ALL RUBBER GASKET, PUSH -ON, MECHANICAL AND FLANGED JOINT FITTINGS FOR CAST IRON OR DUCTILE IRON WATER <br />PIPE SHALL BE MANUFACTURED IN ACCORDANCE WITH ANSI A21.10 (AWWA C110). <br />UNLESS OTHERWISE SPECIFIED, THE INTERNAL SURFACES OF CAST IRON AND DUCTILE IRON WATER PIPE AND FITTINGS <br />SHALL BE LINED WITH A UNIFORM THICKNESS OF CEMENT MORTAR THEN SEALED WITH A BITUMINOUS COATING IN <br />ACCORDANCE WITH ANSI A21.4 (AWWA C104). THE OUTSIDE SURFACES OF CAST IRON AND DUCTILE IRON PIPE AND <br />FITTINGS FOR GENERAL USE SHALL BE COATED WITH A BITUMINOUS COATING ONE (1) NIL (0.0254MM) THICK IN <br />ACCORDANCE WITH ANSI A21.6 OR ANSI A21.51. <br />1. POLYVINYL CHLORIDE (PVC) PIPE SHALL BE FURNISHED IN THE CLASSES, SIZES, AND GRADES DESIGNATED ON <br />THE PLANS AND SPECIAL PROVISIONS. <br />POLYVINYL CHLORIDE PIPE SHALL MEET THE REQUIREMENTS OF AWWA C-900 "POLYVINYL CHLORIDE (PVC) PRESSURE <br />PIPE." PIPE SIZES SHALL BE FOUR INCHES (4") THROUGH TWELVE INCHES (12") ONLY - AWWA CLASS 150 MINIMUM. <br />ALL CLASS 150 PIPE SHALL MEET THE REQUIREMENTS OF DR 18 AND CLASS 200 PIPE SHALL MEET THE REQUIREMENTS <br />OF DR 14 WITH CAST IRON O.D. <br />ALL PIPE SHALL BE SUITABLE FOR USE AS A PRESSURE CONDUIT. PROVISIONS SHALL BE MADE FOR EXPANSION AND <br />CONTRACTION AT EACH JOINT WITH AN 00" RING ELASTOMERIC GASKET SEAL MEETING THE REQUIREMENTS OR ASTM <br />D-1869 AND F-477. SOLVENT WELDED JOINTS WILL NOT BE PERMITTED. THE BELL SECTION SHALL BE DESIGNED TO BE <br />AT LEAST AS STRONG AS THE PIPE WALL. <br />III III�10r1l:a•UT1111111111919�92,TOIaa311111547_SI111111I:Z1h1961zI <br />2. WHEN SPECIAL CONSTRUCTION OF THE WATER MAIN IS REQUIRED FOR THE SEPARATION OF WATER MAINS AND <br />SANITARY SEWERS OR STORM DRAINS AS SET FORTH IN SECTION 64630 OF TITLE 22 OF THE CALIFORNIA <br />ADMINISTRATIVE CODE, ALTERNATE PIPE SHALL CONSIST OF THE FOLLOWING: <br />1. DUCTILE IRON PIPE PER AWWA C151; <br />2. WELDED STEEL PIPE PER AWWA C200, 1/4 -INCH THICK AND LINED AND WRAPPED PER AWWA C203; <br />3. CLASS 200 PVC PIPE PER AWWA C900; <br />4. REINFORCED CONCRETE PRESSURE PIPE, STEEL CYLINDER TYPE, PER AWWA C300, C301 OR C303. <br />INSTALLATION AND CLEARANCES FOR WATER MAIN CROSSINGS SHALL BE IN ACCORDANCE WITH THE REQUIREMENTS OF <br />SECTION 64630 OF TITLE 22, CALIFORNIA ADMINISTRATIVE CODE AND THESE PLANS AND SPECIAL PROVISIONS. <br />VALVES. THIS SPECIFICATION INCLUDES FOUR INCH (4") THROUGH TWELVE INCH (12') DIAMETER VALVES OF ALL KINDS <br />FOR BURIED SERVICE IN A DOMESTIC WATER SYSTEM. <br />GATE VALVES SHALL BE DOUBLE DISC TYPE WITH PARALLEL SEATS AND NONRISING STEMS, MEETING OR EXCEEDING THE <br />LATEST REVISIONS OF AWWA C500 WITH A DESIGN WORKING PRESSURE OF 200.0 PSI. VALVE DISC SEATS SHALL BE <br />GRADE 1 BRONZE. <br />RESILIENT SEATED GATE VALVES CONFORMING TO AWWA SPECIFICATIONS C509-80 ARE ACCEPTABLE AND ARE REQUIRED <br />FOR FIRE HYDRANT INSTALLATIONS. <br />BUTTERFLY VALVES SHALL MEET OR EXCEED THE LATEST REVISIONS OF AWWA C504 WITH A DESIGN WORKING PRESSURE <br />OF 150.0 PSI. OPERATORS FOR BUTTERFLY VALVES TWENTY INCHES (20") AND SMALLER SHALL BE CLASS 150; LARGER <br />OPERATORS WILL BE AS SPECIFIED IN THE SPECIAL PROVISIONS AND DESIGNED FOR ACTUAL LINE CONDITIONS AS <br />COVERED IN AWWA C504, APPENDIX A. <br />VALVE ENDS SHALL BE MECHANICAL JOINT OR FLANGED IN ACCORDANCE WITH AWWA C500 UNLESS OTHERWISE <br />SPECIFIED. <br />VALVES FOR USE WITH FLANGED PIPE SHALL BE CAST WITH CLASS 125 FLANGES, DIMENSIONS AND DRILLING SHALL <br />CONFORM TO ASA B16.L FLANGE BOLT HOLES SHALL BE SPOT FACED IF FLANGE FILLETS INTERFERE WITH BOLT HEADS <br />AND NUTS. <br />CHECK VALVES ON PUMP DISCHARGE SHALL BE OUTSIDE ARM WITH COUNTER WEIGHT AND SPRING CONTROL. <br />THE INLET FLANGE FOR TAPPING GATE VALVES SHALL BE PROVIDED WITH CLASS 125 FLANGE FOR ATTACHING TO <br />TAPPING SLEEVE. THE FLANGE SHALL HAVE A MACHINED PROJECTION COMPATIBLE WITH A MACHINED RECESS IN THE <br />TAPPING SLEEVE. THE OUTLET OF THE VALVE SHALL BE PROVIDED WITH A FLANGE FOR TAPPING MACHINE MOUNTING. <br />TAPPING SLEEVES SHALL BE MECHANICAL JOINT AND FLANGE UNLESS DEVIATION IS PERMITTED BY THE COUNTY. <br />ALL STEM SEALS, GATE VALVES AND BUTTERFLY VALVES, SHALL BE 00" RINGS ONLY. <br />WRENCH NUTS SHALL BE MADE OF TOP GRADE CAST IRON, FITTING THE TOP OF THE VALVE STEM AND SECURED BY <br />NUT OR KEY. WRENCH NUTS SHALL BE ONE AND FIFTEEN -SIXTEENTHS INCH (1-15/16") SQUARE AT THE TOP AND TWO <br />INCHES (2") SQUARE AT THE BOTTOM. <br />VALVES REQUIRING OPERATING WRENCHES EXCEEDING SIX FEET (6') IN LENGTH SHALL HAVE EXTENSION AND GUIDES <br />INSTALLED IN VALVE BOXES. <br />THE OPEN DIRECTION SHALL BE LEFT (COUNTERCLOCKWISE) AND THE CLOSED DIRECTION RIGHT (CLOCKWISE). <br />GST IRON FITTINGS. CAST IRON FITTINGS SHALL BE CLASS D FITTINGS CONFORMING TO ASTM DESIGNATION 126 AND <br />SHALL BE 150 POUNDS. ALL VALVES AND FITTINGS SHALL BE FLANGED. <br />VALVE BOXES, VALVE BOXES AND COVERS SHALL CONFORM TO SAN JOAQUIN COUNTY STANDARD DRAWINGS. <br />GAS$E17S, GASKETS FOR FLANGED JOINTS SHALL BE FULL -CIRCLE ONE -SIXTEENTH INCH (1/16") COMPOSITION GASKETS. <br />THRUST BLOCKS. THRUST BLOCKS SHALL BE INSTALLED AT ALL BENDS AND FITTINGS AND SHALL CONFORM TO SAN <br />JOAQUIN COUNTY STANDARD DRAWINGS. CONCRETE FOR THRUST BLOCKS SHALL BE CLASS B IN ACCORDANCE WITH <br />SECTION 90, "PORTLAND CEMENT CONCRETE; OF THE STANDARD SPECIFICATIONS. <br />FIRE HYDRANTS. FIRE HYDRANTS SHALL CONFORM TO THE REQUIREMENTS OF THE FIRE DEPARTMENT OF THE COUNTY OF <br />SAN JOAQUIN AS SHOWN ON THE STANDARD DRAWINGS AND THE FOLLOWING: <br />A. ALL HYDRANTS SHALL COMPLY WITH AWWA C502, LATEST REVISION. <br />B. ALL OPERATING VALVES SHALL BE LOCATED BELOW GRADE AND PROTECTED BY 'BREAK -OFF" FEATURES SO THAT <br />NO WATER FLOWS IF HYDRANT IS KNOCKED OFF. <br />C. HYDRANT MAIN VALVE SEAT SHALL BE A MINIMUM FIVE AND ONE-QUARTER INCHES (5-1/4). <br />D. HYDRANT VALVE SHALL BE MOLDED NONSWELLING RUBBER. <br />E. HYDRANT MAIN VALVE SEAT SHALL BE THREADED INTO A BRONZE TO BRONZE SUBSEAT. <br />;F. HYDRANT BURY SHALL BE THIRTY-SIX INCHES (36") FROM CONNECTION TO GROUND FLANGE. MATERIALS TO <br />EXTEND THE LENGTH OF BURY MUST BE READILY AVAILABLE. <br />SERVICE LINES. SERVICE LINES UP TO AND INCLUDING METER CONNECTION SHALL BE AS DETAILED IN SAN JOAQUIN <br />COUNTY STANDARD DRAWINGS, AS APPLICABLE FOR THE SERVICE INTENDED AND WITH THE AWWA STANDARD C800, <br />EXCEPT AS HEREINAFTER MODIFIED OR AS MODIFIED BY THE PLANS AND THESE SPECIAL CONDITIONS. <br />1. TYPE OF SERVICE LINE PIPE SHALL BE LIMITED TO THE FOLLOWING: <br />A. COPPER WATER TUBE, TYPE K OR ASTM B-88. <br />B. ULTRA HIGH MOLECULAR WEIGHT (UHMW) P.E. 3406, P.E. 3408, CS 255-63, POLYETHYLENE AS MANUFACTURED <br />BY DRISCOPIPE, ORANGEBURG OR AN APPROVED EQUAL IN ONE INCH (1") IRON PIPE SIZES ONLY. PLASTIC PIPE LARGER <br />THAN ONE AND ONE-QUARTER INCH (1-1/4") AND UP TO AND INCLUDING TWO INCH (2') IRON PIPE SIZES SHALL BE <br />PB 2110 POLYBUTYLENE. CONNECTION OF PLASTIC PIPE SHALL BE MADE USING MUELLER 110 COMPRESSION <br />CONNECTIONS OR APPROVED EQUAL. <br />BENCH MARK: <br />PER U.S.G.S. B.M. 19-8 1907-45. <br />LOCATION: NORTHWEST CORNER OF MASONIC <br />BUILDING IN THE TOWN OF WOODBRIDGE. <br />ELEVATION: 45.85 IS MOST CURRENT PER <br />F.E.M.A. <br />DATE SIGNED: x • t 4 <br />SPECIFICATIONS FOR COLD WATER DISPLACEMENT, TYPE A, AWWA C700-77, OR LATEST EDITION. <br />1. GENERAL <br />METERS SHALL BE THE LATEST MODELS, MUST HAVE BEEN CATALOGUED FOR MORE THAN FOUR (4) YEARS, AND MUST <br />BE MANUFACTURED BY A COMPANY WITH A MINIMUM OF TEN (10) YEARS EXPERIENCE IN THE MANUFACTURE OF WATER <br />METERS. <br />SERIAL NUMBERS SHALL BE CLEARLY AND PERMANENTLY IMPRINTED ON THE DIAL UD OR BODY. <br />ALL METERS SHALL BE OF THE POSITIVE DISPLACEMENT NUTATING AND OSCILLATING TYPE. METERS SHALL BE FURNISHED <br />WITHOUT COUPLINGS OR COMPANION FLANGES. <br />METER BODY SHALL BE BRONZE, SPLIT CASE DESIGN, AND SHALL BE JOINED TOGETHER BY NOT FEWER THAN FOUR (4) <br />BOLTS. BOLTS AND WASHERS SHALL BE BRONZE OR STAINLESS STEEL. <br />REGISTER CHAMBER SHALL BE BRONZE, STAINLESS STEEL OR PLASTIC MATERIAL. PROVIDED THAT, IF PLASTIC MATERIAL, <br />THE REGISTER CHAMBER SHALL BE PROTECTED BY A BRASS OR COPPER LINER HERMETICALLY SEALED TO PREVENT <br />INCURSION OF MOISTURE AND DIRT. LENS SHALL BE GLASS SEALED TO LINER. REGISTER CHAMBER SHALL CONTAIN A <br />DESICCATING CAPSULE. <br />ALL PARTS SHALL BE DESIGNED SO THAT THEY ARE INTERCHANGEABLE WITH COMPARABLE SIZE METERS OF THE SAME <br />MAKE. <br />METERS MAY BE TESTED UPON DELIVERY AND SHALL REGISTER IN ACCORDANCE WITH AWWA SPECIFICATIONS. ANY METER <br />NOT MEETING THESE SPECIFICATIONS WILL BE SUBJECT TO REJECTION. <br />METERS FURNISHED UNDER THESE SPECIFICATIONS SHALL BE GUARANTEED TO OPERATE UNDER A WORKING WATER <br />PRESSURE OF ONE HUNDRED -FIFTY (150) POUNDS PER SQUARE INCH WITHOUT LEAKAGE OR DAMAGE TO ANY PART. <br />DIAL SHALL BE STRAIGHT READING, WITH THE LAST ZERO SHOWN IN WHITE ON BLACK, AND THE PRECEDING NUMERAL <br />OR ODOMETER WHEEL WHITE ON BLACK, AND ALL OTHER PRECEDING ODOMETER WHEELS SHOW NUMERALS IN BLACK ON <br />WHITE. METERS SHALL READ IN GALLONS. <br />LENS SHALL BE OF HEAVY GLASS MATERIAL AND SHALL WITHSTAND THE EFFECT OF A TWO (2) OUNCE STEEL BALL <br />DROPPED FROM A HEIGHT OF TEN FEET (10'). <br />ALL PARTS OF THE REGISTERS SHALL BE MADE OF NONFERROUS OR CORROSION -RESISTANT MATERIALS. <br />2. CHAMBERS AND DISCS <br />METERS EQUIPPED WITH DISCS OF THE FLAT TYPE SHALL BE PROVIDED WITH THRUST ROLLERS MADE OF HARD ROLLED <br />PHOSPHOR BRONZE OR EQUALLY SUITABLE MATERIAL. THE THRUST ROLLER SHAFT SHALL BE SOLIDLY ATTACHED TO THE <br />THRUST ROLLER HEAD, AND ROTATE FREELY IN THE DISC PLATE. IN THE ONE AND ONE-HALF INCH (1 1/2") AND TWO <br />INCH (2") METERS, ONLY THE PART OF THE ROLLER PROTRUDING FROM THE DISC PLATE SHALL BE HARD RUBBER <br />MOUNTED. <br />3. ORIGINAL METER WEAR AND TEAR ALLOWANCE <br />MAGNETIC DRIVE, GEAR TRAIN AND DIAL SHALL BE GUARANTEED FOR A PERIOD OF TEN (10) YEARS. SHOULD FAILURE <br />OCCUR FOR ANY CAUSE, VANDAUSM AND ABUSE EXCEPTED, DURING THE PERIOD OF THE GUARANTEE, THE COMPLETE <br />UNIT SHALL BE REPLACED BY THE SUPPLIER AT NO COST TO THE WATER PURVEYOR. <br />4. MEASURING CHAMBER <br />MEASURING CHAMBER SHALL BE GUARANTEED FOR A PERIOD OF EIGHT (8) YEARS. CHAMBER SHALL BE DESIGNED TO <br />ALLOW PASSAGE OF SAND GRAINS OF NOT GREATER SIZE THAN 50 MESH ASTM, WITHOUT CAUSING STOPPAGE OR <br />CAUSING INCORRECT READING OF MORE THAN ONE-HALF PERCENT (.5%) PER YEAR TESTED AT FLOWS OF FIVE (5) GPM. <br />5. MEASURING CHAMBER TOLERANCE ALLOWANCE <br />AN ALLOWANCE OF ONE-HALF PERCENT (.5%) LOSS OF ACCURACY PER YEAR FOR WEAR AND TEAR DEPRECIATION WILL <br />BE ALLOWED. IF STATED TOLERANCES ARE EXCEEDED AT ANY TIME WITHIN THE PERIOD OF GUARANTEE, THE SUPPLIER <br />SHALL REPLACE THE ENTIRE MEASURING CHAMBER, CASE AND COMPLETE DISC AT NO COST TO THE WATER PURVEYOR. <br />THE COUNTY MAY REMOVE METER ON OR BEFORE ROUTINE MAINTENANCE CHANGE AND WILL TEST METER ON TEST <br />BENCH PRIOR TO ANY REPAIRS TO DETERMINE ACCURACY AND CONDITION OF METER. SHOULD REMOVED METER NOT <br />PERFORM WITHIN THE PERMITTED TOLERANCES, SUCH METER SHALL BE AGAIN TESTED IN THE PRESENCE OF SUPPLIERS <br />REPRESENTATIVE, DISMANTLED IN HIS PRESENCE, AND CAUSE OF FAILURE DETERMINED TO SATISFACTION OF BOTH THE <br />WATER PURVEYOR AND THE SUPPLIER. <br />UNLESS OTHERWISE SPECIFICALLY NOTED, WATER METERS SHALL BE PURCHASED BY DEVELOPER AND DELIVERED TO <br />UTILITIES MAINTENANCE DIVISION. <br />FOR METERS LARGER THAN TWO INCHES (2"), IT WILL BE THE CONTRACTOR'S RESPONSIBILITY TO CONTACT THE COUNTY <br />OF SAN JOAQUIN PRIOR TO INSTALLATION OF METER BOXES TO ASCERTAIN THE DIMENSIONS OF THE METERS. <br />IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO SET METER BOX AND SERVICE FITTINGS IN SUCH A MANNER THAT <br />METER CAN EASILY BE DROPPED IN PLACE. <br />AIR RELIEF VALVE THIS WORK SHALL CONSIST OF INSTALLING AIR RELIEF VALVES ON THE WATER MAINS AND SHALL <br />INCLUDE THE INSTALLATION OF THE WATER MAIN SADDLE TAP, PIPING TO THE RELIEF VALVE, VALVE HOUSING ASSEMBLY <br />AND ALL NECESSARY FIXTURES, FITTINGS AND EQUIPMENT TO PROVIDE AIR RELIEF VALVES COMPLETE AND IN PLACE AS <br />SHOWN ON THE PLANS AND AS SPECIFIED IN THESE SPECIAL PROVISIONS. <br />AIR RELIEF VALVE SHALL BE A UNIVERSAL TYPE AIR AND VACUUM AND PRESSURE RELIEF AIR VALVE, CRISPIN MODEL NO. <br />U10, OR APPROVED EQUAL. <br />INSrALLATION--THE CONTRACTOR SHALL, UNLESS SPECIFIED OTHERWISE, FURNISH ALL MATERIAL, EQUIPMENT, TOOLS, <br />AND LABOR NECESSARY TO DO THE WORK REQUIRED, AND UNLOAD, HAUL AND DISTRIBUTE ALL PIPE, CASTINGS, FITTINGS, <br />VALVES, HYDRANTS AND ACCESSORIES. THE CONTRACTOR SHALL ALSO REMOVE PAVEMENT AS STIPULATED; EXCAVATE <br />TRENCHES AND PITS TO THE REQUIRED DIMENSIONS; EXCAVATE BELL HOLES; CONSTRUCT AND MAINTAIN ALL BRIDGES <br />FOR TRAFFIC CONTROL SHEET, BRACE, AND SUPPORT AND ADJOINING GROUND OR STRUCTURES WHERE NECESSARY; <br />HANDLE ALL DRAINAGE OR GROUND WATER; PROVIDE BARRICADES, GUARDS, AND WARNING LIGHTS; LAY AND TEST THE <br />PIPE, CASTINGS, FITTINGS, VALVES, HYDRANTS, AND ACCESSORIES; BACKFILL AND CONSOLIDATE THE TRENCHES AND PITS; <br />RESTORE THE ROADWAY SURFACE UNLESS OTHERWISE STIPULATED; REMOVE SURPLUS EXCAVATED MATERIAL; CLEAN THE <br />SITE OF THE WORK; AND MAINTAIN THE STREET OR OTHER SURFACE OVER THE TRENCHES AS SPECIFIED. <br />WATER MAINS. THE PIPE SHALL BE HANDLED WITH CARE AT ALL TIMES AND IN A MANNER THAT MEETS THE APPROVAL <br />OF THE ENGINEER. EXTREME CARE SHALL BE EXERCISED IN THE USE OF ANY MECHANICAL DEVICES USED IN LAYING <br />THE PIPE TO AVOID SCARRING OR OTHER DAMAGE. <br />THE COUNTY SHALL BE THE JUDGE OF WHETHER A PIPE IS SERIOUSLY DAMAGED AND ANY PIPE SO CLASSIFIED SHALL <br />BE PERMANENTLY REMOVED FROM THE SITE OF THE WORK. <br />THE INSIDE OF ALL PIPES AND COUPLINGS SHALL BE FREE FROM DIRT, GREASE, OR OTHER DELETERIOUS MATERIALS. <br />THE OPEN ENDS OF ALL PIPE PREVIOUSLY LAID SHALL BE ADEQUATELY PLUGGED WATER TIGHT WHENEVER PIPE LAYING <br />OPERATIONS ARE SUSPENDED AT THE END OF EACH WORK DAY, OR FOR ANY OTHER REASON. <br />SELECT MATERIAL SHALL BE PLACED AND THOROUGHLY COMPACTED ACROSS THE BOTTOM OF THE TRENCH TO PROVIDE <br />FULL SUPPORT OF ALL THE PIPE. BELLS AND/OR COUPLINGS SHALL HAVE SOIL REMOVED TO PROVIDE A UNIFORM <br />BEARING. <br />ALL CONNECTIONS TO EXISTING LINES SHALL BE MADE WITH FLANGED FITTINGS WITH ISOLATION PLATES. CONNECTION <br />DETAILS SHALL BE SUBJECT TO APPROVAL BY THE COUNTY. <br />WATER SERVICES. THIS WORK SHALL CONSIST OF INSTALLING WATER SERVICE CONNECTIONS CONSISTING OF WATER MAIN <br />SADDLE TAPS, SERVICE LINES, METER BOXES, METERS AND ALL NECESSARY FIXTURES AND FITTING TO PROVIDE WATER <br />SERVICE CONNECTIONS AS SHOWN ON THE PLANS AND AS SPECIFIED IN THESE SPECIAL PROVISIONS. <br />EXCAVATION AND BACKFILL EXCAVATION AND BACKFILL SHALL CONFORM TO THE PROVISIONS IN SECTION 19C, <br />"EARTHWORK (STRUCTURE EXCAVATION AND BACKFILL)," OF THESE SPECIAL PROVISIONS. <br />CA: 800-227--2600-- <br />NV: R00-2°7--'600- <br />/ ':'•: <br />'EARTHWORK (STRUCTURE EXCAVATION AND BACKFILL); OF THESE SPECIAL PROVISIONS. <br />THE PIPE SHALL BE LAID IN A TRENCH EXCAVATED TO THE LINES AND GRADES DESIGNATED BY THE ENGINEER. THE <br />BOTTOM OF THE TRENCH SHALL BE GRADED AND PREPARED TO PROVIDE A FIRM AND UNIFORM BEARING THROUGHOUT <br />THE ENTIRE LENGTH OF THE PIPE BARREL <br />SUITABLE EXCAVATION SHALL BE MADE TO RECEIVE THE BELL OF THE PIPE AND THE JOINT SHALL NOT BEAR UPON THE <br />BOTTOM OF THE TRENCH. ALL ADJUSTMENT TO UNE AND GRADE SHALL BE MADE BY SCRAPING AWAY OR FILLING IN <br />WITH SAND, GRAVEL, OR GRANULAR MATERIAL UNDER THE BODY OF THE PIPE, AND NOT BY WEDGING OR BLOCKING. <br />TRENCHES SHALL NOT BE LEFT OPEN FARTHER THAN THREE HUNDRED FEET (300') IN ADVANCE OF PIPE LAYING <br />OPERATIONS OR TWO HUNDRED FEET (200') TO THE REAR THEREOF, UNLESS OTHERWISE PERMITTED BY THE DIRECTOR. <br />THE EXCAVATION SHALL BE SUPPORTED SO THAT IT WILL BE SAFE AND THAT THE GROUND ALONGSIDE THE EXCAVATION <br />WILL NOT SLIDE OR SETTLE, AND ALL EXISTING IMPROVEMENTS, EITHER ON PUBLIC OR PRIVATE PROPERTY, WILL BE <br />FULLY PROTECTED FROM DAMAGE. <br />ALL SUPPORTS SHALL BE REMOVED AFTER CONSTRUCTION IS COMPLETED, UNLESS OTHERWISE DIRECTED BY THE <br />ENGINEER, AND SHALL BE WITHDRAWN IN A MANNER THAT WILL PREVENT THE CAVING OF THE SIDES OF THE <br />EXCAVATION. ALL OPENINGS CAUSED BY THE REMOVAL OF SUPPORTS SHALL BE FILLED WITH SUITABLE MATERIAL <br />PROPERLY COMPACTED. <br />BACKFILL MATERIALS SHALL BE PLACED ON BOTH SIDES OF THE PIPE SIMULTANEOUSLY TO PREVENT ANY UNDUE STRAIN <br />ON THE PIPE. <br />COMPACTING EQUIPMENT OR METHODS THAT MAY DAMAGE THE PIPE OR CAUSE EXCESSIVE DISPLACEMENT SHALL NOT BE <br />USED. <br />ALL PIPE DAMAGED DURING CONSTRUCTION OPERATIONS SHALL BE REPLACED BY THE CONTRACTOR AT HIS EXPENSE TO <br />THE SATISFACTION OF THE ENGINEER. <br />TRENCH RESURFACING. TRENCHES IN EXISTING STREETS SHALL BE RESURFACED WITH THE TYPE AND THICKNESS OF <br />BASES, SURFACING OR PAVEMENT SHOWN ON THE PLANS AND/OR STANDARD DRAWING. <br />THE CONTRACTOR SHALL PROCEED IMMEDIATELY TO RESURFACE ANY PART OF ANY EXCAVATION UPON NOTICE FROM THE <br />COUNTY WITHOUT WAITING FOR COMPLETION OF THE FULL LENGTH OF LINE. <br />TESTING, THE TEST FOR HYDROSTATIC PRESSURE SHALL COMMENCE NO SOONER THAN SEVEN (7) DAYS AFTER THE LAST <br />CONCRETE THRUST BLOCK HAS BEEN CAST WITH STANDARD CEMENT OR AT LEAST AFTER THIRTY-SIX (36) HOURS WITH <br />HIGH EARLY STRENGTH CEMENT, AND AFTER BACKFILLING AND COMPACTING THE TRENCH TO THE PLANE UPON WHICH <br />THE ASPHALT CONCRETE SURFACING IS TO BE PLACED. THE CONTRACTOR SHALL TAKE THE NECESSARY PRECAUTIONS TO <br />ENSURE THAT THE PIPE FITTINGS, COUPLINGS, VALVES, AND OTHER APPURTENANCES ARE NOT DISPLACED DURING THE <br />TEST. TWENTY-FOUR (24) HOURS PRIOR TO THE TIME OF THE TEST, THE SECTIONS OF PIPE TO BE TESTED SHALL BE <br />FILLED WITH WATER, AND CARE SHALL BE EXERCISED TO ASSURE REMOVAL OF ALL AIR FROM THE PIPE. AFTER THE <br />TWENTY-FOUR (24) HOUR PERIOD, THE COMPLETED PIPE SECTIONS TO BE TESTED SHALL BE SUBJECTED TO A <br />HYDROSTATIC TEST PRESSURE OF ONE HUNDRED FIFTY (150) POUNDS PER SQUARE INCH FOR TWO (2) HOURS. DURING <br />THIS PERIOD THE TEST PRESSURE SHALL BE MAINTAINED AND THE AMOUNT OF MAKE-UP WATER MEASURED. THE <br />LEAKAGE RATE FOR THIS TEST SHALL NOT EXCEED 0.01 GALLONS FOR EACH INCH OF DIAMETER FOR EACH PIPE JOINT <br />IN THE SECTION BEING TESTED. <br />ANY LEAKS, FAILURES, OR IMPERFECT CONSTRUCTION REVEALED DURING THE TEST PERIOD SHALL BE CORRECTED BY <br />THE CONTRACTOR AT HIS OWN COST AND EXPENSE. THE CONTRACTOR SHALL REPAIR ALL DEFECTS, FILL AND <br />RECOMPACT THE TRENCH AND RETEST THE SECTION OF LINE UNTIL SATISFACTORY RESULTS ARE OBTAINED. <br />INTERRUPTION OF SERVICE NO VALVE OR OTHER CONTROL ON AN EXISTING SYSTEM SHALL BE OPERATED FOR ANY <br />PURPOSE BY THE CONTRACTOR. THE CONTRACTOR SHALL COORDINATE WITH [ 1* AND SAN JOAQUIN COUNTY <br />PUBLIC WORKS TO OPERATE ANY VALVE, HYDRANT, BLOWOFF OR CURB STOP. THE CONTRACTOR SHALL GIVE A MINIMUM <br />OF TWENTY-FOUR (24) HOURS NOTICE PRIOR TO THE TIME OF PROPOSED INTERRUPTION. INTERRUPTIONS OF SERVICE <br />SHALL NOT EXCEED FOUR (4) HOURS. <br />DISINFECTING WATER MAINS --THE CONTRACTOR SHALL FURNISH ALL MATERIALS, EQUIPMENT, TOOLS AND LABOR <br />NECESSARY TO DO THE WORK REQUIRED TO DISINFECT THE NEW WATER MAINS AS SPECIFIED IN THESE SPECIAL <br />PROVISIONS AND AS DIRECTED BY THE COUNTY. THE INTERIOR OF ALL PIPE, FITTINGS, AND OTHER ACCESSORIES SHALL <br />BE KEPT AS FREE AS POSSIBLE FROM DIRT, FOREIGN MATERIAL AND BACTERIA AT ALL TIMES. DURING PIPE LAYING <br />OPERATIONS, WHEN BACTERIAL CONTAMINATION OF INTERIOR PIPE SURFACES IS OBVIOUS OR SUSPECTED BY THE <br />DIRECTOR, HE MAY ORDER SAID SURFACES TO BE SWABBED WITH AN APPROVED BACTERICIDAL SOLUTION. <br />DISINFECTION OF NEW WATER MAINS SHALL BE ACCOMPLISHED BY USING EITHER METHOD NO. 1 OR METHOD NO. 2 AS <br />SPECIFIED IN THESE SPECIAL PROVISIONS. <br />ISOLATION OF NEW MAINS, ALL NEW WATER LINES SHALL BE COMPLETELY ISOLATED FROM ALL EXISTING MAINS UNTIL <br />THEY HAVE BEEN TESTED AND DISINFECTED TO THE SATISFACTION OF THE DIRECTOR. NEW MAINS MAY BE FILLED FROM <br />EXISTING MAINS, BUT ONLY WHEN USING AN APPROVED TEMPORARY TAP ASSEMBLY. THE TEMPORARY TAP SHALL CONSIST <br />OF A SHUT OFF VALVE AND A STATE DEPARTMENT OF HEALTH SERVICES APPROVED REDUCED PRESSURE BACKFLOW <br />PREVENTION DEVICE. CONNECTION DETAILS SHALL BE SUBMITTED TO THE DIRECTOR FOR APPROVAL PRIOR TO <br />INSTALLATION. <br />* ADD NAME OF CSA OR MAINTENANCE DISTRICT <br />WHEN THE NEW MAIN IS PROPERLY DISINFECTED AND THE ISOLATION DAM IS REMOVED FROM CONNECTION FLANGE OR <br />OTHER TYPE CONNECTION IS MADE, EXTREME CARE SHALL BE EXERCISED TO PREVENT THE ENTRY OF CONTAMINATION. <br />CONNECTION FITTINGS SHALL BE THOROUGHLY SWABBED WITH AN APPROVED BACTERICIDE IMMEDIATELY PRIOR TO THEIR <br />INSTALLATION. <br />FLUSH THE MAINS THOROUGHLY AT THE END OF THE CONTACT PERIOD. THE ORTHOTOLIDINE TEST SHALL SHOW NO MORE <br />CHLORINE IN THE WATER LEAVING THE MAIN THAN IN THE WATER ENTERING THE MAIN. <br />THE CONTRACTOR SHALL COLLECT A SAMPLE FOR BACTERIOLOGICAL EXAMINATION IN A STERILE BOTTLE PROVIDED BY <br />THE LABORATORY. ON THE LABEL, GIVE DATE, ADDRESS, AND THE NAME OR NUMBER FOR THE PROJECT. WHERE <br />POSSIBLE THE SAMPLE SHOULD BE TAKEN FROM A SERVICE LOCATED NEAR THE END OF THE CHLORINATION SECTION, <br />OTHERWISE, IT MAY BE TAKEN THROUGH THE SAME BLOWOFF USED FOR FLUSHING THE HEAVILY CHLORINATED WATER <br />OUT OF THE MAIN SO THAT THE BLOWOFF IS STERILIZED. <br />IF THE BACTERIOLOGICAL TESTS ARE UNSATISFACTORY, THE MAIN SHALL BE RESTERILZED USING METHOD NO. 2, AND <br />THE STERILIZATION REPEATED, IF NECESSARY, UNTIL SATISFACTORY RESULTS ARE OBTAINED. <br />1. METHOD NO. 1 - H.T.H. TABLET METHOD, THIS METHOD IS PREFERRED FOR SHORT JOBS AND FOR SMALL <br />DIAMETER PIPE OF ANY KIND. IT CANNOT BE USED WHERE TRENCH WATER HAS ENTERED THE MAIN. THE MAIN CANNOT <br />BE FLUSHED PRIOR TO STERILIZATION, SO THE METHOD REQUIRES THAT THE PIPE BE KEPT CLEAN DURING INSTALLATION. <br />USING PERMATEX NO. 1 AS AN ADHESIVE, FASTEN THE REQUIRED NUMBER OF TABLETS (SEE TABLE 1) TO THE INSIDE <br />TOP OF EACH LENGTH OF PIPE. THE TABLETS MAY BE FASTENED TO THE PIPE BEFORE IT IS PLACED IN THE TRENCH <br />PROVIDING THE TOP OF THE PIPE IS MARKED TO ENSURE THAT THE TABLETS ARE ON THE TOP OF THE PIPE AFTER <br />INSTALLATION. <br />WHEN USING DRESSER OR SIMILAR COUPLINGS, AN ADDITIONAL TABLET SHALL. BE CRUSHED AND PLACED IN THE <br />ANNULAR SPACE BETWEEN THE COUPLING AND THE PIPE. FILL THE PIPE VERY SLOWLY AND PROCEED AS OUTLINED <br />UNDER GENERAL INSTRUCTIONS OF THE MANUFACTURER. <br />METHOD N0. 2 - H.T.H. SOLUTION WITH HAND PUMP METHOD, THIS METHOD IS GENERAL IN SCOPE AND MUST BE USED <br />WHEN IT IS NECESSARY TO RECHLORINATE AN EXISTING MAIN. WHEN THIS METHOD IS USED ON A MAIN COUPLED WITH <br />DRESSER OR SIMILAR COUPLINGS, A PINCH OF H.T.H. POWDER SHALL BE PLACED IN EACH COUPLING AS THE MAIN IS <br />LAID. EQUIPMENT REQUIRED INCLUDES AN ORDINARY HAND TEST PUMP, SOLUTION HOSE, AND A FIVE (5) GALLON CAN <br />TO CONTAIN THE CHLORINE SOLUTION. <br />A COMPACT AND CONVENIENT ASSEMBLY CAN BE MADE BY MOUNTING THE SOLUTION CAN AND THE PUMP ON A <br />SUITABLE BOARD WITH A PIPE CONNECTION FROM THE TANK ON THE SUCTION SIDE OF THE PUMP. <br />No.I DESCRIPTION <br />H.T.H. COMES AS A POWDER WHICH MUST BE DISSOLVED IN WATER. STRONG CHLORINE SOLUTIONS SHOULD BE <br />HANDLED WITH CARE ACCORDING TO MANUFACTURER'S INSTRUCTIONS. <br />MAKE UP CHLORINE SOLUTION ACCORDING TO TABLE II. THE QUANTITY REQUIRED IS ESTIMATED FROM TABLE II. AN <br />EXCESS VOLUME SHOULD BE PREPARED SO AS NOT TO EMPTY THE CONTAINER BEFORE THE JOB IS COMPLETE. <br />CONNECT PUMP TO MAIN. USE A CORPORATION COCK FOR THIS PURPOSE AND MAKE CONNECTION AT OR AHEAD OF <br />THE INLET END OF THE NEW LINE. <br />AFTER FINISHING APPLICATION OF CHLORINE, CLOSE VALVE OR BLOWOFF. DISCONNECT AND FLUSH PUMP THOROUGHLY <br />WITH FRESH WATER. <br />IF THE ABOVE PROCEDURE HAS TO BE VARIED BECAUSE OF SOME UNUSUAL CONDITION, IT WILL BE NECESSARY ONLY <br />TO REGULATE THE PUMP, CONTROL THE WATER FLOW, OR ADJUST THE STRENGTH OF THE CHLORINE SOLUTION TO GIVE <br />A DOSE OF AT LEAST FIFTY (50) PPM. <br />TABLE I <br />NUMBER OF TABLETS REQUIRED FOR <br />MAIN STERILIZATION <br />Diameter of Pipe <br />Length of Section 2" 4" 6" 8" 10" 12" <br />13' or Less <br />1 <br />1 <br />2 <br />2 <br />3 <br />5 <br />18' <br />1 <br />1 <br />2 <br />3 <br />5 <br />6 <br />20' <br />1 <br />1 <br />2 <br />3 <br />5 <br />7 <br />30' <br />1 <br />2 <br />3 <br />5 <br />7 <br />10 <br />40' <br />1 <br />2 <br />4 <br />6 <br />9 <br />14 <br />OOSE A SUITABLE DISCHARGE RATE AND DETERMINE THE TIME REQUIRED TO APPLY THE CHLORINE FROM TABLE III. <br />COMPARE THE GALLONS OF SOLUTION REQUIRED BY DIVIDING THIS TIME BY THREE (3). <br />USE THE ABOVE TABLE TO DETERMINE THE STRENGTH OF SOLUTION REQUIRED. EXAMPLE: IF THE ESTIMATE TIME FROM <br />TABLE III IS THIRTY-FIVE (35) MINUTES, 11-2/3 GALLONS WILL BE REQUIRED; AND IF THE DISCHARGE RATE IS FIFTY <br />(50) GPM, THE SOLUTION SHOULD CONTAIN ONE (1) POUND OF H.T.H. IN FIVE (5) GALLONS. PREPARE FIFTEEN (15) <br />GALLONS OF SOLUTION SO AS TO BE SURE OF HAVING AN ADEQUATE AMOUNT. <br />OPERATE THE HAND PUMP AT A RATE OF FIVE (5) GALLONS IN FIFTEEN (15) MINUTES, OR ONE (1) GALLON IN THREE <br />(3) MINUTES. <br />TABLE III <br />Time in Minutes to Apply <br />TABLE II <br />Feet <br />HAND <br />CHLORINE SOLUTION STRENGTH <br />PUMP METHOD OF MAIN CHLORINATION <br />Amount of <br />chemical in 5 Gallons of <br />Solution <br />Discharge <br />GPM <br />Rate <br />H.T.H. <br />GPM <br />10 <br />0.25 <br />lbs. <br />20 <br />0.50 <br />lbs. <br />35 <br />0.75 <br />lbs. <br />5o <br />1.00 <br />lbs. <br />75 <br />1.50 <br />lbs. <br />100 <br />2.00 <br />lbs. <br />OOSE A SUITABLE DISCHARGE RATE AND DETERMINE THE TIME REQUIRED TO APPLY THE CHLORINE FROM TABLE III. <br />COMPARE THE GALLONS OF SOLUTION REQUIRED BY DIVIDING THIS TIME BY THREE (3). <br />USE THE ABOVE TABLE TO DETERMINE THE STRENGTH OF SOLUTION REQUIRED. EXAMPLE: IF THE ESTIMATE TIME FROM <br />TABLE III IS THIRTY-FIVE (35) MINUTES, 11-2/3 GALLONS WILL BE REQUIRED; AND IF THE DISCHARGE RATE IS FIFTY <br />(50) GPM, THE SOLUTION SHOULD CONTAIN ONE (1) POUND OF H.T.H. IN FIVE (5) GALLONS. PREPARE FIFTEEN (15) <br />GALLONS OF SOLUTION SO AS TO BE SURE OF HAVING AN ADEQUATE AMOUNT. <br />OPERATE THE HAND PUMP AT A RATE OF FIVE (5) GALLONS IN FIFTEEN (15) MINUTES, OR ONE (1) GALLON IN THREE <br />(3) MINUTES. <br />TABLE III <br />Time in Minutes to Apply <br />Chlorine to 100 <br />Feet <br />of <br />Pipe <br />Discharge Rate <br />PAVEMENT MARKINGS; <br />OF THE STANDARD SPECIFICATIONS. <br />z <br />GPM <br />2" 4" 6" <br />8" <br />10" <br />12" <br />DATE: 08/22/06 <br />SHEET OF <br />C-5 15 <br />10 <br />2 7 15 <br />26 <br />41 <br />59 <br />20 <br />3 7 <br />13 <br />20 <br />29 <br />35 <br />2 4 <br />8 <br />12 <br />17 <br />50 <br />3 <br />5 <br />8 <br />12 <br />75 <br />2 <br />4 <br />6 <br />8 <br />100 <br />3 <br />4 <br />6 <br />THE ABOVE TABLE IS USED TO ESTIMATE THE TIME REQUIRED TO APPLY CHLORINE. FOR EXAMPLE: SEVEN HUNDRED <br />FEET (700') OF EIGHT INCH (8") MAIN CAN BE FILLED WITH CHLORINE SOLUTION IN THIRTY-FIVE (35) MINUTES WITH A <br />DISCHARGE RATE OF FIFTY (50) GPM. <br />REDUCED PRESSURE BACKFLOW PREVENTER--THE REDUCED PRESSURE BACKFLOW PREVENTER SHALL BE A COMPLETE <br />ASSEMBLY, CONSISTING OF TWO (2) SEPARATE SPRING LOADED CHECK VALVES AND A DIFFERENTIAL RELIEF VALVE. <br />THESE DEVICES SHALL AUTOMATICALLY REDUCE THE PRESSURE IN THE "ZONE' BETWEEN THE CHECK VALVES. <br />BOTH CHECK VALVES AND THE DIFFERENTIAL RELIEF VALVE SHALL BE CONSTRUCTED SO THAT THEY MAY BE SERVICED <br />WITHOUT REMOVING THE DEVICE FROM THE LINE. THE DEVICES SHALL BE RATED TO 175.0 PSI WORKING PRESSURE. <br />THE REDUCED PRESSURE BACKFLOW PREVENTER SHALL BE AWWA OR USC APPROVED AND SHALL BE INSTALLED SO <br />THAT FLOODING WOULD NOT CAUSE THE RELIEF VALVE TO BECOME SUBMERGED. IT SHALL BE INSTALLED A MINIMUM OF <br />TWELVE INCHES (12") ABOVE GRADE. <br />SECTION 81 <br />MONUMENTS --MONUMENTS SHALL CONFORM TO THE REQUIREMENTS IN SECTION 81, "MONUMENTS; OF THE STANDARD <br />SPECIFICATIONS, STANDARD DRAWINGS AND THESE SPECIAL PROVISIONS. <br />THE CONTRACTOR SHALL PLACE PROTECTIVE MONUMENT FRAMES AND COVERS AT THE LOCATIONS SHOWN ON THE PLANS. <br />THE LOCATION OF THE MONUMENT FRAMES AND COVERS SHALL BE ESTABLISHED BY THE ENGINEER. <br />SECTION 84 <br />TRAFFIC STRIPES AND PAVEMENT <br />MARKINGS --TRAFFIC <br />STRIPES AND PAVEMENT <br />MARKINGS SHALL CONFORM TO THE <br />REQUIREMENTS IN SECTION 84, "TRAFFIC <br />STRIPES AND <br />PAVEMENT MARKINGS; <br />OF THE STANDARD SPECIFICATIONS. <br />SECTION 86 <br />STREET LIGHTS --STREET LIGHTS SHALL CONFORM TO THE REQUIREMENTS IN SECTION 86, 'SIGNALS, LIGHTING AND <br />ELECTRICAL SYSTEMS; OF THE STANDARD SPECIFICATIONS, THE SAN JOAQUIN COUNTY IMPROVEMENT STANDARDS AND <br />STANDARD DRAWINGS. <br />WW WOOD ESTATES <br />GENERAL N <br />PREPARED IN THE OFFICE OF: <br />ENCINEERIN6,INc. <br />)TES AND SPECIFICATIONS <br />• Civil Engineering <br />• Land Surveying <br />• Structural Engineering <br />• Planning <br />4045 Coronado Avenue • Stockton, CA 95204 <br />209 943-2021• Fax: 209 942-0214 <br />3 <br />w <br />0 <br />z <br />I <br />9 <br />DRAWN BY: <br />DJA <br />N <br />SCALE: <br />z <br />AS SHOWN <br />d <br />DATE: 08/22/06 <br />SHEET OF <br />C-5 15 <br />R.C.E. NO.: 62498 <br />JOB NO. <br />04251 <br />EXP DATE: 09/2007 <br />DRAWING FILE NO. <br />o <br />p <br />G- <br />i <br />4 <br />