Laserfiche WebLink
Street R/W <br />Metal lid on <br />all meter boxes <br />Christy C-20 <br />Exist. Ground lid, or equal \ <br />Bottom of Ditch Christy 812 box, Of <br />(if any) boxequal meter <br />Meter <br />eN Angle <br />Stop <br />0 <br />M Service Line <br />3/4" Min. Size <br />( Connection <br />Corporation Adaptor 5/8" 0 x 36" Rebar with <br />Stop 2 hose clamps 12" apart <br />24" min conver below bottom <br />Service Clamp of ditch (if any) <br />1 or larger <br />ouble Strap) <br />NOTES: <br />1. Service line material shall be type k copper, polyethylene <br />or polybutylene pplastic. <br />2. Plastic pipe up to 1 1/4" I.D. service shall be ultra high <br />molecular weight (UHMW) Polyethlene as manufactured by <br />"Driscopipe", Orangeburg or approved equal with minimum <br />pressure rating of l60 psi. <br />3. Plastic pipe for 2" I.D. service shall be PB 2110 <br />Polybutylene or approved equal with minimum pressure <br />rating of 160 psi. <br />4. Corporation stop shall have corporation cock threads. <br />5. Angle stop shall have swivel nut and lock wings. <br />6. Angle stop shall be vertically plumbed. <br />7. Size of service line shall be as required by the County. <br />8. Mueller Insta-tite fittings shall conform to ASTM <br />designation D 2239. <br />9. Meter shall be Precision Meter Inc. model PPM 5/8"x3/4" <br />with attachment connector spuds <br />10. Lockable corporation cock will precede the meter and entire <br />setup will be in the confines of the water box. <br />11. Non metallic services shall have a No. 10 gauge solid, bare, <br />soft drawn copper wire laid along the service line, and accessible <br />in the meter box. <br />na 1 y 1 1 Mwev4a by <br />WATER SERVICE <br />y JLD <br />by COUNTY OF SAN JOAQUIN Dele SEPT. 1991 <br />=e+• None asamear a MUC raw are,lea x.. W - 1 <br />Line Post <br />END <br />AND CORNER <br />POST <br />ASSEMBLY <br />2'-6" <br />for fabric less than 60" high <br />3'-0" <br />for fabric 60"and over <br />F oflzonteelbg".e rods <br />//ate" watt cats poet 8' max <br />aata aanel <br />Concrete <br />Type CL -4=48" <br />Type CL -6=72" <br />3'-a' at gate poet <br />P.0 Concrete lit <br />D' -� <br />Er <br />r. -- <br />Not less than 3 times max. cross <br />section of post with min. of 8" <br />2'-6" for fabric less than 60" high <br />3'-(r for fabric 60"and over <br />10' <br />Fabric on <br />outside of <br />fence <br />Curb, gutter, and Edge of <br />sidewalk pavement <br />pavement <br />12" Ij 1 z l T <br />I <br />I I 18" <br />I 46 <br />Blue Reflective Pavement Marker <br />PLAN VIEW R/W <br />Variable 1' <br />Break -off <br />check valve or <br />Valve box, frame and lid joint as req'd. <br />refer to Standard Drawing by director <br />No. W-4. <br />Z" above ground line ID <br />Flanged by ring-tite adaptor <br />(as required) <br />Water main <br />2' x 4' concrete <br />anchor block <br />Conc. thrust block <br />refer to Standard 1 <br />Conc. thrust Drawing No. IN <br />block refer to 6" flanged or flanged by <br />Standard Drawingring-tite gate valve <br />No. W-5. <br />Tifco No. 11 tee or equal <br />NOTES: <br />1. Fire hydrants shall be placed with pumper outlet facing directly towards <br />the street. <br />2. Fire hydrants shall be clean and free of concrete. <br />3. Fire hydrants to be American Darling model B -62B, Loiwq Beach model 615, <br />James Jones J-4060, Dresser M & H style 929 "reliant , Mueller "Centurion" <br />or "Modern Centurion", or approved equal with (2)2 1/2" & (1)4" outlets. <br />Dry barrel in the Stockton area; (2)2 1/2" & (1)4 1/2" wet barrel in other <br />areas as approved by the fire chief. <br />4. All hydrants shall be painted OSHA safety yellow or as approved by the <br />fire district. <br />5. Break off check valve, Long Beach Iron Works, model LB 400, or <br />approved equal <br />x.. rxrbe M we... by <br />FIRE HYDRANT <br />pee by JLD <br />by COUNTY OF SAN JOAQUIN ow SEPT. 1991 <br />rx+e NONE DO UP" OF nnuc rasa a,velr w• W _ 2 <br />Brace to be removed after all <br />other fence consturction is <br />completed unless otherwise <br />directed by the Engineer <br />Line post <br />Brace <br />Tmss <br />rods <br />itell <br />Line posts of 1000' max. intervals <br />braced and trussed in both directions <br />except that this bracing and trussing <br />may be omtted when the fabric is <br />stretched by equipment <br />P/L <br />P/L <br />6 or as specified <br />or shown on <br />detail plans <br />(See note below) <br />Facility <br />NOTE: Offset to be 2'-0" at monument locations <br />measured at ft angles to R/W lines. <br />Taper to achieve offset to be at least 20' long. <br />FENCE LOCATION <br />' <br />S <br />LLJ <br />NO. <br />DESCRIPTION <br />GUUN I r At'PKUVAL <br />Weight <br />PLOT DATE: 01/11/95 <br />SCALE <br />NOT TO SCALE <br />APPROVED BY. <br />DATE <br />Fence <br />Up thru 6' <br />2 1/2 <br />4.95 <br />PLOT TIME: 15:30 <br />Over 6'thru 12' <br />4" <br />10.79 <br />22 1/2 <br />Height <br />Round <br />(ID) <br />H <br />and <br />FILE: 93002\DETAILt <br />SURVEY <br />PLANS: F.B.: _ <br />PROFILE: F.B.: _ <br />Round <br />(ID) <br />Lessthra <br />18' <br />S" <br />14.62 <br />90 <br />Over 18'to <br />6 " <br />CHECKED: ❑ Roger D. Rumph <br />24' Max. <br />TEE OUTLET <br />'-0" <br />FOR ALL STREET <br />LOCATIONS - <br />2" asphalt concrete - <br />IN <br />Extensions <br />Cast iron lid (all locations) <br />eu <br />Rattle -proof, machined <br />seating surface <br />-14 114--Er- <br />518" <br />/4 6"-5/8" <br />11 1/8" Finished grade <br />20) <br />c <br />E <br />N <br />NOTES: <br />1. Valve box and lid shall be Christy No. G-5, <br />Brooks No. I R T or 4 -TT, or equal. <br />2. All lids and grade rings shall have <br />machined seating surfaces. <br />3. Extensions shall be as manufactured for the <br />valve box supplied or pipe of correct size can <br />be used. <br />N <br />FOR OFF STREET <br />LOCATIONS <br />Concrete base to be <br />around valve box. <br />Concrete base not <br />necessary when <br />valve box is located <br />in back of sidewalk. <br />VALVE BOX •Wee <br />a.e y JLD <br />"ie4i° by COUNTY OF SAN JOAQUIN oee SEPT. 1991 <br />aerie NONE aewm`e"r of ruwro rclw aa,+s re. W - 4 <br />GATE POST <br />Fence <br />Gate <br />Nominal <br />Weight <br />Height <br />Width <br />I.D. <br />per Foot <br />Fence <br />Up thru 6' <br />2 1/2 <br />4.95 <br />6'-0" <br />Over 6'thru 12' <br />4" <br />10.79 <br />22 1/2 <br />Height <br />Round <br />(ID) <br />H <br />and <br />Over 12' <br />Roll Formed <br />Round <br />(ID) <br />Lessthra <br />18' <br />S" <br />14.62 <br />90 <br />Over 18'to <br />6 " <br />18.97 <br />24' Max. <br />TEE OUTLET <br />'-0" <br />2,-cr4'- <br />Up thru 6' <br />3" <br />7.58 <br />Over <br />less <br />1 1/2 • <br />1 )/a x1 a/a <br />1 )/e x1 a/a <br />S <br />J 1/1 a 1/2 <br />2 x 1 3/4 <br />6" <br />Over 6'thru 12' <br />5" <br />14.62 <br />over <br />Over 12' <br />6" <br />18.97 <br />3' 1 <br />thru 18' <br />45 <br />3'-O" <br />2'-6EE <br />Over 18'to <br />4'- <br />2$,55 <br />r <br />24' Max. <br />2 1/4 xt J/4 <br />2 1/2 • <br />NOTE: <br />Above post dimensions and weights are minimums <br />Larger sizes may be used on approval of Engineer <br />O .� <br />Typical Fabric Mounting Details <br />TYPICALMEMBER DIMENSIONS <br />sIONS(See Note ) <br />THRUST <br />Line Postses <br />Latch Poste Comer <br />#4 0 18" O.C. <br />7-1/4" <br />I <br />S-0.015 C' =p,015 <br />FITTINGS <br />A <br />-1/4- <br />Fence <br />A <br />T & B <br />LINE <br />I <br />10 LINE <br />22 1/2 <br />Height <br />Round <br />(ID) <br />H <br />Roll <br />roared <br />Round <br />(ID) <br />Roll Formed <br />Round <br />(ID) <br />" <br />Roll Formed <br />41- <br />90 <br />n <br />Wand <br />4' - <br />TEE OUTLET <br />'-0" <br />2,-cr4'- <br />DEAD END <br />less <br />1 1/2 • <br />1 )/a x1 a/a <br />1 )/e x1 a/a <br />S <br />J 1/1 a 1/2 <br />2 x 1 3/4 <br />1 1/4 ' <br />1 1/2 .1 5/16 <br />1a/a x1 1/4 <br />1 3/4 x1 1/ <br />over <br />'-0" I <br />2'- <br />3' 1 <br />3'- <br />45 <br />3'-O" <br />2'-6EE <br />4'- <br />6. <br />r <br />2 1/4 ,Q <br />2 1/4 xt J/4 <br />2 1/2 • <br />J 1/2 1a 1/2 <br />2 1/2 ,a 1/1 <br />1 1/4 - <br />1 1/2 xi a/18 <br />1 a/s x1 1/4 <br />1 3/4 x1 1/ <br />NOTES: <br />1. The above table shows examples of post and brace sections which may <br />comply with the Specifications <br />2. Sections shown in the tables must also comply with the strength <br />requirements and other provisions of the Specifications <br />3. Other sections which comply with the strength requirements and other <br />of the Specifications may be used on approval of the Engineer <br />4. Options exercised shall be uniform on any one project <br />5. Dimensions shown are nominal <br />6. Plastic slats are required when specified on the plans <br />B.M._DESCRIPTION: <br />BRASS CAP 1640' WEST OF SOUTH 99 <br />FRONTAGE ROAD, SOUTH SIDE OF FRENCH <br />CAMP ROAD, MARKED QR -30.7, U.S.G.S. <br />DATUM <br />ELEVATION: <br />28.118' <br />THRUST BLOCK DETAILS <br />45' Max. <br />d�Fe <br />• I... '7 .: . <br />C13 n <br />4 ".4 .= s 1. 4 ...>, a :4 �'4 a ..' <br />17 <br />Min. <br />BEND TEE OUTLET DEAD END TYPICAL SECTION <br />THRU <br />THRUST BLOCK <br />NOTES: <br />1. All khr st bIo ks shall be p ured <br />agams undls urbed soil an d° shall <br />be Class "Er Concrete. <br />2. Thrust blockk di ensions ,were <br />calculated to a�ow a soil <br />bearing value of 1,000 pounds <br />per square foot. <br />N.. IM,Yea M MMe+ea y <br />THRUST BLOCK DETAILS <br />a..e <br />by JLD <br />O."d by COUNTY OF SAN JOAQUIN ow. SEPT. 1991 <br />r^+• NONE avwrrar OF neuo area aero ro. W - 5 <br />Q <br />I I I I I I <br />3'-0" 1'-6" d 1'-6" 3'-0" <br />z'-0 I SCREENED INLET \ <br />----- --I� 24" <br />I 24" I I t I I I I <br />MH SLOPE BOTTOM <br />C I--I--�-c---------- y----I--I_ i <br />0.015 (TYP.) <br />" <br />MH <br />9-1/4' Q 9_ /4" <br />24'-0" <br />PLAN VIEW <br />!b 18" O.C. <br />F & B <br />Jt(_; I IUN U -C <br />4" DIA. PIPE OPENING <br />WITH SEALING RING - <br />SEE SEWER TREATMENT <br />PLANS FOR LOCATION m <br />00 <br />NOTES: <br />- LAP REINFORCEMENT 45 DIAMETERS (TYP.) <br />- TANK SHALL BE WATERPROOFED INSIDE <br />AND OUTSIDE WITH A HEAVY COATING OF <br />COAL TAR EPDXY. <br />BUFFER TANK @ <br />SANITARY TREATMENT PLANT <br />NOT TO SCALE <br />p00EP 0. <br />1V& <br />em "Ife'r <br />CAVIL _. <br />SHEET <br />U -� <br />OF 12 <br />1A" <br />#6 0 18" O.C. <br />x <br />O.C. \ <br />B j <br />a1� <br />THRUST <br />BLOCK <br />DIMENSIONS <br />#4 0 18" O.C. <br />7-1/4" <br />I <br />S-0.015 C' =p,015 <br />FITTINGS <br />A <br />-1/4- <br />FITTINGS <br />A <br />T & B <br />LINE <br />I <br />10 LINE <br />22 1/2 <br />1'-6" <br />11- <br />-#4 0 <br />3'- <br />2'- <br />45 <br />'-0" <br />'- <br />#6 0 9" O.C. <br />41- <br />3'- <br />90 <br />3'-0" <br />-27-r-5'- <br />4' - <br />TEE OUTLET <br />'-0" <br />2,-cr4'- <br />DEAD END <br />3'-0" <br />2'-0" <br />4'-O" <br />4'-0" <br />LINE <br />1 <br />LINE <br />22 1/2 <br />'-0" I <br />2'- <br />3' 1 <br />3'- <br />45 <br />3'-O" <br />2'-6EE <br />4'- <br />4'- <br />0 <br />4'-O" <br />3'-6" <br />8'-0" <br />4'-0 <br />-TEE OUTLET <br />3'-6" <br />Y -O" <br />5'- <br />4'-O" <br />DEAD END <br />3'-6" <br />3'-O" <br />5'-6" <br />4'-O" <br />NOTES: <br />1. All khr st bIo ks shall be p ured <br />agams undls urbed soil an d° shall <br />be Class "Er Concrete. <br />2. Thrust blockk di ensions ,were <br />calculated to a�ow a soil <br />bearing value of 1,000 pounds <br />per square foot. <br />N.. IM,Yea M MMe+ea y <br />THRUST BLOCK DETAILS <br />a..e <br />by JLD <br />O."d by COUNTY OF SAN JOAQUIN ow. SEPT. 1991 <br />r^+• NONE avwrrar OF neuo area aero ro. W - 5 <br />Q <br />I I I I I I <br />3'-0" 1'-6" d 1'-6" 3'-0" <br />z'-0 I SCREENED INLET \ <br />----- --I� 24" <br />I 24" I I t I I I I <br />MH SLOPE BOTTOM <br />C I--I--�-c---------- y----I--I_ i <br />0.015 (TYP.) <br />" <br />MH <br />9-1/4' Q 9_ /4" <br />24'-0" <br />PLAN VIEW <br />!b 18" O.C. <br />F & B <br />Jt(_; I IUN U -C <br />4" DIA. PIPE OPENING <br />WITH SEALING RING - <br />SEE SEWER TREATMENT <br />PLANS FOR LOCATION m <br />00 <br />NOTES: <br />- LAP REINFORCEMENT 45 DIAMETERS (TYP.) <br />- TANK SHALL BE WATERPROOFED INSIDE <br />AND OUTSIDE WITH A HEAVY COATING OF <br />COAL TAR EPDXY. <br />BUFFER TANK @ <br />SANITARY TREATMENT PLANT <br />NOT TO SCALE <br />p00EP 0. <br />1V& <br />em "Ife'r <br />CAVIL _. <br />SHEET <br />U -� <br />OF 12 <br />1A" <br />#6 0 18" O.C. <br />x <br />O.C. \ <br />B j <br />a1� <br />#6 0 18" O.C. <br />SECTION A -A <br />1/4" <br />STD. CAST IRON <br />MANHOLE FRAME <br />r, <br />AND COVER (TYP.) <br />2-5.7 <br />3" CLR <br />TYP. <br />9-1/4" <br />#6 0 9" O.C. <br />5=0.015 r015 <br />#4 0 18" O.C. <br />7-1/4" <br />I <br />S-0.015 C' =p,015 <br />V#4 0 18" O.C. <br />-1/4- <br />#6 0 18" O.C. <br />SECTION A -A <br />1/4" <br />STD. CAST IRON <br />MANHOLE FRAME <br />r, <br />AND COVER (TYP.) <br />2-5.7 <br />SECTION B -B <br />#4 0 18" O.C. <br />T & B <br />ASSOCIATES, INC. <br />�► P.O.Box see <br />San Andreas, Ca. 95249 <br />it <br />Ph. (209) 754-3588 <br />FRENCH CAMP GOLF & R. V. PARK <br />UTILITIES & FENCING DETAILS <br />% DATE: <br />RCE NO: 12741 <br />1 61�#6 <br />V#4 0 18" O.C. <br />-1/4- <br />� <br />0 9" O.C. <br />T & B <br />I <br />T & B <br />N <br />9-1/4- <br />-#4 0 <br />18" O.C. <br />#s®s"O.C. <br />1#6 <br />0 9" O.C. <br />#6 0 9" O.C. <br />1-1/2" CHAMFER <br />T & B <br />TYP. ALL <br />ACORNERS <br />S=0.015 <br />SECTION B -B <br />#4 0 18" O.C. <br />T & B <br />ASSOCIATES, INC. <br />�► P.O.Box see <br />San Andreas, Ca. 95249 <br />it <br />Ph. (209) 754-3588 <br />FRENCH CAMP GOLF & R. V. PARK <br />UTILITIES & FENCING DETAILS <br />% DATE: <br />RCE NO: 12741 <br />