to
<br />-o-
<br />r
<br />R.V. PARK
<br />-0-0-0
<br />CONTROL PANEL
<br />8" THICK PCC SLAB PEDESTAL MOUN
<br />BASE w/TOP 3" ABOVE
<br />GRADE.
<br />W
<br />W
<br />n
<br />0— NOTES:
<br />1. UNDERGROUND ELECTRIC SERVICE
<br />PER UTILITY CO. SPECIFICATIONS
<br />2. EXTERIOR OF CONTROL
<br />PANEL TO BE PAINTED LIGHT
<br />BUFF COLOR. (2 COATS MIN.)
<br />4" GRAVEL
<br />V 0
<br />0 0'
<br />�'- 0 --�120 WIDE SINGLE
<br />FIRE EMERGENCY ACCESS ROAD
<br />4" GRAVEL
<br />AlCLavllliTZ
<br />NOT TO SCALE
<br />ALUMINUM ACCESS DOOR
<br />w HANDLE,LOCK,HASP &
<br />LOCK OPEN "BILCO" OR E
<br />15 0 9" D.C.
<br />0TH WAYS. (TYP.)
<br />3 1/2--J
<br />GUIDE RAIL.
<br />°
<br />ELL.
<br />VALVE
<br />ENCLOSURE
<br />E
<br />WATERTIGHT N
<br />COMPRESSION
<br />SEAL (TYP. ALL 4" FORCE MAIN
<br />LINES)
<br />- GALVANIZED
<br />S•T�EL CHAIN 4" GATE VALVE
<br />19.00 ALARM ELEV. w/RING °. 4" CHECK
<br />VALVE.
<br />6" SAN. SEWER SEALING ''
<br />2" DRAIN UNE w/CHECK VALVE
<br />RING
<br />18.75 6" INV.
<br />(TYP-)
<br />18.50 2nd PUMP ON
<br />4"0 PVC SCHED. 80
<br />> PIPE w/FLANGES
<br />°
<br />17.50 FIRST PUMP ON
<br />°. 6' DIAMETER WET WELL R.C.P. CL. III
<br />'.. w + OR REINFORCED FIBERGLASS ON
<br />CIL ' CONCRETE BASE
<br />a.
<br />.. w
<br />Ir °..
<br />:' x
<br />VV) SLIDE -AWAY QUICK
<br />C3 DISCONNECT COUPLINGS.
<br />15.00 BOTH PUMPS OFF ° r
<br />HEAVY DUTY, NON -CLOG ° GROUT
<br />SUBMERSIBLE SEWAGE PUMP.
<br />STATIONARY
<br />10" " ELBOW
<br />zF 12.50
<br />...........
<br />#4 O 12" BOTH
<br />STAINLESS STEEL
<br />ANCHOR BOLTS.
<br />PUMP STATION SECTION
<br />NOT TO SCALE
<br />NO. DESCRIPTION COUNTY APPROVAL
<br />APPROVED BY.• DATE PLOT DATE: 04/26/95 SCALE
<br />HORIZONTAL: AS SHOWN
<br />U)
<br />O PLOT TIME: 17:59
<br />W FILE: 93002\MAINSSPS SURVEY
<br />PLANS: F.B.:
<br />CHECKED: ❑ Roger D. Rumph PROFILE: F.B.:
<br />3
<br />6' HIGH CHAIN LINK FENCE
<br />THE INSIDE AND OUTSIDE OF WET WELL (IF
<br />CONCRETE PIPE) AND ALL VALVES AND
<br />FITTINGS SHALL BE HEAVILY COATED WITH
<br />COAL TAR EPDXY.
<br />T.B.M. DES
<br />BRASS CAP 1640' WEST OF SOUTH 99
<br />FRONTAGE ROAD, SOUTH SIDE OF FRENCH
<br />CAMP ROAD, MARKED QR -30.7, U.S.G.S.
<br />DATUM
<br />ELECTRICAL NOTES:
<br />1. All materials, equiptment, and installation work shall conform with the
<br />California Administration Code, Title 24, State Building Standards, Part 3,
<br />Basic Electrical Regulations, the National Electric Code, the NEMA
<br />specifications, and the Division of Industrial Safety requirements.
<br />2. Contractor shall furnish all equipment, materials and labor necessary to provide
<br />a complete and operating electrical installation whether shown on this drawing
<br />or not. Motor control equipment shall be of one manufacturer except as
<br />indicated to insure compatability.
<br />3. All conductors to be type THW insulation.
<br />4. No conduit smaller than 3/4" shall be used.
<br />5. SERVICE ENTRANCE—service entrance conduit and conductors shall be installed
<br />in accordance with P.G. & E. instructions for commercial and industrial
<br />installations and in conformance with local requirements. Verify location of
<br />service with local P.G. & E. representatives.
<br />6. Contractor to provide as—built drawings.
<br />7. All wires shall be numbered and tied where possible.
<br />SAN. SEWER LIFT PUMP STATION IS A PART OF THE
<br />R.V. PARK AND SHALL BE PERMANENTLY OWNED,
<br />OPERATED & MAINTAINED BY OWNER OF R.V. PARK.
<br />CONTROL DIAGRAM
<br />ELEVATION:
<br />28.118'
<br />LEGEND
<br />HOA HAND-OFF AUTOMATIC SWITCH
<br />FE-Tm-1 ELAPSED TIME METER
<br />atz CONTROL RELAY
<br />TD TIME DELAY
<br />0c RUNNING INDICATOR UGHT (GREEN)
<br />MP MERCURY PROBE
<br />IA) ALARM UGHT-100 WATT INCANDESCENT
<br />nn��cc (FLASHING) WITH RED GLOBE.
<br />CROUSE HINDS VRB-120
<br />® SEAL FAILURE LIGHT (RED)
<br />®SEWER TREATMENT PLANT CONTROL RELAY -
<br />HIGH WATER IN BUFFER TANK
<br />ISR INTRINSICALLY SAFE RELAY
<br />450 VOLT
<br />,3PH
<br />Ilelam:0Inspl]I:TenzAaml
<br />SHEET
<br />I I
<br />OF
<br />L irmo ► —M 0 ► O NIM. I"G h,
<br />Contractor shall furnish and install as shown on these drawings and as described
<br />in these specifications one duplex submersible type sanitary sewer pumping station
<br />complete, including, pumps, motors, electrical controls, quick disconnect system, wet
<br />well and discharge piping.
<br />PUMP AND MOTOR CONSTRUCTION:
<br />Pumps shall be of the heavy duty non—clog type capable of pumping unscreened
<br />sewage consisting of water, heavy sludge and spherical solids up to 3 inches in
<br />diameter.
<br />Each pump shall have a capacity of 175 GPM ® 35' TDH with 50% minimum
<br />efficiency and 120 GPM ® 39' TDH.
<br />Motors shall be 5 H.P., 3 phases 60 HZ, 480 volts. Both pumps and motors shall
<br />have the capability of running dry for extended periods without damage to motor seals.
<br />Pump volute, motor enclosure and seal housing shall be ASTM A-48 Class 30 cast
<br />iron or better. All fasteners exposed to the pumped liquid and the motor shaft
<br />on which the impeller is mounted shall be stainless steel. Impeller shall be single
<br />or mulitple port enclosed type. Impeller diameter shall be trimmed to meet
<br />specified system flow and head conditions. The inner seal shall operate in a sealed,
<br />oil—filled chamber containing moisture sensing probes capable of detecting any
<br />influx of conductive liquid past the outer seal. Pumps shall be "PACO", FLYGT"
<br />or -approved equal. Replacement parts must be locally available (within a 200
<br />mile radius).
<br />ELECTRICAL CONTROLS:
<br />All electrical controls for the pump station shall be mounted in a NEMA 3R
<br />double—door, dead—front enclosure with a padlock hasp. The controls for each
<br />pump shall include a thermal circuit breaker, a rotary hand—off automatic switch,
<br />a thermal magnetic motor starter with ambient compensated overload relays
<br />and quick trip heaters, running lights and elapsed time meter.
<br />Pump operation shall be controlled by four bulb—type liquid level sensors (Flygt
<br />Model ENP -10 or equivalent): one for lead pump turn—on, one for lag pump turn—on,
<br />one for both pumps turn—off, and one for high water alarm. The pumps shall operate
<br />singly or in parallel. An automatic alternator shall alternate the lead—standby duty on
<br />each succeeding pump cycle. A 0-10 minute adjustable delay timer shall be included in
<br />the lead pump activation circuit. The pumps shall be set
<br />to tum off 2.5 feet above the bottom of the wet well. The on—site alarm shall
<br />include a flashing red light and horn. The alarm circuit shall include 2 spare contacts
<br />for use in transmitting alarm to remote location.
<br />DISCONNECT SYSTEM:
<br />The design of the disconnect system shall permit the easy removal of pumping
<br />units for inspection or service. The pump when lowered into place, shall be
<br />automatically connected to the discharge piping. There shall be no need for
<br />personnel to enter the wet well to inspect or service the pump. Pump shall be
<br />securely attached to a sliding guide bracket. A minimum schedule 40 standard
<br />stainless steel pipe guide rail shall be furnished and installed by the contractor.
<br />The sliding guide bracket shall have non -sparking material at the point of contact
<br />with the guide rail to prevent spark ignition of explosive wet well gases during
<br />pump installation and removal. A cast iron discharge elbow, located on the floor
<br />of the wet well, will receive the pump discharge when the pump is lowered into
<br />place. The receiving edge of the discharge elbow shall be fitted with non -sparking
<br />material to prevent spark ignition of explosive wet well gases during pump
<br />installation and removal. The pump discharge shall be fitted with a resilient seal
<br />which provides a positive hydraulic seal for maximum pump system efficiency.
<br />The lower guide rail bracket shall be mounted by the pump manufacturer on a steel
<br />base plate, in alignment for proper operation of the disconnect system. The base
<br />assembly shall provide stable, three point support of the pumping unit during pump
<br />operation. The entire quick disconnect pumping system must be listed and labeled
<br />by underwriter's laboratory (UL) as suitable for operation in Class 1, Group D,
<br />Division 1 located as defined in Section 501-8 of the National Electric Code.
<br />DISCHARGE PIPING:
<br />The discharge piping for each pump shall include cast iron discharge elbow,
<br />schedule 80 PVC and flanged fittings, 175 PSI flanged check valve with spring assist,
<br />especially designed to handle raw sewage, 125 PSI flanged gate valve and flexible coupling.
<br />WET WELL:
<br />The wet well shall be constructed of 6 feet diameter Class III reinforced concrete
<br />pipe (R.C.P.) with PCC base, fully lined with coal tar epoxy or reinforced fiberglass
<br />on a PCC base.
<br />TESTING:
<br />The entire installation shall be tested in the presence of the owner. Panel and circuits
<br />shall be tested for shorts and ground with mains and disconnect from feeders. Each
<br />individual circuit shall be tested at the panel with all equipment connected for proper
<br />operation. The actual flow rates shall be measured for all phases of operation. The
<br />actual flow rates shall be within 10% of the specified design. flow rates when tested
<br />at the design head.
<br />OPERATION AND MAINTENANCE:
<br />Contractor shall furnish the owner three (3) bound sets of 0 & M manuals
<br />including complete wiring diagram, exploded view of all electrical components, pump
<br />equipment and pump curve, all part numbers and one laminated wire schematic in
<br />pocket on panel door. He shall also provide the owner the name, address
<br />and phone number of the nearest local distributors for parts.
<br />WARRANTY'
<br />All material including pumps, valves, electrical controls, etc. shall be warranted for
<br />a minimum one-year period from the date of final acceptance by the Owner.
<br />ASSOCIATES, INC.
<br />P.O.Box see
<br />San Andreas, Ca. 95249
<br />Ph. (209) 754-3588
<br />FRENCH CAMP GOLF & R. V. PARK
<br />MAIN SANITARY SEWER PUMP STATION
<br />DATE: 4L/Z7 195
<br />/ RCE NO: 12741
<br />EXP. DATE: 3/31/94
<br />DESIGN ENGIN R