pumper outlet facing directly towards <br />the street. <br />2. Fire hydrants shall be <br />clean and free of concrete. <br />3. Fire hydrants to be American Darling model B -62B, Long Beach model 615, <br />James Jones J-4060, <br />Dresser M & H style 929 "reliant", Mueller "Centurion" <br />or "Modern Centurion", <br />or approved equal with (2)2 1/2" & (1)4" outlets. <br />Dry barrel in the Stockton area; (2)2 1/2 & (1)4 1/2" wet barrel in other <br />areas as approved by <br />the fire chief. <br />4. All hydrants shall be painted <br />OSHA safety yellow or as approved by the <br />fire district. <br />5. Break off check valve, <br />Long Beach Iron Works, model LB 400, or <br />approved equal <br />FIRE HYDRANDT <br />NOT TO SCALE: <br />DRAWN BY DATE PROJECT ENGINEER DATE CHECKED DATE SUBMITTED DATE APP OVED DATE CONSTRUCTION NOTES SHEET TOTAL <br />J.C. White 6/,4,9 COUNTY OF SAN JOAQUIN SCALE: None FAIROAKS WATER SYSTEM NO. SHEETS <br />Q' �7/9z )&-,�✓J - �91271?7_�� G b i��ti: G� ' �i� AND DETAILS <br />INTERCONNECTS PHASE 1 4 4 <br />T77 <br />FILE NAME DRAWER SHEET N0. ACAD <br />D:\FOWSI\SHEET4 <br />