r.
<br />MAINTENANCE BUILDING
<br />CONTROL PANEL
<br />8" THICK PCC SLAB PEDESTAL MOUN
<br />BASE w/TOP 3" ABOVE
<br />GRADE.
<br />r
<br />4" GRAVEL
<br />u
<br />U
<br />4" GRAVEL
<br />24.00 ALARM ELEV.
<br />4" SAN. SEWER
<br />23.75 4"23.75 4" INV.
<br />23.50 2nd PUMP ON
<br />23.00 FIRST PUMP ON
<br />HEAVY DUTY, NON—CLOG
<br />SUBMERSIBLE SEWAGE PUMP.
<br />PLAN VIEW
<br />NOT TO SCALE
<br />ALUMINUM ACCESS DOOR
<br />w HANDLE,LOCK,HASP &
<br />LOCK OPEN "BILCO" OR
<br />VO 9" O.C.
<br />BOTH WAYS. (TYP.)
<br />_ VALVE
<br />° ENCLOSURE
<br />3 1/2-J
<br />STAINLESS STEE
<br />GUIDE RAIL WATERTIGHT
<br />COMPRESSION
<br />SEAL.(TYP. ALL
<br />�Ik LINES
<br />4"x3"
<br />HAND—OFF AUTOMATIC SWITCH
<br />0
<br />ELAPSED TIME METER
<br />E2
<br />STREET ELL
<br />M
<br />TIME DELAY
<br />0c
<br />'
<br />GALVANIZED
<br />MERCURY PROBE
<br />q J
<br />ALARM LIGHT -100 WATT INCANDESCENT
<br />'
<br />(FLASHING) WITH RED GLOBE.
<br />STEEL CHAIN
<br />CROUSE HINDS VRB-120
<br />SEAL FAILURE LIGHT (RED)
<br />3" GATE VALVE
<br />w/RIN
<br />3" CHECK
<br />• VALVE.
<br />iEALING
<br />RING
<br />2" DRAIN LINE w/CHECK VALVE
<br />(TMP)
<br />°.
<br />4"0 PVC SCHED. 80
<br />e PIPE w/FLANGES
<br />5' DIAMETER WET WELL R.C.P. CL III
<br />Li
<br />OR REINFORCED FIBERGLASS ON
<br />CL
<br />' CONCRETE BASE
<br />EL
<br />-.
<br />w
<br />x
<br />vii
<br />SLIDE—AWAY QUICK
<br />DISCONNECT COUPLINGS.
<br />f'
<br />GROUT
<br />STATIONARY
<br />ELBOW
<br />z� 18.50
<br />#4 O 12" BOTH
<br />STAINLESS STEEL
<br />ANCHOR BOLTS.
<br />PUMP STATION SECTION
<br />NOT TO SCALE
<br />NO. DESCRIPTION wvry IT rirrrNVVAL
<br />APPROVED BY. DATE PLOT DATE: 04/27/95
<br />V)
<br />O PLOT TIME: 07:12
<br />5
<br />W FILE: 93002\PRO_SSPS
<br />O::
<br />PLANS:
<br />CHECKED: ❑ Roger D. Rumph PROFILE:
<br />SCALE
<br />HORIZONTAL: AS SHOWN
<br />RI
<br />3" FORCE MAIN
<br />L•1
<br />NOTES:
<br />1. UNDERGROUND ELECTRIC SERVICE
<br />PER UTILITY CO. SPECIFICATIONS
<br />2. EXTERIOR OF CONTROL
<br />PANEL TO BE PAINTED LIGHT
<br />BUFF COLOR. (2 COATS MIN.)
<br />6' HIGH CHAIN LINK FENCE
<br />NOTES:
<br />THE INSIDE AND OUTSIDE OF WET WELL (IF
<br />CONCRETE PIPE) AND ALL VALVES AND
<br />FITTINGS SHALL BE HEAVILY COATED WITH
<br />COAL TAR EPDXY.
<br />T.B.M. DESCRIPTION:
<br />BRASS CAP 1640' WEST OF SOUTH 99
<br />FRONTAGE ROAD, SOUTH SIDE OF FRENCH
<br />CAMP ROAD, MARKED QR —30.7, U.S.G.S.
<br />DATUM
<br />ELECTRICAL NOTES:
<br />1. All materials, equiptment, and installation work shall conform with the
<br />California Administration Code, Title 24, State Building Standards, Part 3,
<br />Basic Electrical Regulations, the National Electric Code, the NEMA
<br />specifications, and the Division of Industrial Safety requirements.
<br />2. Contractor shall furnish all equipment, materials and labor necessary to provide
<br />a complete and operating electrical installation whether shown on this drawing
<br />or not. Motor control equipment shall be of one manufacturer except as
<br />indicated to insure compatability.
<br />3. All conductors to be type THW insulation.
<br />4. No conduit smaller than 3/4" shall be used.
<br />5. SERVICE ENTRANCE—service entrance conduit and conductors shall be installed
<br />in accordance with P.G. & E. instructions for commercial and industrial
<br />installations and in conformance with local requirements. Verify location of
<br />service with local P.G. & E. representatives.
<br />6. Contractor to provide as—built drawings.
<br />7. All wires shall be numbered and tied where possible.
<br />SAN. SEWER LIFT PUMP STATION IS A PART OF THE
<br />R.V. PARK AND SHALL BE PERMANENTLY OWNED,
<br />OPERATED & MAINTAINED BY OWNER OF R.V. PARK.
<br />CONTROL DIAGRAM
<br />LEGEND
<br />HoA
<br />HAND—OFF AUTOMATIC SWITCH
<br />0
<br />ELAPSED TIME METER
<br />E2
<br />CONTROL RELAY
<br />M
<br />TIME DELAY
<br />0c
<br />RUNNING INDICATOR LIGHT (GREEN)
<br />MSP
<br />MERCURY PROBE
<br />q J
<br />ALARM LIGHT -100 WATT INCANDESCENT
<br />nuc
<br />(FLASHING) WITH RED GLOBE.
<br />CROUSE HINDS VRB-120
<br />SEAL FAILURE LIGHT (RED)
<br />ISR
<br />INTRINSICALLY SAFE RELAY
<br />210 VOLT
<br />1PH. 3W
<br />s
<br />POWER DIAGRAM
<br />119M
<br />RCE ti747
<br />Ep.7rNva►
<br />SHEET
<br />11
<br />OF
<br />UMP STATION SPECIFICATION
<br />Contractor shall furnish and install as shown on these drawings and as described
<br />in these specifications one duplex submersible type sanitary sewer pumping station
<br />complete, including, pumps, motors, electrical controls, quick disconnect system, wet
<br />well and discharge piping.
<br />PUMP AND MOTOR CONSTRUCTION:
<br />Pumps shall be of the heavy duty non—clog type capable of pumping unscreened
<br />sewage consisting of water, heavy sludge and spherical solids up to 2-1/2 inches in
<br />diameter.
<br />Each pump shall have a capacity of 60 GPM O 30' TDH with 50% min. efficiency.
<br />Motors shall be 2 H.P., 1 phase 60 HZ, 240 volts. Both pumps and motors shall
<br />have the capability of running dry for extended periods without damage to motor seals.
<br />Pump volute, motor enclosure and seal housing shall be ASTM A-48 Class 30 cast
<br />iron or better. All fasteners exposed to the pumped liquid and the motor shaft
<br />on which the impeller is mounted shall be stainless steel. Impeller shall be single
<br />or mulitple port enclosed type. Impeller diameter shall be trimmed to meet
<br />specified system flow and head conditions. The inner seal shall operate in a sealed,
<br />oil—filled chamber containing moisture sensing probes capable of detecting any
<br />influx of conductive liquid past the outer seal. Pumps shall be "PACO", "FLYGT"
<br />or approved equal. Replacement parts must be locally available (within a 200
<br />mile radius).
<br />ELECTRICAL CONTROLS:
<br />All electrical controls for the pump station shall be mounted in a NEMA 3R
<br />double—door, dead—front enclosure with a padlock hasp. The controls for each
<br />pump shall include a thermal circuit breaker, a rotary hand—off automatic switch,
<br />a thermal magnetic motor starter with ambient compensated overload relays
<br />and quick trip heaters, running lights and elapsed time meter.
<br />Pump operation shall be controlled by four bulb—type liquid level sensors (Flygt
<br />Model ENP -10 or equivalent): one for lead pump turn—on, one for lag pump turn—on,
<br />one for both pumps turn—off, and one for high water alarm. The pumps shall operate
<br />singly or in parallel. An automatic alternator shall alternate the lead—standby duty on
<br />each succeeding pump cycle. A 0-10 minute adjustable delay timer shall be included in
<br />the lead pump activation circuit. The pumps shall be set
<br />to turn off 2.5 feet above the bottom of the wet well. The on—site alarm shall
<br />include a flashing red light and horn. The alarm circuit shall include 2 spare contacts
<br />for use in transmitting alarm to remote location.
<br />The design of the disconnect system shall permit the easy removal of pumping
<br />units for inspection or service. The pump when lowered into place, shall be
<br />automatically connected to the discharge piping. There shall be no need for
<br />personnel to enter the wet well to inspect or service the pump. Pump shall be
<br />securely attached to a sliding guide bracket. A minimum schedule 40 standard
<br />stainless steel pipe guide rail shall be furnished and installed by the contractor.
<br />The sliding guide bracket shall have non—sparking material at the point of contact
<br />with the guide rail to prevent spark ignition of explosive wet well gases during
<br />pump installation and removal. A cast iron discharge elbow, located on the floor
<br />of the wet well, will receive the pump discharge when the pump is lowered into
<br />place. The receiving edge of the discharge elbow shall be fitted with non—sparking
<br />material to prevent spark ignition of explosive wet well gases during pump
<br />installation and removal. The pump discharge shall be fitted with a resilient seal
<br />which provides a positive hydraulic seal for maximum pump system efficiency.
<br />The lower guide rail bracket shall be mounted by the pump manufacturer on a steel
<br />base plate, in alignment for proper operation of the disconnect system. The base
<br />assembly shall provide stable, three point support of the pumping unit during pump
<br />operation. The entire quick disconnect pumping system must be listed and labeled
<br />by underwriters laboratory (UL) as suitable for operation in Class 1, Group D,
<br />Division 1 located as defined in Section 501-8 of the National Electric Code.
<br />DISCHARGE PIPING:
<br />The discharge piping for each pump shall include cast iron discharge elbow,
<br />schedule 80 PVC and flanged fittings, 175 PSI flanged check valve with spring assist,
<br />especially designed to handle raw sewage, 125 PSI flanged gate valve and flexible coupling.
<br />WET LLTYEL
<br />The wet well shall be constructed of 6 feet diameter Class III reinforced concrete
<br />pipe (R.C.P.) with PCC base, fully lined with coal tar epoxy or reinforced fiberglass
<br />on a PCC base.
<br />TESTING:
<br />The entire installation shall be tested in the presence of the owner. Panel and circuits
<br />shall be tested for shorts and ground with mains and disconnect from feeders. Each
<br />individual circuit shall be tested at the panel with all equipment connected for proper
<br />operation. The actual flow rates shall be measured for all phases of operation. The
<br />actual flow rates shall be within 10% of the specified design. flow rates when tested
<br />at the design head.
<br />OPERATION AND MAINTENANCE:
<br />Contractor shall furnish the owner three (3) bound sets of 0 & M manuals
<br />including complete wiring diagram, exploded view of all electrical components, pump
<br />equipment and pump curve, all part numbers and one laminated wire schematic in
<br />pocket on panel door. He shall also provide the owner the name, address
<br />and phone number of the nearest local distributors for parts.
<br />WARRANTY:
<br />All material including pumps, valves, electrical controls, etc. shall be warranted for
<br />a minimum one—year period from the date of final acceptance by the Owner.
<br />ASSOCIATES, INC.
<br />P.O.Hoz ese
<br />40 San Andreas, Ca. 95m
<br />Ph. (209) 754-3588
<br />FRENCH CAMP GOLF & R. V. PARK
<br />PRO -SHOP SAN. SEWER PUMP STATION
<br />DATE: Z 9S
<br />RCE NO: 12741
<br />9 z F eirvt.A e EXP. DATE: 3/31/94
<br />DESIGN ENGINE R
<br />
|